Touch-plate Nexus NEX-MB-XX Guía del usuario

Nexus System Manual

Table Of Contents
Precautions...............................................................................................................................................2
Compatible Hardware .............................................................................................................................2
Warranty. ..................................................................................................................................................2
Nexus Overview .....................................................................................................................................3
Nexus Contact Closure Input Wiring . ...................................................................................................4
Nexus Power Wiring.................................................................................................................................5
Nexus 2-Wire Wiring ................................................................................................................................6
Nexus 5-Wire Wiring . .............................................................................................................................7
Nexus Firing Card Wiring ........................................................................................................................8
Nexus MS/TP RS485 Wiring.....................................................................................................................9
Nexus Softpatching ...............................................................................................................................10
Programming Contact Closure or Station Inputs.. ............................................................................10
Appendix I - Powering the Nexus . ......................................................................................................11
Appendix II - Discovery Mode ..............................................................................................................11
Appendix III - Clearing the Programming. .........................................................................................11
Appendix IV - Programming Interface Explanations . .......................................................................12
Appendix V - Programming Interface Explanations ..........................................................................13
Appendix VI - Option Dip Switches .....................................................................................................14
Troubleshooting Guide ........................................................................................................................15
Frequently Asked Questions.................................................................................................................16
4822 Projects Dr lFort Wayne, Indiana 46825 l1.260.426.1565 lwww.touchplate.com

Page 2
www.touchplate.com
Touch-Plate® Lighting Controls
Nexus System Manual
Precautions
The Nexus hardware is designed to be in environments that have a temperature range of 0-60°C
(non-condensing atmosphere). Installing in an environment outside of these parameters will short-
en the life span of the hardware.
Touch-Plate recommends the use of 18 to 22 AWG wire for low voltage wiring of contact closure
products, 18 AWG wire for all 24V power connections, and 16 AWG wire for 2-wire Smart Switch
Stations.
All 120VAC wiring must use wire as specified by National Electric Code for load size and wire length.
Compatible Hardware
• Digital Control Stations
• 2-Wire Stations (Mystique and Ultra Series)
• 5-Wire Stations (Mystique and Ultra Series)
• Contact Closure Control Stations via Smart Control Bridge or on board inputs
• Panel Products (Solare, Soluxe, Calypso, and ZoneZ Series)
Warranty
Touch-Plate warrants this product against defects in materials or workmanship, under normal use,
for a period of ONE (1) year from date of shipment. If a defect arises and a valid claim is received
within the Warranty Period, Touch-Plate will repair or replace the product at no charge.
This warranty does not apply to:
a. Damage to unit(s) caused by accident, acts of God, inappropriate installation, faulty
installation, or any negligent use;
b. Unit(s) which have been subject to being taken apart or otherwise modified;
c. Unit not used in accordance with instructions;
d. The finish on any portion of the product, such as surface and/or weathering, as this
is considered normal wear and tear;
e. Non-Touch-Plate hardware installed by the user;
f. Damage caused by Non-Touch-Plate products;
g. Damage caused by operating the product outside the permitted or intended uses
described by Touch-Plate;
h. -or- Specific plans or Specific application requirements, unless the plans and
specifications have been forwarded to Touch-Plate and Touch-Plate has approved
and accepted the plans in writing.
EXCEPT AS PROVIDED IN THIS WARRANTY, TOUCH-PLATE IS NOT RESPONSIBLE FOR DIRECT, SPECIAL,
INCIDENTAL, OR CONSEQUENTIAL DAMAGES RESULTING FROM ANY BREACH OF WARRANTY OR CONDITION,
INCLUDING BUT NOT LIMITED TO, INSTALLATION OR REPLACEMENT LABOR COSTS.

A
B
CDEF G
H
I
J
Touch-Plate® Lighting Controls
Nexus System Manual
Page 3
www.touchplate.com
Nexus Overview
The Nexus menu is an on board menu. The LEDs lit on the Nexus menu options are the cursors. As
you navigate through the menu options look for and use the cursors.
The Nexus is capable of operating in a BACnet system or as a Standalone system. For BACnet instal-
lations and operation please see the Nexus BACnet Manual.
Board Items Options Board Position Page #
Low Voltage Connections Contact Closure Switches A 4
18-24VDC Power B
2-Wire Control Stations C
5-Wire Control Stations D
Firing Cards (Relays/Dimmers) E
RS485 (BACnet MS/TP) F
Dip Switches MS/TP Address GN/A
Options H
Programming Programming Interface I
Clear/Discover J

Wired to Contact
Closure Switch
Page 4
www.touchplate.com
Touch-Plate® Lighting Controls
Nexus System Manual
Nexus Contact Closure Input Wiring
To correctly wire the Contact Closure Inputs to the Nexus, use the wiring diagram below.
Recommended gauge wire is 16-26.

Wired to 18-24VDC
Transformer
Touch-Plate® Lighting Controls
Nexus System Manual
Page 5
www.touchplate.com
Nexus Power Wiring
To correctly bring power to the Nexus, use the wiring diagram below. Power must be a Class 2, Iso-
lated Transformer, with a rating of 18-24VDC. This will typically come from the factory pre-wired.
The power connection is not polarity sensitive.

Wired to 2-Wire
Station or Sensor
Page 6
www.touchplate.com
Touch-Plate® Lighting Controls
Nexus System Manual
Nexus 2-Wire Wiring
To correctly wire the 2-Wire connection to the Nexus, use the wiring diagram below.
•2-Wire Stations and Sensors are not polarity sensitive (topology free).
Wire must be Tappan 1680AB2/CMP (16 AWG, 2 Conductor, Twisted, Unshielded) or an equivalent wire.

Wired to 5-Wire
Station or Sensor
Touch-Plate® Lighting Controls
Nexus System Manual
Page 7
www.touchplate.com
Nexus 5-Wire Wiring
To correctly wire the 5-Wire connection to the Nexus, use the wiring diagram below.
Wire must be Axlink 22/01PSH + 18/2C or an equivalent wire.

Wired to
Touch-Plate Firing
Card
Page 8
www.touchplate.com
Touch-Plate® Lighting Controls
Nexus System Manual
Nexus Firing Card Wiring
To correctly wire the Firing Card connection to the Nexus, use the wiring diagram below.
Wire must be Cat5e or an equivalent wire.
Typical items wired via the RJ-45 connection are: Touch-Plate Relay and Dimmer Firing Cards.

Green: (S)
Black: (-)
Red: (+)
Touch-Plate® Lighting Controls
Nexus System Manual
Page 9
www.touchplate.com
Nexus MS/TP RS485 Wiring
To correctly wire the RS485 connection to the Nexus, use the wiring diagram below.
•Shield or Ground for MS/TP RS485 connection must be isolated from the ground
on the power supply. Using the same ground will create a direct short across the
diode bridge and damage the unit.
Wire must be Liberty 18/2C SHLD or an equivalent wire.
Tabla de contenidos