Wellington SCS Connect Manual de usuario

INSTALLATION PROCESS MANUAL
CONNECT

© 2016 Wellington Drive Technologies Limited
Saving Generaon for the Next Generaon
21 Arrenway Drive, Rosedale, Auckland 0632, New Zealand
PO Box 302-533, North Harbour, Auckland 0751, New Zealand
Phone: + 64 9 477 4500, Fax: + 64 9 479 5540,
Email: info@wdtl.com Website: www.wdtl.com

4 WARNINGS!
7 INTRODUCTION
9 PROCESS OVERVIEW
13 CONFIGURATION OVERVIEW
17 CONFIGURATION
21 ConguraonTroubleshoong
23 INSTALLATION AND WIRING
29 TESTING
33 Troubleshoong
35 IN-FIELD SET-UP
41 In-eldSet-upTroubleshoong
43 APPENDIX 1
Quick Read
TABLE OF CONTENTS
TABLE OF
CONTENTS
INTRODUCTION
& WARNINGS
PROCESS
OVERVIEW
CONFIGURATION
OVERVIEW
CONFIGURATION
WIRING AND
INSTALLATION
TESTINGIN-FIELD SET-UPFAULTS
APPENDICES
PD0009 V1.0 – 22 Jan 2016 3

Quick Read
WARNINGS!
TABLE OF
CONTENTS
INTRODUCTION
& WARNINGS
PROCESS
OVERVIEW
CONFIGURATION
OVERVIEW CONFIGURATION WIRING AND
INSTALLATION TESTING IN-FIELD SET-UP FAULTS APPENDICES
Important Do’s and Dont’s:
Do not use water jets on the
rear of the unit. Warning!
Risk of electrocution. If
correctly installed, powerful
water jets may be applied
only to the front of the unit.
Do not drop the SCS
Connect.
There are no serviceable
parts inside the SCS
Connect. Do not open the
housing. Warning! Risk of
electrocution.
PD0009 V1.0 – 22 Jan 2016
4 4
Pleasereadthefollowingwarningstomaintainthesafefuncon
andconnuedperformanceofyourWellingtonDriveTechnologies
Limited SCS™ Connect controller:
Installaon;
InstallaonoftheSCS Connect controller other than in
accordancewiththe“Descripon&Install”seconofthis
manual will invalidate the warranty. The SCS™ Connect must
onlybeinstalledandconguredbytrainedandauthorizedsta.
Washdown;
Thefrontoftheunitmaybeexposedtowaterjets.Warning!
Therearoftheunitmustnotbeexposedtohighpressure
waterjetsortemporarysubmersion,asthiswillinvalidate
thewarranty,andmaydamageelectroniccircuitsleadingto
prematurefailureorunsafeoperaon.Mounngoftheunit
mustbeinaccordancewithorientaonasspeciedinthe
“Descripon&Install”secon.Warning!Riskofelectrocuon.
Chemicals;
The SCS Connectcontroller’shousingismadeofpolycarbonate,
andshouldnotbeexposedtochemicalswhichaackthis
material,asthiswillinvalidatethewarrantyandmaydamage
thehousing,leadingtounsafeoperaon.Warning! Risk of
electrocuon
Temperature;
The SCS Connectcontrollermustonlybesubjectedto
temperaturesasspeciedinthe“TechnicalSpecicaons”
seconofthismanual.Exceedingtheseranges,eitherin
operaon,installaon,transportaon,orstorage,willinvalidate
thewarranty,andmaydamageelectroniccircuitsandhousing
components,leadingtoprematurefailure.
Vibraonandimpact;
TheunitMUSTbeinstalledinsuchawayastobeprotected
fromimpactinoperaon.Donothitordroptheunit.
Exposuretoimpacts,eitherinoperaon,installaon,
transportaon,orstorage,maydamageelectroniccircuits
andhousingcomponents,leadingtoprematurefailure,and
may cause the SCS Connect controller to become unsafe. Any
impactwhichcausesvisualdamagetothecontrollercasingwill
invalidate the warantee.
Noserviceableparts;
TherearenoserviceablepartsinsidetheSCS Connect
controller.Donotopenthehousing,exceptfortherearcover,
asdescribedinthe“DescriponandInstallaon”seconof
thismanual.Openingoftheelectronicshousing,alterang
ormodifyingtheSCS Connect controller will invalidate the
warrantyandcancauseriskofelectrocuon.

