KMC Controls STE-6010-10 Manual de usuario

STE-6010/6011/6013/6015 Room Temperature Sensors 1 Installation Guide
2.438
2.250
R 3.094
R .187
.643 .450
STE-6013 STE-6011
.475
max.
STE-6010/6015
Modular
RJ-45
Jack
Four-pin
EIA-485
PC Data
Port
Clamp
(Screw-type)
Terminals
Clamp
(Screw-type)
Terminals
.149
Installation Guide
Room Temperature Sensors
STE-6010/6011/6013/6015
Mounting
according to the appropriate wiring diagram on
the next page.
5. Replace the cover.
STE-6011 Only
Handy Box Installation (Recommended)
1. Mount a universal backplate HMO-6036 to the
handy box using the two screws provided.
2. Remove the cover from the back panel.
3. AachwiresaccordingtotheSTE-6011wiring
diagram on the next page.
4. Aachthebackpaneltothebackplateusingtwo
screws.
5. Check that leads to the thermistor are straight
and the thermistor is completely extended.
6. Replace the cover.
Hollow Wall Installation
1. Remove the cover from the back panel.
2. Use the back panel as a template to drill two
holes for mounting screws (7/64 inches or 3 mm
in diameter and 1.4 inches, 1-13/32 inches, or 35.6
mm apart) and to cut a center hole (7/8 inch or 20
mm) for the terminal block or jack.
3. AachwiresaccordingtotheSTE-6011wiring
diagram on the next page.
4. Aachthebackpaneltothewallusingtwo
#6 self-threading screws. (Plastic anchors are
recommended, and the size of the holes will then
need adjusting.)
5. Check that leads to the thermistor are straight
and the thermistor is completely extended.
6. Replace the cover.
All dimensions
are in inches
Location and Cover Removal (All)
Install the sensor on an inside wall where it can sense
the average room temperature and be away from
direct sunlight, heat sources, windows, air vents, and
air circulation obstructions (curtains, furniture, etc.). It
can be mounted on a hollow wall or (with a universal
backplate HMO-6036) to a 2 x 4 inch handy box.
Thecoverisheldtotheblack,backpanelbythree,
small,roundpegsthattintheholesofthecover.
Theboompegisonatabandsnapsintothecenter
boomhole.
1. With a small Phillips screwdriver or hex wrench,
pressinandholdthetabbuonthatsnapsinto
thecenterholeontheboomcover.
2. Carefully pull or pry the back panel from the
front cover.
STE-6010/6013/6015 Only
Handy Box Installation (Recommended)
1. Mount a universal backplate
HMO-6036 to the handy box
using the two screws provided.
2. Remove the cover from the back panel.
3. Aachthebackpaneltothebackplateusingthe
two screws provided.
4. Aachthecabletotheterminalblockorjack
according to the appropriate wiring diagram on
the next page.
5. Replace the cover.
Hollow Wall Installation
1. Remove the cover from the back panel.
2. Using the back panel as a template, drill two holes for
mounting screws (7/64 inches or 3 mm in diameter
and 1.4 inches, 1-13/32 inches, or 35.6 mm apart) and
cut a center hole (size needed is dependent on model)
for the terminal block or jack.
3. Aachthebackpaneltothewallusingtwo
#6 self-threading screws. (Plastic anchors are
recommended, and the size of the holes will then
need adjusting.)
4. Aachthecabletotheterminalblockorjack

