Voltage connection
Notes:
a. Shields should be connected at the signals source.
b. The 0V signal of the analog input must be connected to the controllers 0V.
Current connections
Notes:
a. Shields should be connected at the signals source.
b. The 0V signal of the analog input must be connected to the controllers 0V.
Analog Input 10-bit, multi-range input:
0-10V
0-20mA, 4-20mA
Conversion method Successive approximation
Input impedance >100KW for voltage
500W for current
Galvanic isolation None
Resolution (except 4-20mA) 10-bit (1024 units)
Resolution at 4-20mA 204 to 1023 (820 units)
Conversion time Synchronized to scan time
Absolute max. rating ±15V
Full scale error ± 2 LSB
Linearity error ± 2 LSB
Status indication Yes, see Note
Note:
The analog value can also indicate when the input is functioning out of range.
If an analog input deviates above the permissible range, its value will be 1024.
2
M91-19-R1 02/02
Display STN, LCD display
Illumination LED yellow-green backlight
Display size 1 line, 16 characters long
Character size 5 x 7 matrix, 3.07 x 5.73mm
Keypad Sealed membrane
Number of keys 15
LC program 2048 words
Bits/Coils 256
Integers/Registers 256
Timers 64
Execution time 12µsec. for bit operations
HMI displays 80 user-designed displays
HMI variables 50 HMI variables are available to
conditionally display and modify
text, numbers, dates, times & timer
values. The user can also create
a list of up to 120 variable
text displays, totaling up to 2K.
RS232 serial port Used for:
lApplication Download/Upload
lApplication Testing (Debug)
mode
lConnect to GSM or standard
telephone modem:
-Send/receive SMS messages
-Remote access programming
lRS485 Networking via
adapter: up to 32 nodes
I/O expansion port Up to 64 additional I/ s,
including digital & analog I/ s,
RTD and more.
Miscellaneous
Clock (RTC) Date and time-year 2000
compliant.
Battery back-up 7 years typical battery back-up for
RTC and system data.
Weight 310g (10.9 oz.)
perational temperature 0 to 50°C (32 to 122°F)
Storage temperature -20 to 60°C (-4 to 140°F)
Mounting method DIN-rail mounted (IP20/MENA1)
Panel mounted (IP65/NEMA4X)
Digital outputs
6 relay outputs, 230VAC/ 12/24VDC
utput type SPST-N relay
Type of relay Takamisawa (Fujitsu) JY-12H-K, or
NAIS (Matsushita) JQ1A-12V or
MR N G6B-1114P-12VDC
Isolation by relay
utput current 5A max. (resistive load)
1A max. (inductive load)
Max. frequency 10Hz
Contact protection External precautions required
L1, L2, L3 (115/230VAC)
Relay Outputs
+V (12/24VDC)
+V
0V
12 VDC
or 24 VDC
Circuit
protection
device
nitronic
US
4 wire
current
transmitter
ower
Supply
I1
I0 I3
I2 I4 I5 I6 I7 I8 AN
+
-
I9
+V
0V
12 VDC
or 24 VDC
Circuit
protection
device
nitronic
US
2 wire
current
transmitter
I1
I0 I3
I2 I4 I5 I6 I7 I8 I9 AN
+
-
+V
0V
12 VDC
or 24 VDC
Circuit
protection
device
nitronic
US
3 wire
current
transmitter
I1
I0 I3
I2 I4 I5 I6 I7 I8 I9 AN
+
-
+
+V
0V
12 VDC
or 24 VDC
Circuit
protection
device
nitronic
US
0-10V
I1
I0 I3
I2 I4 I5 I6 I7 I8 AN
+
-
I9