Locating th Mr.St am®G n rator
Select a location as near as practical to the steam room.
Typical locations include: closet, vanity cabinet, heated attic or basement.
1 . ocate steambath generator within 50 feet of steam room. Note: The standard
length of the cable for connecting the control to the steam generator is 30 feet.
The steam generator and control must be located accordingly. A 60 foot cable
(PN 103990-60) is available as a special order part.
2.DO NOT install steambath generator inside steam room.
3.DO NOT install steambath generator outdoors or wherever environmental
conditions may affect the safety and/or performance of the generator.
4.DO NOT install steambath generator or plumbing lines in
unheated attic or any locations where water could freeze.
5.DO NOT install steambath generator near flammable or
corrosive materials or chemicals such as gasoline, paint thinners,
or the like. Installation in areas having high concentrations of
chlorine (such as pool equipment room) must be avoided.
6.Install steambath generator on a solid and level surface.
Keyhole slots are provided for wall mounting. Insure the
steam generator is properly secured and level when
mounting with keyhole slots.
7.Install steambath generator in an upright position only.
Install a pressure reducing valve to limit supply to 15-20 PSIG
8.Install anti-water hammer device as necessary.
9.Provide a minimum of (12) inches at both ends and top of the steam
generator or as required for servicing.
For Illustrative purposes only. Consult with qualified designer,
architect or contractor for steamroom construction details.