meitav-tec PYROCON19 Manual de usuario

PYROCON19
Controller and User Interface panel
Owner’s manual & Technician Settings
Rev.5.2.9

Index
Introduction…………………………………………………………………...……. 3
Wiring diagram …………………………………...……………………………….. 4
Connecting snow sensors to the system……………………………………...5
Operating instructions…………………………………………………………….6
Turning the system ON and OFF………………………………………………. 6
Selecting temperature scale……………………………………………………..6
Selecting Automatic or Manual mode …………………………………………. 6
Heaters indication………………………………………………………………... 6
Snow flake icon and digital time indication……………………………………. 6
Technician settings……………………………………………………………….. 7
Enter technician settings mode…………………………………………...……. 7
P01 - Temperature set point……………………………………………………. 7
P02 - Lower limit temperature for heating …………………………………….. 8
P03 - Upper limit temperature for heating …………………………………….. 8
P04 -Time delay before stopping the heaters………………………………….9
P05 - Manual mode ON time……………………………………………………. 9
P06 – Heaters cycle and splitting time………………………………………….9
P07 - Heater outputs logic (by PYROSENSE or by 3rd party sensor)…..…. 10
P08 - Snow sensor sensitivity ……………………………………………..…… 11
P88 - Snow detection threshold………………………………………………… 11
P09 - Number of snow sensors connected……………….……………….….. 12
P10 - Test conditions mode…………………………………………………….. 13
P11 - Master/Slave ……………………………………………………………… 13
P12 - Controller’s MAC Address for BMS …………………………………….. 13
P13 - Not in use …………………………………………………………………. 14
P14 - Reset PYRO sensors MAC Address …………………………………… 14
P15 – Offset for calibration of measured temperature ………………………. 14
Save changes end return to normal display………….………………...….…. 14
Restore default values……………………………………………………………. 14
DIP Switch settings……………………………………………………………….. 15
DIP switch S2 - Short measuring times (test only) …………………………... 15
DIP switches S3 and S4 – heaters sequencing logic………………………... 15
Enable/Disable zones……...……………………………………………………... 16
Select Critical zones ……...…………………………………………………….... 17
Temperature reading errors……………………………………………………... 18
Ambient temperature sensor readings out of range………………………….. 18
Communication error with one or more snow sensors………………………..18
Upper limit temperature sensor is not connected or short circuit …………... 18
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 2

Introduction
The PYROCON19 offers smart and easy control over the PYRO Snow & Ice Melting system.
It can operate up to 4 snow melting zones and one auxiliary zone, with selectable sequencing method.
Typical applications include driveways, sidewalks, loading docks, stairs, pavements and gutters.
The backlit LCD screen provides full interface and information to the system status.
The Use of several zones staggering allow covering larger area for snow melting with less available
electrical power.
The PYROCON19 offers various operating and programming options such as:
- Switchable temperature scales (°F or °C) - Adjustable Lower ambient temperature limit to stop
- Both Automatic and Manual modes heaters (lockout)
- Adjustable heaters cycle and splitting times - Energy saving temperature limit
- Adjustable heaters hold on off delay - Adjustable snow sensor sensitivity
- Optional auxiliary control based 3rd party - Commissioning/Test environment
snow sensor (e.g. Gutter/Pavement sensor) - Master/Slave connections
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 3
Optional 3rd party sensor
(e.g. Gutter/Pavement sensor)
Optional PYROSENSE
(Up to 4 Aerial sensors)
(Do not run communication cables close
to heaters or high voltage wires)
Zone
1
General system layout
Zone
5
Zone
2
Zone
3
Zone
4
Auxiliary control
(e.g. Gutter or
Pavement
heaters)
Optional PYROSENSE-GUTTER
(up to 2 Gutter sensors)
Optional T2 –
Outdoor temperature sensor
BMS (Bacnet/Modbus)
or WiFi module
Optional PYROSENSE-GROUND
(Up to 2 Ground sensors)
PYRO-JBOX
ON
PYROCON19 Optional PYROULS –
Upper limit sensor
Contactors

