Response:
82A5012C012C0100640000(Current configuration)
(3)Calibrate the baseline:
After the configuration is successful, users can re-acquire and set the baseline value after 13 hours.
Downlink:03A5000000000000000000
Response:
83A5000000000000000000(Configuration success)
83A5010000000000000000(Configuration failure)
Example of ReportDataCmd
FPort:0x06
Bytes 1 Byte 1 Byte 1 Byte Var(Fix=8 Bytes)
Version DeviceType ReportType NetvoxPayLoadData
Version– 1 byte–0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType– 1 byte – Device Type of Device
ReportType – 1 byte –the Presentation of the NetvoxPayLoadData,according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
Device
Device
Type
Report
Type NetvoxPayLoadData
R720E
0xA5 0x01 Battery
(1Byte, Unit: 0.1V) TVOC
(2Bytes, 1ppb) Temperature
(Signed2Bytes, Unit: 0.01°C)
Humidity
(2Bytes, Unit: 0.01%) Reserved
(1Byte, fixed 0x00)
Uplink:01A5012400290A4B11B400
TVOC= 0029 Hex = 41 Dec , 41ppb
Temperature= 0A4B Hex = 2635 Dec , 2635*0.01° = 26.35 °C
Humidity= 11B4 Hex = 4532 5 Dec , 4532*0.01% = 45.32 %
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime) Sleeping(MinTime)
Wake up and collects data
Wakes up and collects data
Wakes up and collects data
REPORTS 3.6V