ABB REC650 ANSI Manual de usuario

Relion® 650 series
Bay control REC650
Product Guide

Contents
1. 650 series overview..............................................3
2. Application...........................................................3
3. Available functions...............................................6
4. Control................................................................18
5. Current protection..............................................20
6. Voltage protection..............................................22
7. Frequency protection.........................................23
8. Secondary system supervision..........................23
9. Logic...................................................................24
10. Monitoring.........................................................26
11. Metering............................................................28
12. Human Machine interface.................................29
13. Basic IED functions...........................................29
14. Station communication.....................................30
15. Hardware description........................................32
16. Connection diagrams........................................33
17. Technical data...................................................40
18. Ordering............................................................75
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes
no responsibility for any errors that may appear in this document.
© Copyright 2011 ABB AB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
2 ABB

1. 650 series overview
The 650 series IEDs provide optimum 'off-the-
shelf', ready-to-use solutions. It is configured
with complete protection functionality and
default parameters to meet the needs of a
wide range of applications for generation
transmission and sub-transmission grids.
The 650 series IEDs include:
• Complete ready-made solutions optimized
for a wide range of applications for
generation, transmission and sub-
transmission grids.
• Support for user-defined names in the local
language for signal and function
engineering.
• Minimized parameter setting based on
default values and ABB's new global base
value concept. You only need to set those
parameters specific to your own
application, such as the line data.
• GOOSE messaging for horizontal
communication.
• Extended HMI functionality with 15
dynamic three-color-indication LEDs per
page, on up to three pages, and
configurable push-button shortcuts for
different actions.
• Programmable LED text-based labels.
• Settable 1A/5A -rated current inputs.
2. Application
REC650 is used for the control, protection
and monitoring of different types of bays in
power networks. The IED is especially
suitable for applications in control systems
with distributed control IEDs in all bays with
high demands on reliability. It is intended
mainly for sub-transmission stations. It is
suitable for the control of all apparatuses in
single busbar single CB, double busbar single
CB switchgear arrangement.
The control is performed from remote
(SCADA/Station) through the communication
bus or from local HMI. Different control
configurations can be used, and one control
IED per bay is recommended. Interlocking
modules are available for common types of
switchgear arrangements. The control is
based on the select before execute principle
to give highest possible security. A
synchronism control function is available to
interlock breaker closing. Synchronizing
function where breaker closes at the right
instance in asynchronous networks is also
provided.
A number of protection functions are
available for flexibility in use for different
station types and busbar arrangements. The
auto-reclose includes priority circuits for
single-breaker arrangements. It co-operates
with the synchrocheck function with high-
speed or delayed reclosing.
High set instantaneous phase and earth
overcurrent, 4 step directional or non-
directional delayed phase and earth
overcurrent, thermal overload and two step
under- and overvoltage functions are
examples of the available functions allowing
user to fulfill any application requirement.
Disturbance recording is available to allow
independent post-fault analysis after primary
disturbances.
Three packages have been defined for
following applications:
• Single breaker for single busbar (A01)
• Single breaker for double busbar (A02)
• Bus coupler for double busbar (A07)
The packages are configured and ready for
direct use. Analog and control circuits have
been pre-defined. Other signals need to be
applied as required for each application. The
main differences between the packages above
are the interlocking modules and the number
of apparatuses to control.
The graphical configuration tool ensures
simple and fast testing and commissioning.
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
Revision: -
ABB 3

REC650-A01 – Single Busbar Single breaker 10AI (4I+1I+5U)
S CSWI
Control
S XCBR
Control
S CSWI
Control
SMB RREC
79 0->1
S CSWI
Control
S CSWI
Control
SMP PTRC
94 1->0
S CSWI
Control
S CSWI
Control
SES RSYN
25 SYNC
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
Other configured functions
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
OV2 PTOV
59 U>
PH PIOC
50 3I>>
CC RBRF
50BF 3I> BF
V MMXU
Meter.
C MMXU
Meter.
ETP MMTR
Wh<->
QA1
QB1
QB9
QC9
QC2
QC1
EF4 PTOC
51N/67N IN>
Q CBAY
Control
WA1
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
SEL GGIO
Control
C MSQI
Meter.
V MSQI
Meter.
CV MMXN
Meter.
CC RPLD
52PD PD
DRP RDRE
Mont.
V MMXU
Meter.
IEC61850
ANSI IEC
Function Enabled
in Settings
132 kV Bus
1000/1
132kV/110V
132kV/110V
OC4 PTOC
51/67 3I>
IEC09000648-2-en.vsd
S SCBR
Cond
S SIMG
63
DNP
ANSI IEC
Function Disabled in Settings
IEC60870-5-103
ANSI IEC
IEC09000648 V2 EN
Figure 1. A typical protection and control application for a single busbar in single breaker
arrangement
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
4 ABB