STE-6010/6011/6013/6015 Room Temperature Sensors 2 Installation Guide
AttheboomoftheSTE-6010/6015caseisanEIA-
485(formerlyRS-485)computerport.Thisport
provides a temporary connection to the digital
network for network setup or troubleshooting.
Tousetheporttoconnecttoacomputer,ameansof
convertingtheEIA-485signaltoaUSBorEIA-232
(formerlyRS-232)signalwillbeneeded.Theexact
connection depends on the computer and the opera-
torworkstationsoware.(Seealsotheinstructions
includedwiththosedevicesandsoware.)
For• USB(toWinControlorBACstage),usea
KMD-5576USBCommunicator(seetheillustra-
tion above).
For• EIA-232 to BACstage, use a third-party
interface.
For• EIA-232 to WinControl, use a KMD-5559
CommTalkandKMD-5624cable(orequivalent
interface).
ToaccessthenetworkthroughtheSTE’sport:
1. Connectthekeyed,atendoftheKMD-5624
interface cable (included with the KMD-5576 but
not the KMD-5559) to the port on the sensor.
2. Connect the other end of the cable to the interface
device that converts the EIA-485 signal into an
EIA-232orUSBsignal.
3. Connect the suitable cable from the interface
devicetothecomputer’sserialorUSBport.Install
anyrequiredsowareandconguretheportas
necessary.
STE-6013
Common (Ground)
Thermistor (10K Ohms)
D
B
C
10 VDC LED Supply (from Controller)
STE-6011
Controller Connection
Connectwiresasshownfortherelevantmodel.(SeetheModelsandSpecicationssection.)
Thermistor (10K Ohms)
(Wires are
interchangeable)
(Override
Button)
ConnectinganyoftheSTE-6010/6015toacontroller
requiresaspecialcablewith(onthesensorend)an
RJ-45 connector and (on the controller end) an RJ-11
connector with additional wires for controller inputs.
Purchasing pre-assembled cables from KMC is more
cost-eective and reliable than creating custom
cablesintheeld.Useoneofthefollowingcables:
KMD-569• 3= 25 feet
KMD-569• 4= 50 feet
KMD-569• 5= 75 feet
Theadditionalorange wire is for the thermistor
input to the controller.
Theadditionalgreen and the orange/white wires
should be clipped or taped back since they are
notusedwithanSTE-6010/6015.(The additional
orange/white wire is for the STE-6014/6016/6017/6018
setpoint signal input to the controller, and the additional
green wire is for auxiliary supply voltage to the STE-
6015/6018/6016.)
KMD-5624
Cable
KMD-5576
PC Port Connection
STE-6010/6015
KMD–5693= 25 feet; KMD–5694= 50 feet; KMD–5695= 75 feet
1 8
Orange Wire = Thermistor Input to Controller
Orange/White Wire = Setpoint Signal Input to Controller
(for STE-6014/6016/6017/6018 only; clip or tape when not used)
12 inches
52
RJ-11 and
Wire Leads
to Controller
RJ-45
to STE
Sensor
Green Wire = Aux. Supply Voltage to STE-6015/6018
(10 VDC) or STE-6016 (7.5/12 VDC) (clip or tape when not used)
RJ-11 RJ-45 Color
(Lead) 8 Orange
7 N.C.
(Lead) 6 Green
3 5 Blue
4 4 Blue/White
5 3 Green/White
2 N.C.
(Lead) 1 Orange/White
(Cables crossed, 20 AWG)

STE-6010/6011/6013/6015 Room Temperature Sensors 3 Installation Guide
Controller Configuration
Overview
Ensure that the corresponding 10,000 ohm pull-up
resistors on the controller are selected (switched
On).Consultthecontroller’ssetupinstructionsfor
information on switching on the pull-up resistors.
Controller conguration instructions are given for
both WinControl and BACstage. See the relevant
soware section.
WinControl Software
Thermistor Input (All)
1. IntheWinControlsowaremainmenu,select
Control > Inputs.
2. Click Edit.
3. TypeinanameintheDescriptioneld(upto20
characters) and/or Labeleld(upto8characters).
NOTE: Notwolabelsordescriptionsinacontroller
can be identical.
4. Click Units(whichopenstheCongureInputs
screen).
5. SelectType: Analog if it is not the default.
6. SelectDeg F (or C) KMC10K Type II.
8. Optionally, change Format from 0 to the desired
number of temperature decimal places.
9. Optionally, change the Average to the desired
number of thermistor readings averaged before
displaying the result.
10. Click OK.
11. Click End Edit.
12. Click OK.
Override Input (STE-6013/6015 only)
1. IntheWinControlsowaremainmenu,select
Control > Setpoint/Variables.
2. Click Edit.
3. TypeinanameintheDescriptioneldand/or
Labeleld.
4. Click Units(whichopenstheCongureVariables
screen).
5. SelectType: Digital.
6. SelectO/On (or No/Yes, Stop/Start, Dis/Enabled
according to preference).
7. Click OK.
8. Click End Edit.
9. Click OK.
BACstage Software
Thermistor Input (All)
1. IntheBACstagesowaremainmenu,select
Objects > Inputs.
2. Click Edit.
3. TypeinanameintheDescriptioneld(upto32
characters) and/or Labeleld(upto16characters).
NOTE: Notwolabelsordescriptionsinacontroller
can be identical.
4. SelectObject Type: Analog if it is not the default.
5. SelectDevice Type: KMC10K Type II.
6. SelectUnits: °F or °C.
7. Click End Edit.
8. Click Yesfor“SendUpdateNoticationNow?”
9. IntheBACstagesowaremainmenu,select
Device > Device Tables > KMC10K Type II Table.
10. Click Edit.
11. Click Defaults(valueswillllin).
12. Click End Edit.
13. Click Yesfor“SendUpdateNoticationNow?”
14. Click OK.
Override Input (STE-6013/6015 only)
1. IntheBACstagesowaremainmenu,select
Objects > Binary Values.
2. Click Edit.
3. TypeinanameintheDescriptioneldand/or
Labeleld.
4. Click in the Units column and select O/On (or
No/Yes, Stop/Start, Disabled/Enabled, Inactive/Active
according to preference).
5. Click End Edit.
6. Click Yesfor“SendUpdateNoticationNow?”
7. Click OK.

