________________________________________________________________________________________________________
ELCOS –Parma –Italy –CAM-335 Valid for firmware revision 1.14 and above Page 10 of 20
EJP FUNCTION
To activate the EJP function, see the programming manual. It is only active in automatic mode. When the contact
connected to terminal 32 closes to ground, EJP STARTUP is shown on the display. After the EJP STARTING DELAY
has elapsed (set to 25 minutes), the start-up cycle begins. When the contact connected to terminal 33 closes to
ground, EJP SWITCHING CONSENT is shown on the display and operation is the same as that of a mains failure.
When the two contacts open, operation is the same as when mains power is restored.
VOLTMETRIC CONNECTIONS
The control unit can be configured to manage THREE-PHASE, TWO-PHASE and SINGLE-PHASE voltages. This
selection is valid both for the mains and for the generator; therefore, it is possible to manage, for example, three-
phase voltage from the mains and two-phase from the generator. When the mains power is three-phase, the phases
must be connected to terminals 91, 92 and 93 and the neutral to terminal 90. With two-phase connection, terminals
91 and 92 must be connected and the neutral must not be connected. Instead, with the single-phase connection, the
phase must be connected to terminal 92 and the neutral to terminal 90. Likewise, when the generator power is three-
phase, the phases must be connected to terminals 96, 97 and 98 and the neutral to terminal 95. With two-phase
connection, terminals 96 and 97 must be connected and the neutral must not be connected. Instead, with the single-
phase connection, the phase must be connected to terminal 97 and the neutral to terminal 95.
MAINS/GENERATOR VOLTMETRIC RELAYS
The voltmetric relays are located inside the control unit and serve to control the mains and genset voltages and
frequencies. The parameters considered are: power failure, undervoltage, overvoltage, asymmetrical voltages,
incorrect phase sequence, under-frequency and overfrequency.
Mains voltmetric relay: when each parameter has been accepted individually, after the mains voltage present
delay has elapsed (programmed to 100 seconds), if the genset is running, it stops and the mains contactor is
energized.
Generator voltmetric relay: when each parameter has been accepted individually, after the generator voltage
present delay has elapsed (programmed to 7 seconds), the generator contactor closes. It takes just one
parameter outside the normal range to de-energize the generator contactor.
FUEL FILLING MANAGEMENT
When the automatic fuel filling function is enabled, a dedicated menu is displayed. With filling, the fuel is
transferred from a storage tank to the genset tank. Either automatic mode, manual mode or filling lockout can be
selected using the display touch screen. The filling function is managed independently, meaning it does not depend
on the control unit’s operation mode. It is possible to enable filling either when the genset is powered or when the
user is powered. A contact float controls the maximum safety level. Another float with variable resistance (terminal
37) manages activation and deactivation of the output for pump and/or solenoid valve piloting. If the function is
enabled by default, the pump relay piloting output is associated to terminal 70, while the maximum level float input is
associated to terminal 41.
To change the filling management operation mode, simply press “AUT”, “MAN” or “OFF” on the display. The mode is
saved in the control unit even if the battery gets disconnected.
Automatic filling: when the level of fuel drops below the “minimum level”, the output is
enabled and MINIMUM FUEL LEVEL appears on the display. When the “maximum level” is
exceeded, the output is disabled and MAXIMUM FUEL LEVEL appears on the display.
Manual filling: pressing the START button on the display enables the filling output; taking the
finger off the button disables the output.
Filling OFF: turns filling off; the output, if enabled, is disabled.
Request the connection diagram, which can also be downloaded from the website www.elcos.it.