REC650-A02 – Double Busbar Single breaker 10AI (4I+1I+5U)
S CSWI
Control
S XCBR
Control
S CSWI
Control
SMB RREC
79 0->1
S CSWI
Control
S CSWI
Control
SMP PTRC
94 1->0
S CSWI
Control
S CSWI
Control
S CSWI
Control
SES RSYN
25 SYNC
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
Other configured functions
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
OV2 PTOV
59 U>
PH PIOC
50 3I>>
CC RBRF
50BF 3I> BF
V MMXU
Meter.
C MMXU
Meter.
ETP MMTR
Wh<->
QA1
QB1 QB2
QB9
QC9
QC2
QC1
EF4 PTOC
51N/67N IN>
Q CBAY
Control
WA1
WA2
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
SEL GGIO
Control
C MSQI
Meter.
V MSQI
Meter.
CV MMXN
Meter.
CC RPLD
52PD PD
DRP RDRE
Mont.
V MMXU
Meter.
V MMXU
Meter.
OC4 PTOC
51/67 3I>
IEC61850
ANSI IEC
Function Enabled
in Settings
132 kV Bus
1000/1
132kV/110V
132kV/
110V
132kV/
110V
IEC09000649-2-en.vsd
S SIMG
63
S SCBR
Cond
DNP
ANSI IEC
Function Disabled in Settings
IEC60870-5-103
ANSI IEC
IEC09000649 V2 EN
Figure 2. A typical protection and control application for a double busbar in single breaker
arrangement
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
ABB 5

REC650-A07 – Bus Coupler single breaker 10AI (6I+4U)
S CSWI
Control
S XCBR
Control
S CSWI
Control
S CSWI
Control
S CSWI
Control
SMP PTRC
94 1->0
S CSWI
Control
S CSWI
Control
S CSWI
Control
SES RSYN
25 SYNC
TCS SCBR
Cond
TCS SCBR
Cond
SPVN ZBAT
Cond
Other configured functions
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
S XSWI
Control
EF4 PTOC
51N IN>
Q CBAY
Control
S SCBR
Cond
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
S CILO
Control
SEL GGIO
Control
DRP RDRE
Mont.
QA1
QB1 QB2
QC2
QC1
WA1
WA2
QC11 QC21
CC RBRF
50BF 3I> BF
PH PIOC
50 3I>>
CC RPLD
52PD PD
C MMXU
Meter.
C MSQI
Meter.
V MMXU
Meter.
V MMXU
Meter.
IEC61850
ANSI IEC
Function Enabled
in Settings
132 kV Bus
1000/1
132kV/
110V 132kV/
110V
OC4 PTOC
51/67 3I>
IEC09000650-2-en.vsd
S SIMG
63
DNP
ANSI IEC
Function Disabled in Settings
IEC60870-5-103
ANSI IEC
IEC09000650 V2 EN
Figure 3. A typical protection and control application for a bus coupler in single breaker
arrangement
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
6 ABB

3. Available functions
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
ABB 7

Control and monitoring functions
IEC 61850/
Function block
name
ANSI Function description Bay
REC650 (A01)
1CBA
REC650 (A02)
1CBAB
REC650 (A07)
BCAB
Control
SESRSYN 25 Synchrocheck, energizing check,
and synchronizing
111
SMBRREC 79 Autorecloser 1 1 1
SCILO 3 Logical node for interlocking 8 8 8
BB_ES 3 Interlocking for busbar earthing
switch
333
A1A2_BS 3 Interlocking for bus-section breaker 2 2 2
A1A2_DC 3 Interlocking for bus-section
disconnector
333
ABC_BC 3 Interlocking for bus-coupler bay 1 1 1
BH_CONN 3 Interlocking for 1 1/2 breaker
diameter
111
BH_LINE_A 3 Interlocking for 1 1/2 breaker
diameter
111
BH_LINE_B 3 Interlocking for 1 1/2 breaker
diameter
111
DB_BUS_A 3 Interlocking for double CB bay 1 1 1
DB_BUS_B 3 Interlocking for double CB bay 1 1 1
DB_LINE 3 Interlocking for double CB bay 1 1 1
ABC_LINE 3 Interlocking for line bay 1 1 1
AB_TRAFO 3 Interlocking for transformer bay 1 1 1
SCSWI Switch controller 8 8 8
SXCBR Circuit breaker 3 3 3
SXSWI Circuit switch 7 7 7
POS_EVAL Evaluation of position indication 8 8 8
SELGGIO Select release 1 1 1
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
8 ABB