STE-6010/6011/6013/6015 Room Temperature Sensors 4 Installation Guide
Models and Specifications
© 2008 KMC Controls, Inc. 866-019-03
KMC Controls, Inc.
19476 Industrial Drive, New Paris, IN 46553
574.831.5250
www.kmccontrols.com; [email protected]
Maintenance
Careful installation will also ensure long-term
reliability and performance. Remove dust as neces-
saryfromholesintopandboom.Cleanwithaso,
damp cloth and mild soap.
Model
Number
Interface
Features
Cable
Connections
Override
Button
LED
Status
Indicator
Screw
Clamp
Terminals
RJ-45
Connector
EIA-485
Data
Port
STE-6010-10 X X
STE-6011-10 X
STE-6013-10 X X X
STE-6015-10 X X X X
Accessories
HMO-6036 UniversalBackplate
KMD-569x STE-6010/6014/6015/6016/6017/
6018 to Controller Cable with RJ-
45 to RJ-11 Connectors (-5693= 25
.;-5694=50.;-5695=75.)
KMD-5624 PCDataPort(EIA-485)Cable
KMD-5576 EIA-485toUSBCommunicator
SP-001 Flatblade&hexendscrewdriver
STE-6010/6011 STE-6013/6015
BAC-A1616BC BACnet Building Controller
Select the 10K ohm pull-up resistor jumper posi-
tion for the corresponding input.(SeetheInstalla-
tionsectionoftheBAC-A1616ABCBuildingControl-
ler Installation and Operation Guide for the correct
jumper position.)
BecausetheBuildingControllerhasa0–12VDC
totalinputrange,dierenttablesarerequiredthan
inother(0–5VDC)KMCcontrollers.Downloadthe
CSVtablelesfromwww.kmccontrols.comand
importtheneededtablesasdescribedintheTables
sectionoftheBAC-A1616ABCBuildingController
Installation and Operation Guide. (You must log-in
toseethezippedtablesinSupport>Technical>
Tablesonthewebsite.)
1. In the desired Analog Input setup screen of the
webpageinterface,selectKMCTypeIIDegree
FahrenheitorKMCTypeIIDegreeCelsius.
2. SelecttheLookupTablefortheTypeII
Thermistor.
3. For the Fahrenheit scale, the multiplier is 1.8 and
theosetis32.ForCelsius,themultiplieris1and
theosetis0.
4. Click Save.
Connections Clamp (screw-type) terminals
or modular RJ-45 jack
Sensor
Type TypeIIthermistor
Accuracy ± 0.36° F (± 0.20° C)
Resistance 10,000 ohms @ 77° F (25° C)
Front Buon (STE-6013/6015)Onemo-
mentarypushbuon,shunts
temperature sensor to signal
override condition
Power Requirement (LEDIndicatoronSTE-
6013/6015)10VDC(12VDC
max); 5 mA max. current draw
at12VDC
Environmental Limits
Operating 34° to 125° F (1.1° to 51.6° C)
Shipping –40°to140°F(–40°to60°C)
Humidity 0 to 95% RH non-condensing
NOTE: Foradditionalspecications,seethe
STE-6000SeriesRoomTemperature
Sensors/TransmiersDataSheet.
Este manual sirve para los siguientes modelos
3
Tabla de contenidos
Otros manuales de Accesorios de KMC Controls

KMC Controls
KMC Controls NetSensor KMD-1162 Instrucciones de funcionamiento

KMC Controls
KMC Controls STE-6014 Guía del usuario

KMC Controls
KMC Controls KMD-1183 Instrucciones de funcionamiento

KMC Controls
KMC Controls STE-6014-10 Manual de usuario

KMC Controls
KMC Controls NetSensor KMD-1261 Instrucciones de funcionamiento

KMC Controls
KMC Controls Conquest STE-90 Series Manual de usuario

KMC Controls
KMC Controls THE-1105 Manual de usuario

KMC Controls
KMC Controls STW Series Manual de usuario

KMC Controls
KMC Controls STE-6014 Manual de usuario

KMC Controls
KMC Controls STE-6010 Guía del usuario