AEG Protect PV Manual de usuario

Protect PV - Solar Inverters
Installation Manual
AEG Power Solutions GmbH
Revision: 01
Date: 2011-05-25
InstallationManual
8000038781_00_BAL_en

Contents
1. Safety and Conformity 2
Safety Information 2
Hazards of PV Systems 3
PV Load Switch 3
Conformity 4
Approvals and Certifications 4
2. Introduction 5
Introduction 5
Installation Sequence 6
Overview of Inverter 7
3. Installation 8
Installation Dimensions and Patterns 8
Mounting the Inverter 10
Removing the Inverter 11
Opening and Closing the Inverter 12
AC Grid Connection 14
PV Connection 16
Auxiliary Input/Output 17
Autotest Procedure - Italy Only 17
4. Start-up and Check of Settings 18
Start-up and Check of Settings 18
Troubleshooting 21
Master Mode 21
5. Technical Data 23
Technical Data 23
Cable Requirements 25
Wiring Diagram 28
Auxiliary Interface Specifications 29
RS485 Communication Board Connections 31
Contents
8000038781_00_BAL_en / L00410564-01_02 1

1. Safety and Conformity
1.1. Safety Information
All persons installing and servicing inverters must be:
• Trained and experienced in general safety rules for work on electrical equipment
• Familiar with local requirements, rules and regulations for the installation
Safety information important for human safety. Violation of warnings may result in
injury to persons or death.
Information important for the protection of property. Violation of this type of in-
formation may cause damage and loss of property.
Note:
Useful additional information or “Tips and Tricks” on specific subjects.
Read this before installing, operating or maintaining the inverter.
1. Safety and Conformity
2 8000038781_00_BAL_en / L00410564-01_02
1

Before installation:
Check for damage to inverter and packaging. If in doubt, contact the supplier be-
fore installing the inverter.
Installation:
For optimum safety, follow the steps described in this manual. Keep in mind that
the inverter has two voltage carrying sides; the PV input and the AC grid.
Disconnecting the inverter:
Before starting work on the inverter, switch off AC grid at the mains switch and PV
using the PV load switch. Ensure that the device cannot be unintentionally recon-
nected. Use a voltage tester to ensure that the unit is disconnected and voltage
free. The inverter can still be charged with very high voltage at hazardous levels
even when it is disconnected from grid/mains and solar modules. Wait at least 30
min. following disconnection from grid and PV panels before proceeding.
Maintenance and modification:
Only authorised personnel are allowed to repair or modify the inverter. To ensure
optimum personal safety, only original spare parts available from the supplier
should be used. If non-original spare parts are used, the compliance with CE
guidelines in respect of electrical safety, EMC and machine safety is not guaran-
teed.
Also observe the danger of burn injury. The temperature of the cooling racks and
components inside the inverter may exceed 70ºC.
Functional safety parameters:
Never change the parameters of the inverter without authorisation from the local
energy supply company and instructions from AEG PS.
Unauthorised changes of functional safety parameters may cause injury or acci-
dents to people or inverter. Additionally it will lead to the cancellation of all inver-
ter operating approval certificates.
The AEG PS inverters are all designed according to the German VDE0126-1-1
(February 2006) standard, which includes an insulation test between PV array(s)
and Earth, and a type B, RCMU according to DIN VDE 0100-712.
1.2. Hazards of PV Systems
Very high DC voltages are present in the system even when the AC grid is disconnected. Faults
or inappropriate use may lead to electric arcing. Do not work on the inverter while it has cur-
rent connected to it.
The short-circuit current of the photovoltaic panels is only slightly higher than the maximum op-
erating current and depends on the level of solar irradiation.
1.3. PV Load Switch
Illustration 1.1: Protect PV PV Load Switch
The inverter has been equipped with a PV
load switch (1) for safe disconnection of DC
current.
1. Safety and Conformity
8000038781_00_BAL_en / L00410564-01_02 3
1

1.4. Conformity
1.4.1. Approvals and Certifications
For more information, go to the download area at www.aegps.com/solarinverters, Approvals
and Certifications.
CE marking - This certifies the conformity of the equipment with the regula-
tions which apply in accordance with the directives 2004/108/EC and
2006/95/EC.
1. Safety and Conformity
4 8000038781_00_BAL_en / L00410564-01_02
1