Quick Read
Warnings - cont
TABLE OF
CONTENTS
INTRODUCTION
& WARNINGS
PROCESS
OVERVIEW
CONFIGURATION
OVERVIEW
CONFIGURATION
WIRING AND
INSTALLATION
TESTINGIN-FIELD SET-UPFAULTS
APPENDICES
Do not run power and
signal cables together in the
same conduit. Warning!
Risk of electrocution.
Do not connect the SCS
Connect controller to the
incorrect voltage supply.
Ensure phase and relay
terminals are correctly
crimped. Risk of fire.
PD0009 V1.0 – 22 Jan 2016 5
Thefollowingpartsareconsideredtobesubjecttonormal
wear and tear, and as such are not covered by warranty
•Scratchesandothervisualdamagetofrontpanel
Voltages;
The SCS Connect controller must only be connected to
powersupplieswhichcomplywiththeacceptablevoltage
rangesspeciedinthe“TechnicalSpecicaon”seconof
thismanual.Connecontosupplyvoltagesoutsideofthese
rangescandamageelectricalcircuits,leadingtopremature
failure, and may cause the SCS Connect controller to
become unsafe. All SCS Connectcontroller’sshipfromthe
factorywithvoltagelimitsenabled.Disablingthisprotecon
invalidatesanywarrantyduetoincorrectvoltages.
MaximumvoltagesareloggedbytheSCS Connect controller.
Voltageuctuaonsandsurges;
SCS Connectcontrollerhassurgeproteconasspecied
inthe“TechnicalSpecicaon”seconofthismanual.
Exposuretosurgevoltagesoutsidetheselimits,or
excessivelyrepeatedsurgeswithintheselimits,maycause
damagetoelectricalcircuits,leadingtoprematurefailure.
Failureduetoexcessivesurgevoltagesisnotcoveredby
warranty.
Currents;
SCS Connectcontrolleroutputsshouldnotbeconnectedto
shortcircuitsortoloadswhichexceedthecurrentsspecied
inthe“TechnicalSpecicaon”seconofthismanual.
Doingsomaycausethecontrollertofailprematurelyor
immediately,andpossiblytodamagetheconnectedload.
Connecontoincorrectloadsvoidsthewarranty.
Phaseandrelayterminalsmaycarrycurrentshighenough
tooverheatcableterminaons,ifthesearenotcorrectly
speciedandcrimped.Thismaycauseriskofelectrocuon
orre.Caremustbetakentoensurethatcablesand
terminaonsaresafelyterminated.
Segregaonofpowerandsignalcabling;
Correctsegregaonofpowerandsignalcablingmustbe
followed.Donotrunpowerandsignalcablestogetherin
thesameconduit.Induconfrompowercablesmaycorrupt
datasignals,leadingtoincorrectoperaon.
Consequenalfailures;
SCS Connectcontrollerincludesfeaturestoprotectboth
itselfandconnectedcomponentsintheeventofafailure.
Howeverfailureofconnectedcomponentsmaycause
damagetotheSCS Connect controller, and failure of the
SCS Connectcontrollermaycausedamagetoconnected
components.Cricalorvulnerablecomponentsshould
beprotectedindependentlyagainstfailure.SCSConnect
controllerisnotwarrantedagainstdamagecausedbyorto
othercomponents.

Quick Read
Warnings - cont
TABLE OF
CONTENTS
INTRODUCTION
& WARNINGS
PROCESS
OVERVIEW
CONFIGURATION
OVERVIEW CONFIGURATION WIRING AND
INSTALLATION TESTING IN-FIELD SET-UP FAULTS APPENDICES
The SCS Connect controller
must only be used for the
purposes described in this
manual.
The SCS Connect controller
must not be disposed off
in municipal collections;
it must be disposed off
through an approved
e-waste collection point.
The design and specification
of the SCS Connect
controller is subject to
change without warning.
PD0009 V1.0 – 22 Jan 2016
6
Fitforpurpose;
The SCS Connect controller must only be used for the
purposeandfunconsdescribedinthismanual.While
WellingtonDriveTechnologiesLimitedmayprovide
technicalsupportonsuitableapplicaonsandconguraon
of the SCS Connectcontroller(wheresucharelaonship
mayexist),noliability,responsibilityorriskisacceptedin
determiningiftheSCS Connectcontrolleristforpurpose
foranyparcularapplicaon.Aseachdierentapplicaon
requiresadierentconguraonofcontrollingparameters,
noliability,responsibilityorriskisacceptedbyWellington
DriveTechnologiesLimitedforthecorrectoperaonal
funconofanyparcularinstallaonorconguraon.
Connuousdevelopment;
WellingtonDriveTechnologiesLimitedundertakesto
connuouslydevelopandimproveproductsandservices.
ThedesignandspecicaonfortheSCS Connect controller
issubjecttochangewithoutwarning.Thecontentsofthis
manualaresubjecttochangewithoutwarning.While
everyendeavourismadetoensurethatallspecicaons
anddocumentsarecurrentandcomplete,WellingtonDrive
TechnologiesLimitedacceptsnoliability,responsibilityor
riskduetoomissionsorchangescausedbyconnuous
improvementanddesignchanges.Usersofthismanual
should verify that they have the current released version
(publishedontheWellingtonDriveTechnologieswebsite
www.wdtl.com)beforeproceeding.
Correctdisposal;
The SCS ConnectcontrollerissubjecttoEUDirecve
2002/96/EC(WEEE)fore-waste.Itmayalsobesubjectto
othernaonallegislaonforthesafedisposalofe-waste.
The SCS Connectcontrollermustnotbedisposedoin
municipalcollecons;itmustbedisposedothroughan
approvedWEEEcolleconpoint.Alternavely,theSCS
Connectcontrollermaybereturnedtoanauthorized
WellingtonDriveTechnologiesLimiteddistributorattheend
ofitsworkinglife.Penalesmaybeapplicableforincorrect
disposal,asspeciedbynaonallegislaon.Thecircuit
boardmaycontainhazardoussubstanceswhichcouldaect
healthandtheenvironmentifdisposedoincorrectly.The
SCS ConnectcontrollercomplieswithEUDirecve2002/95/
EC (RoHS).

