Primex STATION VIEW Manual de usuario

STATION VIEWTM
DUPLEX PUMP CONTROLLER
User Manual
+1-844-4PRIMEX (477-4639)
WWW.PRIMEXCONTROLS.COM

TABLE OF CONTENTS
Introduction and Specifications ............................................. 1
Main Screen .......................................................................... 2
Keypad Operation ................................................................. 3
Main Menu Navigation .......................................................... 4
Active Alarms ........................................................................ 5
Alarm History......................................................................... 6
Alternation ............................................................................. 7
Datalog.................................................................................. 8
Set Levels ............................................................................. 9
Simulate .............................................................................. 10
Advanced Setup Navigation................................................ 11
System & Sensor ................................................................ 12
Flow .................................................................................... 13
Flow (continued) & Amps.................................................... 14
Dry Run & High Amp .......................................................... 15
Date/Time, Max Run Time, Password & Pump Data ......... 16
I/O Status ............................................................................ 17
I/O Configuration, Dimensions & Mounting......................... 18
PRIMEX®Station View™Controller User Manual

WARNINGS
Failure to read and understand the information provided in this manual may result in personal injury or
death, damage to the product or product failure. Please read each section in its entirety and be sure
you understand the information provided in the section and related sections before attempting any of
the procedures or operations given.
Failure to follow these precautions could result in serious injury or death.
Keep these instructions with warranty after installation. This product must be
installed in accordance with National Electrical Code, ANSI/NFPA 70 so as to
prevent moisture from entering or accumulating within the controller housing.
ELECTRICAL SHOCK HAZARD
A qualified service person must install and service this product
according to applicable codes and electrical schematics.
Disconnect power prior to servicing an equipment with the
Station View™controller.
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable liquids. Do not install in
hazardous locations as defined by National Electrical Code,
ANSI/NFPA 70.
• Do not connect power to this equipment if it has been damaged or has
any missing parts.
• The Station View™ contains no serviceable parts; do not attempt to
repair this equipment.
• Do not install in areas with: excessive or conductive dust, corrosive or
flammable gas, moisture or rain, excessive head, regular impact shocks,
or excessive vibration.
PRIMEX®Station View™Controller User Manual

INTRODUCTION & SPECIFICATIONS
Congratulations, and thank you for your purchase of the Station View™controller. This manual explains the
features and operations of the Station View™controller which was designed specifically for wastewater pump
stations. It can be configured to use a level transducer with two (2) back up float switches, or with four (4) float
switches without a level transducer.
GENERAL
Duplex pump controller.
4-20mA transducer with (optional) 2 back up floats (High + low)
Or 4 float Switches (Stop/Start/Lag/High level)
Pump amps monitoring
Pump flow monitoring (with level transducer)
Pump HOA selector switch in AUTO monitoring
Power loss monitoring
Graphic display with easy navigation and intuitive setup.
LCD backlit display. 128x64 pixels
Real Time clock
CONTROLLER FEATURES
Level/flow monitoring
Pump level in feet + bar graph
Float switch status indication (when using float switches)
Pump GPM. (using volumetric calculation with level transducer)
PUMP CONTROL AND PROTECTION
Automatic pump alternation
Alternation can be forced to start a particular pump first every time
Pump dry run protection (based on motor Amps + timer)
Pump run indication
Pump Amp indication (with current transducer)
SYSTEM
24hrs data log + 7 days of historical data
Volume pumped (with transducer)
Number of starts for each pump
Run time for each pump
Average GPM for each pump (with transducer)
Real time clock
Password protection
Alarm log
Level simulation (with level transducer)
ELECTRICAL SPECIFICATIONS
10 Digital inputs
2 analog inputs (4-20mA)
8 digital outputs (6 relay + 2 transistors)
24Vdc power, 5.2W
COMMUNICATION
SCADA compatible
Serial port: RS 485 Modbus RTU slave
Optional cellular remote monitoring (PRIMEX®PUMP WATCH™)
CERTIFICATION
UL /CE listed
POWER UP SCREEN & REVISION
®
PRIMEX®1 Station View™Controller User Manual

PROGRAMMING
MAIN SCREEN
The main screen gives the operator an overview of the lift station status.
Level Transducer Mode
Float Switches Mode
PRIMEX®2 Station View™Controller User Manual

KEY PAD OPERATION
The controller keypad is used for screen navigation and data entry.
PRIMEX®3 Station View™Controller User Manual

MAIN MENU NAVIGATION
Navigation from the Main screen to the Menu Screens.
Press to go back to the previous screen at any time.
PRIMEX®4 Station View™Controller User Manual

ACTIVE ALARMS
If an alarm event occurs, it is displayed on the message bar on the Main Screen. A flashing alarm bell
is also displayed.
Possible alarms include:
#DISPLAY DEFINITION FIX
0HIGH LEVEL XDCR Level in the wet well has exceeded the High
Level Set point
Check pump operation, check in ow, check
level transducer
1MAX RUN TIME Pump running longer than allowable Run time Check pump operation, check in ow, check
level transducer
2HIGH LEVEL FLOAT High level oat is ON (up) Check pump operation, check in ow, check
level transducer
3LOW LEVEL FLOAT Low level oat is OFF (down) Check transducer
4HIGH AMPS Pump amps higher than expected (after time
delay)
Check pump, check voltage
(low or imbalance)
5DRY RUN Pump amps lower than expected for time
delay
Check transducer, check low level oat,
check pump
6LEVEL SENSOR OPEN Transducer signal is less than 4mA Check transducer connection, check trans-
ducer and vent tube
7LEVEL SENSOR SHORT Transducer signal is more than 20mA Check transducer
8P1 OL/OT Pump 1 Overload trip or Over temp trip Check pump operation, clogging
9P2 OL/OT Pump 2 Overload trip or Over temp trip Check pump operation, clogging
10 STOP FLOAT FAIL Stop oat out of sequence Check oat tree
11 START FLOAT FAIL Start oat out of sequence Check oat tree
12 LAG FLOAT FAIL Lag oat out of sequence Check oat tree
13 CURRENT SENSOR OPEN Current sensor signal is less than 4mA Check transducer connection, check
transducer
14 POWER FAIL Power loss or Phase loss to the control panel Check incoming power and phase loss
monitoring setting (if used)
15 ILLEGAL ENTRY Unauthorized personnel are tampering with
the control panel
Control access to the control panel
PRIMEX®5 Station View™Controller User Manual

ALARM HISTORY
The Alarm History of the control panel can be accessed via the Alarm Menu. The last 14 alarm events
are recorded with time and date stamp. The last alarm recorded is displayed first.
Use the to view previous alarms.
Press to go back to the previous screen at any time.
PRIMEX®6 Station View™Controller User Manual

ALTERNATION
The alternation mode is set to AUTO by default. The pump will alternate operation during each call to
run. It is possible to force the alternation sequence to start the same pump every time. This is typically
done to equalize run times.
If 1-2 is selected, P1 will start every time, and P2 will only be used as a lag pump.
If 2-1 is selected, P2 will start every time, and P1 will only be used as a lag pump.
Press to go back to the previous screen at any time.
PRIMEX®7 Station View™Controller User Manual