2. Introduction
2.1. Introduction
This manual explains the installation and setup of the Protect PV solar inverter, for the installa-
tion technician.
Illustration 2.1: Protect PV 10 kW, Protect PV 12.5 kW, Protect PV 15 kW
CE marking - This certifies the conformity of the equipment with the regula-
tions which apply in accordance with the directives 2004/108/EC and
2006/95/EC.
The Protect PV inverter series comprises:
Protect PV
Protect PV easy
Common features of the Protect PV variants:
• Output rating of 10 kW, 12.5 kW or 15 kW
• IP 54 enclosure
• PV load switch
• MC4 connectors
2. Introduction
8000038781_00_BAL_en / L00410564-01_02 5
2

Protect PV
variant
User interface Ancillary services DC power rat-
ing
Local Web Server Power Level Adjust-
ment,
Primary Frequency
Control
Ride Through Fault Ride Through
Reactive Power
10 kW
12.5 kW
15 kW
Protect PV ✓ ✓ ✓ ✓ ✓
Protect PV
easy
✓ ✓ ✓ ✓ ✓ ✓
Table 2.1: Differing Features of Protect PV Variants
Product Label
Illustration 2.2: Product Label
The product label on the side of the inverter
shows:
• Inverter type
• Important specifications
• Serial number, see (1), for identifi-
cation by AEG PS
2.1.1. Installation Sequence
1. Read the installation manual. Pay special attention to the section
Important Safety In-
formation
.
2. Install the inverter according to the section
Installation Dimensions and Patterns
and
the section
Mounting the Inverter
.
3. Open the inverter according to the section
Opening and Closing the Inverter
.
4. Install AC according to the section
AC Grid Connection
.
5. Install PV. Remember to use the terminal block to establish parallel connection (if re-
quired), as described in the section
PV Connection
. The inverter has auto-detection.
6. Install Auxiliary input according to the section
Connection of Peripheral Units
.
7. Close the inverter according to the section
Opening and Closing the Inverter
.
8. Turn on AC at the mains switch.
9. Set language, time, date, installed PV power and country:
-For setup via the integrated Web Server, see the Protect PV User Manual,Web
Server Quick Guide section
-For setup via the display, see the section
Start-up and Check of Settings
in
this manual.
10. Turn on PV by turning the PV load switch on.
11. Verify the installation by comparing with the auto-detection result in the display, as de-
scribed in the section
PV Connection
.
12. The inverter is now ready for operation.
2. Introduction
6 8000038781_00_BAL_en / L00410564-01_02
2

2.1.2. Overview of Inverter
Illustration 2.3: Overview of AEG PS Protect PV inverter
Live Part
1. AC Connection Area
2. DC Connection Area
3. Terminal block for parallel connection
4. Auxiliary output: Potential free relay
PELV (Safe to touch)
5. Auxiliary interface: RS485
6. Auxiliary interface: Temperature, Irradiation, Energy meter (SO)
7. Auxiliary interface: Ethernet
Other
8. DC-switch
The inverter can also be configured via the Web Server . For further information refer to the
Web Server User Manual.
2. Introduction
8000038781_00_BAL_en / L00410564-01_02 7
2

3. Installation
3.1. Installation Dimensions and Patterns
Note:
When choosing the installation place, ensure that all labels are visible at all times.
For details refer to the section
Specifications
.
Avoid constant stream of water.
Avoid direct sunlight.
Ensure adequate air flow.
Ensure adequate air flow.
Mount on non-flammable surface.
Mount upright on vertical surface.
Prevent dust and ammonia gases.
3. Installation
8 8000038781_00_BAL_en / L00410564-01_02
3

Illustration 3.1: Safe Distances
Observe these distances when installing one or more inverters. One row mounting is recom-
mended. Contact the supplier for information on mounting in more rows.
Illustration 3.2: Wall Plate
Note:
Use of the wall plate delivered with the inverter is mandatory.
Use screws that can safely carry the weight of the inverter. The inverter must be aligned and it
is important that the inverter is accessible at the front to allow room for servicing.
3. Installation
8000038781_00_BAL_en / L00410564-01_02 9
3
Otros manuales para Protect PV
1
Este manual sirve para los siguientes modelos
4
Tabla de contenidos
Otros manuales de Inversor de AEG

AEG
AEG AS-IC01-2 Series Manual de usuario

AEG
AEG AS-IR01 Manual de usuario

AEG
AEG AS-IC01-4000-2 Manual de usuario

AEG
AEG AGN6500 Manual de usuario

AEG
AEG 1000 W Manual de usuario

AEG
AEG Protect PV 4600 Manual de usuario

AEG
AEG Si 150 Manual de usuario

AEG
AEG AS-IR02 Series Manual de usuario

AEG
AEG AS-IC01 Manual de usuario

AEG
AEG Protect PV 2800 Manual de usuario