Graphic Annunciator Manual P/N 06-131 2/98
Page 3
Overview
The Fike 10-11XX Graphic Annunciator is an ancillary system designed for use with the Fike Intella-
ScanFire Alarm Control Panel. It is designed to provide remote status of an individual device, zone,
and system by illumination of a color LED(s). Each Graphic Annunciator is a customized design
(typically a building floor layout) defined by the customer. The LED indicators are available in four
individual colors to distinguish event type (Red, Yellow, Green, Orange). A typical Graphic viewing
window will illustrate building or zone detectors. When the Intella-Scan panel receives an alarm or
trouble, the Graphic Annunciator will illuminate the appropriate LED and sound the local piezo. The
illuminated LED will give the operator an instant locator to the appropriate alarm/trouble location. Two
diagnostic LED’s (‘MICRO COMPUTER OK and COMMUNICATION OK”) verify the system is
operating. All LED’s will blink OFF each time data is received from the Intella-Scan system. The blink
rate will vary depending on the size of the system and the other types of ancillary devices that are
connected. Four operator switches are located on the front of the panel door:
SILENCE - Press to silence the local piezo, when ON. The local piezo will sound each time an
event occurs.
TEST - Press to verify that each LED can illuminate. ALL LED’s will illuminate when
pressed.
REVIEW - Press and hold to review sequence of events, when used in conjunction with the
STEP switch. Review is used for detector address and system type LED’s only, it
will not review zone type LED’S.
STEP - While the REVIEW switch is pressed, press to chronologically step through
events. First press will illuminate first LED; second press will add the second
LED, etc. Systems with only one Micro board will step through LEDsin
chronological order. Systems with multiple Micro boards (JP6 should be installed
on each Micro board) will step through EVENTs in chronological order, whether
an LED was programmed for the event or not. Therefore, on a multiple Micro
board system, it is possible that the status of the LED display will not change if no
LED was programmed for the given event.
The Graphic Annunciator will turn ON only 1 LED at a time. The flash rate between each ON/OFF time
is so short, it appears to be constantly ON. This design allows many LED’s to appear ON at the same
time, with minimal current being drawn from the system. The Intella-Scan communicates to the Graphic
through a fiber optic connection. The Graphic is field programmable by using the Fike PGRAPHIC or
EGRAPHIC Software Program.
.