Example#3 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e.
BatteryVoltageChange= 0.1V.
MaxTime
sleeping sleeping ...
0H 15th M 30th M 45th M 1H 1H 10th M 1H 25th M
1H 40th M 1H 55th M 2H 10th M
Notes :
1) The device only wakes up and performs data sampling according to MinTime Interval. When it is
sleeping, it does not collect data.
2) The data collected is compared with the last data reported. If the data variation is greater than the
ReportableChange value, the device reports according to MinTime interval. If the data variation
is not greater than the last data reported, the device reports according to MaxTime interval.
3) We do not recommend to set the MinTime Interval value too low. If the MinTime Interval is too
low, the device wakes up frequently and the battery will be drained soon.
4) Whenever the device sends a report, no matter resulting from data variation, button pushed or
MaxTime interval, another cycle of MinTime/MaxTime calculation is started.