60IXD Installation Manual
8 INS261-3
Commissioning and Testing
Programming the 60IXD Expander (Local Mode)
Once the 60IXD expander module has been installed, the following procedure must be
carried out in order to enable the module:
1. Enter into the Engineers Menu !"#$.
2. Select the UDL/Digi Options menu %and press &.
3. Select the Com Port Setup menu 'and press &.
4. Select Expansion Port option $.
5. Press (to change and select iD Module option ", followed by &to
accept.
6. Exit from the Expansion Port menu by pressing ).
7. Exit from the Com Port Setup menu by pressing ).
8. The Comms Led on the expander module should now be flashing.
9. Select the Engineer Utils menu *and press &.
10. Select the View iD Data menu +and press &.
11. Follow the flowchart on the next page for viewing and programming the iD
biscuit options.
12. Once the iD biscuits have been mapped to zones on the system you can now
program them as you would normal zones, refer to the “Zone Setup” menu in
the Premier 48/88/168/640 Installation Manual.
Viewing the iD Data (Local Mode)
As shown on the flowchart on the next page you can view the iD biscuit data that
expander is reporting to the control panel. There are two way of viewing the data from
the expander:
Normal Scan Mode
This is the normal operation mode of the expander and the data being displayed is the
average result of 4 successive scans of the iD loop.
Quick Scan Mode
In this mode the data being displayed is the result of each scan of the iD loop. This
mode is useful for identifying problems with biscuits due to interference, high
resistance connections etc.