BESMOKEYV2 - User Manual
Smoke Alarm, Photoelectric, Surface Mount
220-240V AC, 9V Battery Back Up / Individual or Interconnected
Thank you for purchasing our smoke alarm. This instruction contains important
information on the correct installation and operation of your smoke alarm.
Read this instruction fully before attempting installation and retain them
for future reference.
Standard: AS 3786-2014
Licence Number: SMK41282
WARNING:
• This product must only be installed and serviced by appropriately qualied electrician;
• This product must only be used for the purpose described in these instructions and must be installed in
accordance with the wiring rules and regulations in local location.
• Hazardous voltage may be presented at the wire leads of this product.
• Disconnect the AC power before installing or removing the smoke alarm.
• Ensure that the product has been correctly installed and tested for safe operation before reconnecting the
electrical supply.
• DO NOT connect the interconnection wire to Live or Neutral.
• A non-pure sinusoidal power sources is not suitable for this smoke alarm (e.g. derived from square-wave
invertors).
• The apparatus shall not be exposed to dripping or splashing and that no objects lled with liquids, such as
vases, shall be placed on the apparatus.
Failure to follow these instructions may result in death or serious injury.
Specications:
Main Power Source 220-240V AC 50 Hz
Secondary Power Source
Suitable batteries: GP DC 9V carbon battery or PAKKO DC 9V
carbon battery; or EVE DC 9V Lithium battery; or Raymax DC
9V Alkaline battery
AC Operating Current <60mA
Interconnecting Max. 24 alarms (wired 150m maximum)
Operating Temperature 0 °C to 40 °C
Ambient Humidity 5-95%
Alarm Sensitivity 0.100-0.180 dB/m
Alarm Volume ≥ 85dB(A) @ 3m
Sound Pattern
ISO8201(BI 0.5s - pause 0.5s - BI 0.5s - pause 0.5s - BI 0.5s
- pause 1.5s, with the RED LED ashing, repeat this alarm
pattern)
Comply with AS 3786:2014+A 1 :2015+A2:2018
Product function description:
Function Indication Description
Standby status The Red LED ashes about every 48
seconds. The unit is working.
AC power indication The Green LED illuminates continuously. The unit is receiving AC power.
Low battery warning The unit chirps with Red LED ashing
about every 48 seconds.
The battery voltage is too low, must replace a new battery
within 30 days.
Fault warning The unit beeps twice and ashes twice
every 48 seconds
The unit is faulty, get helps from the section:“Trouble
Shooting”.
Self-test fault warning The Red LED ashes twice about every
48 seconds. The buzzer fault or buzzer detection circuit fault.
End-of-life warning The unit chirps between the Red LED two
times ashing.
The unit will send end-of-life warning after working 10
years. Need to replace a new smoke alarm.
Test function
The Red LED ashes once every second
with alarm sounding until the TEST
button is released.
• Test by pressing the TEST button on the smoke alarm
at least 5 seconds.
• The alarm will sound if all electronic circuitry, horn
and battery are working properly.
• If no alarm sounds, refer to“Trouble Shooting”.
• Recommend testing the alarm Weekly by pressing
the TEST button.
Silence function The Red LED ashes every 8 seconds.
• This smoke alarm has a built-in Silence feature.
• If cooking or other non-hazardous sources cause the
alarm to sound, it can be temporarily silenced by
pressing the HUSH button for above 2 seconds.
• The alarm enters silence mode for 10 minutes.
• After the 10 minute dormant period, the smoke
alarm will resume normal ooeration.
Fire alarm The Red LED ashes every second, with
alarm sounds. Generate alarm sounds when re happening.
Fire alarm memory The Red LED ashes twice every 24
seconds.
After the unit exits Fire alarm state, it enters the Fire alarm
memory state, and the red LED ashes twice every 24
seconds for 72 hours.
Interconnection alarm The unit generates alarm sounds without
Red LED ashing.
The unit will enter the interconnection alarm mode when
received wire interconnection alarm signals.
Interconnection alarm
memory The Red LED ashes once every 1 second.
After the unit exits Interconnection alarm state, it enters
Interconnection alarm memory state, and the red LED
ashes once every 1 second for 3 minutes.
Do not disturb The Red LED ashes about every 48
seconds.
The unit will stop nuisance warning about 10 hours
under low battery or fault mode when the HUSH button
is pressed.
CAUTION:
• Before using the silence function, identify the source of the smoke and make sure a safe condition existing.
After 10 minutes silence, the unit will resume to normal operation.
• DO NOT use an open ame to test your alarm which may damage the alarm or ignite combustible materials
and result in a re.
• If the alarm sounds, and it is not being tested, it means the unit detected smoke. THE SOUND OF THE ALARM
REQUIRES YOUR IMMEDIATE ATTENTION AND ACTION.