PYROCON19
Owner’s manual & Technician Settings
Pg. 4
Wiring diagram - with optional components and connections
1 2 Z5 22
421
PYROULS
Upper limit
Sensor
PYROCON19
R
C
Z1
Z2
Z3
Z4
A
B
3
To
Contactors
5
T3 T2 B2 A2
3rd party
sensor
or dry
contact switch
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
Up to 4
PYROSENSE
Aerial sensors
A
B
R
C
A
B
R
C
A
B
R
C
A
B
R
C
110
110
Up to 2 Gutter
sensors
Up to 2 Ground
sensors
A
B
R
C
A
B
R
C
A
B
R
C
A
B
R
C
110
110
Up to 3
PYROCON19
(slaves)
Outdoor sensor (option)
Should be used when only
PYROSENSE-GROUND
is connected
24VAC
C
External
transformer
120/24VAC,
25VA
Supply
120VAC
ULTESS T2
~
N
110VAC
BMS (BACnet/Modbus)
or WiFi Module
Z5Z4Z3Z2Z1
Optional devices connected to
A,B through PYRO-JBOX
(See P09 for instructions on
how to connect sensots)
EGFPD
CCC
PYRO
JBOX
PYRO
JBOX
Important!
The PYROCON19 does
not include an integral
EGFPD (Equipment
Ground Fault Protection
Device).
EGFPD needs to be
provided in the end
application.
AB N~
AB N~
22R
R
A2
B2

Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 5
Connecting communicating sensors and PYROCON19 slaves
These devices/sensors can be connected directly to A,B terminals on the
PYROCON19 or through multiple PYRO-JBOX junction boxes with built
in 50VA, 110~24VAC transformer - Allowing connection and powering up
to 3 sensors.
Device/Sensor
type
PYROSENSE
Aerial sensor
Gutter sensor
Ground sensors
Number of
sensors/devices
Up to 4
Up to 2
Up to 2
Power
consumption
(24VAC)
4VA
4VA
15.6VA
Power/Comm.
cable length
32.8ft / 10m
32.8ft / 10m
32.8ft / 10m
MAC
Address
1-4
7-8
5-6
PYROCON19
(slaves) Up to 3 x x 14-16
A
B
PYROCON19
Master
PYRO-JBOX
R C A B R C A B R C A B R C A B
110V
110V
Internal transformer
110~24VAC,50VA
Supply
110VAC
White
Blue
Red
Black
White
Blue
Red
Black
White
Blue
Red
Black
PYROCON19
Slave #3
(A2,B2)
or Sensor #3
Note: Use multiple PYRO-JBOXes
to connect up to 6 sensors and 3
PYROCON19 slaves
PYROCON19
Slave #2
(A2,B2)
or Sensor #2
PYROCON19
Slave #1
(A2,B2)
or Sensor #1
The PYROSENSE aerial sensors are supplied with:
1. A plastic cap, to protect the sensor from dust and debris for when the sensor
is not in use (off season).
Important! The protective cap must be removed before use of the sensor.
If the protective cap is not removed, the sensor will not detect snow!
2. Plastic spikes, to be used if necessary, to keep birds off the sensor.

Operating instructions
Turning the system ON and OFF
Press the [SELECT] button to switch between modes:
“Automatic” Heating will start and stop automatically depending on snow
detection by the snow sensor/sensors.
“Manual ON” Heating will start regardless of snow sensor measurements and will
stop after a preset time (pls. refer to the “Manual ON” section in the
technician settings P05).
Note: Mode will always return to “Automatic” after switching the unit OFF and ON.
Press and hold the [ON] button for 0.5 seconds to turn the system ON or OFF.
The words “ON” or “OFF” will appear on display.
Selecting Automatic or Manual mode
Selecting temperature scale
Press the [+] button for Celsius.
Press the [-] button for Fahrenheit.
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 6
Heaters indication
Heater ON Heater OFF
The number beneath the heater icon
indicates the heater outputs (1 to 5).
Heater
1
Heater
2
Heater
3
Heater
4
Heater
5
Black icon – Heater ON
White icon – Heater OFF
A solid snow flake icon will appear on display while sensing snow and during normal
heaters operation.
Snow flake icon and digital time indication
A blinking snow flake icon will appear on display during heaters off delay or when manual mode is
activated. The digital clock will count down the remaining time until the heaters are turned off.
The snow flake icon will disappear from display as long as the heaters are turned off.
Heater ON in off delay time
(see technician parameter P04)

Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 7
Technician settings
P01 Temperature set point
P02 Lower ambient temperature limit to stop heaters
P03 Energy saving, upper slab temperature limit to stop heaters
P04 Time delay before stopping the heaters
P05 ON time for manual mode
P06 Heaters cycle time / Splitting time
P07 Sensors and heaters control logic
P08 Snow sensor sensitivity
P88 Snow detection threshold
P09 Number of snow sensors connected
P10 Commissioning / Test mode
P11 Master/Slave
P12 Controller’s MAC Address for BMS
P13 Not in use
P14 Reset PYRO sensors MAC Address
P15 Offset for calibration of measured temperature
Restore defaults
Move DIP switch S1 located on the side of thermostat to ON position.
Press the [SELECT] and [+] buttons simultaneously to move forward to the
next technician parameter.
Press the [SELECT] and [-] buttons simultaneously to return to the previous
technician parameter.
Enter technician settings mode
Enter technician
settings mode
Important: Changes made to technician parameters will not take effect
as long as DIP switch S1 is in ON position. Save changes
and exit
technician
settings mode
Save changes and exit technician settings mode
Move DIP switch S1 located on the side of thermostat to OFF position.
Cont’
Use the technician settings to view and adjust the following parameters:

Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 8
P01 - Temperature set point
Move DIP switch S1 located on the side of thermostat to ON position to enter
technician settings mode.
“P01” and the temperature set point will appear on display.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: 14…59°F / -10…+15°C, default 37°F / +3°C
As long as the ambient temperature is lower than the temperature set point P01,
the heaters will turn ON upon receiving a positive snow signal from the snow
detector.
Temperature
set point
Technician settings
Ambient
temperature
sensor
Snow
detector
Snow
detector
Ambient
temperature
sensor
PYROSENSE-GUTTER PYROSENSE
Cont’
The controller will read the ambient temperature from the connected sensors in
the following priority:
1. PYROSENSE – aerial sensor.
2. PYRO-GUTTER gutter sensor.
3. T2 sensor – When no aerial or gutter sensors are used.

Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 9
Cont’
Technician settings (Cont’)
temperature
on heaters
sensor
P03 – Upper limit temperature for heating
Press the [SELECT] and [+] buttons simultaneously.
“P03” and the slab upper limit temperature will appear on display.
Use the [+] and [-] buttons to adjust the upper limit temperature.
Range: +41…+122°F / +5…+50°C Default: 86°F / +30°C
*For numbers above 100, “100” will appear on display.
Press the [SELECT] and [+] buttons simultaneously again.
The word “ON” or “OFF” will appear on display.
Use the [+] and [-] buttons enable (ON) or disable (OFF) the P03
parameter.
If disabled, the heaters will work regardless of the upper limit.
Press the [SELECT] and [+] buttons simultaneously again.
The display will show the temperature on the upper limit sensor.
Upper limit
temperature
Set point
enabled
P03
disabled
P02 - Lower limit temperature for heating
Press the [SELECT] and [+] buttons simultaneously.
“P02” and the low limit temperature will appear on display.
When the temperature on the temperature sensor drops below the low
temperature limit, the heating system will stop.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: -40…+23°F / -40…0°C Default: -31°F / -350°C
Press the [SELECT] and [+] buttons simultaneously again.
The word “ON” or “OFF” will appear on display.
Use the [+] and [-] buttons enable (ON) or disable (OFF) the P02
parameter.
If disabled, the heating system will operate without low temperature
limitations.
Low limit
Temperature
P02
enabled
P02
disabled

Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON19
Owner’s manual & Technician Settings
Pg. 10
Technician settings (Cont’)
P05 - Manual mode ON time
Press the [SELECT] and [+] buttons simultaneously.
“P05”, “On” and the “Manual ON” mode time period will appear on display.
The hours will blink.
The delay time parameter defines a time frame in which the heaters remain
ON after receiving an “Manual ON” command.
Use the [+] and [-] buttons to adjust the hours of the working time.
Range: 00...48 hours Default: 6 hours
Press the [SELECT] and [+] buttons simultaneously again.
The minutes will blink.
Use the [+] and [-] buttons to adjust the minutes of the working time.
Range: 00...59 minutes Default: 00 minutes
Manual ON
hours
Manual ON
minutes
Cont’
P04 -Time delay before stopping the heaters
Press the [SELECT] and [+] buttons simultaneously.
“P04”, “dL” and the time delay before stopping the heaters (Hold ON) will
appear on display. The hours will blink.
Use the [+] and [-] buttons to adjust the hours of the time delay.
Range: 0...9 hours Default: 1 hours
Press the [SELECT] and [+] buttons simultaneously again.
The minutes will blink.
Use the [+] and [-] buttons to adjust the minutes of the time delay.
Range: 00...59 minutes Default: 30 minutes
Note 1. The time delay countdown will start when the snow detection signal
from snow sensor controlling the specific heater will switch from
positive to negative.
Note 2. The staggering sequence will continue during the time delay period.
Note 3. The heater icon will blink when the heater is in off delay time.
Time delay
hours
Time delay
minutes