SEQUENCER CONTROLLER
WITH OR WITHOUT
DIFFERENTIAL PRESSURE MEASUREMENT
Page 6 sur 15 - 6 -Page 6 sur 15 - 6 - - 6 - - 6 - - 6 -
2) DP control selection:
Choose "AdP" or "SdP".
"AdP": for cycle controlled by the DP measurement.
"SdP": for cycle not controlled by the DP measurement.
3) Maxi DP setting:
If the DP measurement exceeds this threshold for longer than one second, the DP order becomes « on »
4) Mini DP setting:
If the DP measurement goes below the DP threshold for longer than one second, the DP order becomes
« off »
Note: If Maxi DP=Mini DP=000 then the DP order is mechanically controlled « on »
5) High DP Alarm Setting:
If the DP measurement goes above this threshold for longer than 5 seconds high DP alarm.
If the DP measurement goes below this threshold for longer than 5 seconds no high DP alarm
Note: if the high DP alarm is set at 000, it is inactive (no high alarm generated).
6) Low DP Alarm setting:
If the DP measurement goes below this threshold for longer than 5 seconds low DP alarm.
If the DP measurement goes above this threshold for longer than 5 seconds no low DP alarm.
Note: if the low DP alarm is set at 000, it is inactive (no low alarm generated).
7) Threshold for accelerated operation setting (T2A threshold):
If the DP measurement goes above this threshold for longer than 5 seconds accelerated operation.
If the DP measurement goes below this threshold for longer than 5 seconds normal operation
In accelerated operation, the T2 time is replaced by the T2A time.
Note: if this threshold is set at 000, the function is inactive (still in normal operation).
8) Cycle view:
If cleaning is running, display of the time countdown (T2, T3 or T2A if it’s equipped with the DP) with
rapid flashing of the led of the menu opposite the corresponding time.
If there is a fault, display of the type of fault.
If manual running or fan stoppage cycles are in course, the led-menu opposite the fan/manu flashes rapidly.
If key + pressed, display of nxx with xx = EV will be actuated at the next blast.
9) Type of stop setting:
Choose "Fcy" or "Sto".
"Fcy": to stop at the end of the cycle.
"Sto": to stop cycle to the running SV (stop on image).