EUROSTER UNI4 –USER MANUAL 9
Correction of sensors
Correction of temperature sensors allows to correct temperature reading errors, such as the
ones resulting from improper contact between the sensor and the pipe.
Automatic operation
The function enabling automatic switch-off of the CH 1 and CH 2 zones if the temperature of
the S7 sensor (outdoor sensor) exceeds the preset value of the "Switch-off temperature".
The heating will be restarted if the external temperature drops below the preset value of
"Switch-on temperature".
The automatic operation mode is available when the outdoor temperature sensor is connected
and WINTER season selected.
Events
The device records hazardous events. The display shows subsequently: Event number (since
the installation), date, time, and comments, e.g.: 11. 19-09 14:16:38 DHW overheating
4. INSTALLATION
4.1. Connection
◼Prior to the commencement of any installation works read this manual carefully!
Incorrect installation and handling of the controller result in loss of manufacturer's
warranty.
◼Prior to mounting or dismantling the controller make sure that it is de-energized.
Connection and disconnection of temperature sensors should also be performed when
the device is de-energized.
◼Voltages hazardous to life are present on the controller and its connections, therefore
only qualified and authorized technicians may be entrusted with the installation of the
controller.
◼Install the controller in the circuit with proper electrical protections, in accordance with
current regulations.
◼The performed electric connections and cables used shall be adequate to the applied
loads and must conform to all requirements.
◼Do not install the controller in rooms of increased humidity, protect it against water and
other liquids.
◼The controller is designed to be mounted on a 35 mm DIN rail in a protective cabinet.
◼Do not install any controller showing signs of mechanical damage.
◼The controller is not a safety component. Additional protection devices must be used in
systems prone to the risk of damage due to the failure of control systems.
CAUTION! Euroster Uni4 controller and a heat emitting device are connected to the
“BOILER RELAY” output and must be powered from the same phase of the power
system.
CAUTION! When connecting power cables, pay particular attention to the correct
connection of PE conductors.
The temperature sensors are not suitable to be immersed in liquids.
The controller interacts only with actuators equipped with limit switches.
The controller must be installed in a place where ambient temperature does not exceed 40°C.
All necessary cables must be laid prior to mounting the device.
Screw the electric cables to the connection blocks according to the description and drawing.
Make sure to keep the proper designation of the cables. Screw the neutral conductors to N
terminals, phase conductors to L terminals, and grounding conductors to PE terminals. Connect
the device using a cable with a minimum diameter of 0.75mm².
The controller is equipped with seven temperature sensors. It is not necessary to connect
sensors for the switched-off zones/functions.
The controller sensors may be connected in any way, with no need to keep cable polarity. At
installation avoid leading the sensors parallel to live cables. Moreover, make sure to provide
the proper contact with measured surfaces.
The outdoor temperature sensor should be installed in a shaded place, away from windows and
doors, at a height of approximately 2 m above ground.