7 / 15
Siemens Room temperature controller REV34.. CE1N2208en
Building Technologies 2017-11-15
Technical features
DIP switches
ON / OFF 1 2 3 4 5 6 7 8 9 10 See
See ASensor calibration On Medium-sized room
E
Sensor calibration Off Small room
BSetpoint limitation 16…35 °C Large room
Setpoint limitation 3…35 °C Medium-sized room
CTemperature display °F Normally sized heat output
F
Temperature display °C Undersized heat output
D
Start optimization: 1 h/°C Oversized heat output
Start optimization: ¼ h/°C Normally sized heat output
Start optimization: ½ h/°C Quartz G
Start optimization: Off Radio clock
HDIP switch reset
ON
1342
56 7 89
After you change one or several DIP switch positions, you must press the DIP switch reset button to reset the DIP switch (see
also Fig. ). Otherwise, the previous setting remains active!
H
Factory setting: All DIP switches to OFF
If the displayed room temperature does not match the measured room temperature, the
temperature sensor can be recalibrated.
Set DIP switch to ON and press the DIP switch reset button:
CAL symbol is displayed. The currently measured temperature flashes.
Press or to recalibrate by max. ± 5 °C.
Set DIP switch to OFF and press the DIP switch reset button to save the settings.
The minimum setpoint limitation of 16 °C prevents undesired heat transfer to
neighboring spaces in buildings featuring several heating zones.
DIP switch ON: Setpoint limitation 16…35 °C.
DIP switch OFF: Setpoint limitation 3…35 °C (factory setting).
Press the DIP switch reset button to save the settings.
DIP switch ON: Temperature display in °F.
DIP switch OFF: Temperature display in °C (factory setting).
Press the DIP switch reset button to save the settings.
Optimization advances the switch-on point P.1 to ensure that the selected setpoint is
reached at the desired time. The setting depends on the controlled system, i.e., on heat
transmission (piping system, radiators), building dynamics (building mass, insulation),
and heat output (boiler capacity, flow temperature).
DIP switches 4 ON and 5 ON: 1 h/°C For slow controlled systems.
DIP switches 4 ON and 5 OFF: ¼ h/°C For fast controlled systems.
DIP switches 4 OFF and 5 ON: ½ h/°C For medium controlled systems.
DIP switches 4 OFF and 5 OFF: OFF Off, no effect (factory setting).
Press the DIP switch reset button to save the settings.
ASensor calibration:
DIP switch 1
BSetpoint limitation:
DIP switch 2
C
°C or °F:
DIP switch 3
DStart optimization:
DIP switches 4 and 5