Quick Read
INTRODUCTION
TABLE OF
CONTENTS
INTRODUCTION
& WARNINGS
PROCESS
OVERVIEW
CONFIGURATION
OVERVIEW
CONFIGURATION
WIRING AND
INSTALLATION
TESTINGIN-FIELD SET-UPFAULTS
APPENDICES
Mobile app with intuitive
touch screen interface
Wireless data logging and
diagnostic control
Compact size
Sealed
PD0009 V1.0 – 22 Jan 2016 7
The SCS ConnectcontrollerbyWellingtonisanelectronic
refrigeraoncontrolunitdesignedtoprovideexibilityfor
manufacturersofrefrigeraonunits.
AuniquefeatureisthemobileappthatgivesauthorizedService
Techniciansfullwirelessaccesstodatalogginganddiagnosc
control.
The SCS Connectcontroller’shousingmeetsindustrybenchmarks
forcompactsizeandexceedsbenchmarksforsealingatthefront
face.
ThisInstallaonProcessManualcoversallthesteprequired
tocorrectlycongureandtestanSCS Connect controller, from
arrivingatthemanufacturer,tobeingfullyinstalledandset-up
readyfortrackingandautomatedfaultdetecon.
TheProcessOverviewsecondiscussestheoverallprocess,
backgroundinformaon,andincludesanoverallprocessow
diagram.Each“Process”thenhasasecondedicatedtoit,witha
owdiagramatthestartoftheseconwhererequiredtoexplain
thesub-stepsinvolved.
Atroubleshoongguideisplacedattheendofeachseconto
helpidenfyandcorrectanyissuesthatmayoccurduringthat
process.

PD0009 V1.0 – 22 Jan 2016
8

Quick Read
PROCESS OVERVIEW
TABLE OF
CONTENTS
INTRODUCTION
& WARNINGS
PROCESS
OVERVIEW
CONFIGURATION
OVERVIEW
CONFIGURATION
WIRING AND
INSTALLATION
TESTINGIN-FIELD SET-UPFAULTS
APPENDICES
Six attributes can be set
Parameters
IDs
Model
Serial No.
Asset No.
Installation Address
PD0009 V1.0 – 22 Jan 2016 9
BetweenarrivingattheManufacturer’sfactory,andacabinet
beingfullyinstalledandcommissionedintheeld,thereare
fourprocessareaswheretheSCS Connectcontrollerundergoes
handling.
Goods received at Factory
Conguraon(Seepage17)
Installaonintothecabinetatthefactory(Seepage23)
Cabinetinstallaonintheeld(Seepage35)
EachprocessarearequiresinteraconwiththeSCS Connect
controller,andaprocessneedstobefollowedtoensure
productqualityismaintained.
Duringtwooftheprocesssteps,dataisrequiredtobeentered
into the controller.
Conguraon
Thisisperformedinthemanufacturer’sfactoryBEFOREthe
controllerhasbeenplacedintothecabinet.
Thiscanbeaspartofanin-lineorbatchprocess.
Informaonisenteredthroughtheuseofadockingcradle
connectedtoacomputer(Seepage17)
Cabinetinstallaonintheeld.
Informaonisenteredthroughtheuseofamobilephone
applicaon(Seepage35)
The order in which data is entered into the controller, and
atwhichprocessstepmaydierfrommanufacturerto
manufacturerandownertoownerdependingonexisng
manufacturingprocesses.

Conguration
Installation and Wiring
Cabinet Test
Transportation to
Customer Warehouse
COMPLETE
Goods Inwards Checking
Transportation to
Retail Outlet
Installation in Field
Delivery to Manufacturer
Data Entry
SeePageX
SeePageX
Data Entry
SeePageX
SeePageX
Overall Process
Process Flow
TABLE OF
CONTENTS
INTRODUCTION
& WARNINGS
PROCESS
OVERVIEW
CONFIGURATION
OVERVIEW CONFIGURATION WIRING AND
INSTALLATION TESTING IN-FIELD SET-UP FAULTS APPENDICES
PD0009 V1.0 – 22 Jan 2016
10