IEC 61850/
Function block
name
ANSI Function description Bay
REC650 (A01)
1CBA
REC650 (A02)
1CBAB
REC650 (A07)
BCAB
QCBAY Bay control 1 1 1
LOCREM Handling of LR-switch positions 1 1 1
LOCREMCTRL LHMI control of Permitted Source
To Operate (PSTO)
111
SLGGIO Logic Rotating Switch for function
selection and LHMI presentation
15 15 15
VSGGIO Selector mini switch extension 20 20 20
DPGGIO IEC 61850 generic communication I/
O functions double point
16 16 16
SPC8GGIO Single point generic control 8 signals 555
AUTOBITS AutomationBits, command function
for DNP3.0
333
I103CMD Function commands for
IEC60870-5-103
111
I103IEDCMD IED commands for IEC60870-5-103 1 1 1
I103USRCMD Function commands user defined
for IEC60870-5-103
444
I103GENCMD Function commands generic for
IEC60870-5-103
50 50 50
I103POSCMD IED commands with position and
select for IEC60870-5-103
50 50 50
Secondary system supervision
CCSRDIF 87 Current circuit supervision 1 1 1
SDDRFUF Fuse failure supervision 1 1 1
TCSSCBR Breaker close/trip circuit monitoring 3 3 3
Logic
SMPPTRC 94 Tripping logic 1 1 1
TMAGGIO Trip matrix logic 12 12 12
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
ABB 9

IEC 61850/
Function block
name
ANSI Function description Bay
REC650 (A01)
1CBA
REC650 (A02)
1CBAB
REC650 (A07)
BCAB
OR Configurable logic blocks, OR gate 283 283 283
INVERTER Configurable logic blocks, Inverter
gate
140 140 140
PULSETIMER Configurable logic blocks, Pulse
timer
40 40 40
GATE Configurable logic blocks,
Controllable gate
40 40 40
XOR Configurable logic blocks, exclusive
OR gate
40 40 40
LOOPDELAY Configurable logic blocks, loop delay 40 40 40
TIMERSET Configurable logic blocks, timer
function block
40 40 40
AND Configurable logic blocks, AND gate 280 280 280
SRMEMORY Configurable logic blocks, set-reset
memory flip-flop gate
40 40 40
RSMEMORY Configurable logic blocks, reset-set
memory flip-flop gate
40 40 40
ANDQT Configurable logic Q/T, AND gate
with quality and time
120 120 120
ORQT Configurable logic Q/T, OR gate
with quality and time
120 120 120
INVERTERQT Configurable logic Q/T, inverter
gate with quality and time
120 120 120
XORQT Configurable logic Q/T, exclusive
OR gate with quality and time
40 40 40
SRMEMORYQT Configurable logic Q/T, set-reset
with memory flip-flop gate with
quality and time
40 40 40
RSMEMORYQT Configurable logic Q/T, reset-set
with memory flip-flop gate with
quality and time
40 40 40
Bay control REC650 1MRK 511 249-BEN -
Product version: 1.1 Issued: February 2011
10 ABB
Otros manuales para REC650 ANSI
6
Tabla de contenidos
Otros manuales de Relé de ABB

ABB
ABB Tmax T1 Manual de usuario

ABB
ABB Relion REB500 Manual de usuario

ABB
ABB REJ 527 Manual del producto

ABB
ABB REL 301 Manual de usuario

ABB
ABB REJ 527 Manual del producto

ABB
ABB CVQ Manual

ABB
ABB B23 UL Manual de usuario

ABB
ABB ELR48P Manual de usuario

ABB
ABB SPAU 130 C Manual de lista de piezas

ABB
ABB CR324GXNS Manual de usuario