
5
CP 1 ~ 200
5.0
-199.9 ~
999.9
0
K1
DB
INP
2. Advanced menu illustration
9
11
12
13
14
15
17
16
AL1
AD1
(1)
AL2
HY2
AD2
(1)
FL ~FH
10 HY1 0 ~1000
0 ~12
10
FL ~FH
5
1
0 ~1000
1
0 ~6
4
3
30
5
1
I
0~9999 120
18
19
20
21
22
23
24
D
OVS
0~9999
0~9999
OT Control Mode,0:ON/OFF Heating control;1:PID
heating;2:ON/OFF Cooling control;3:Reserved;
4:Over temperature cooling output;5:PID Cooling
0
~
5 1
P 0~9999 30
A-M AUTO~AM AUTO
PS
-1999 ~ 9999
0
0
25
Control Mode,0 ~1:SSR Output or Transistor output
ACT 0
~
1
0
26 AE1
(2) 0~5
0
27 AE2
(2) 0~5
1.0
0~3DP28
(0~20)
DTR 0.0 ~ 2.0
0
29
SSM Press the key on the panel to switch the RUN/STOP
operation switch, 0: prohibited, 1: OPEN 0 ~1
0
30
SLL
SLH
Low limit of target setting value range
High limit of target setting value range
FL~FH
FL~FH
33 FL
34 FH
OLL
OLH
35
FT 0 ~ 255 10
0
-5.0 ~ 100.0
0.0 ~ 105.0
0.0
100.0
36
37
38
39
40
41
42
43
Temperature unit setting ℃: Celsius ℉: Fahrenheit,
note: this unit setting is only for temperature
measurement signals,“_”: No unit display
PT
PDC
UNIT
0 ~ 9999
FUZ/STD
(25)℃
(26)℉
FUZ
(25)℃
31
32
PRS EEP/RAM EEP
RSS
LPH
EEP/RAM EEP
0.0~999.9 0.0
The actual power of each channel load, used for the
total power limit; Unit: KW.When set to 0, this channel
don't participate in power limitation
No.
Name
Symbol
Illustration Setting range
Factory
setting
1st alarm value, note: the minus is dealed as absolute
value when it is as a deviation value.
1st alarm hystersis
1st alarm mode,note: when AD1=0, close alarm
function . When AD1>6, 2nd alarm function is invalid.
2nd alarm value, note: the minus is dealed as
absolute value when it is as a deviation value.
2nd alarm hystersis
2nd alarm mode
Overshoot limit, during PID control process, when PV(measured
value) > SV(set value) + OVS(overshoot limit), force to close output.
The smaller this value is, the smaller the PID adjustment range is,
the worse the control stability is. Please set the appropriate value
according to the actual situation.This function is unavailable when it is
set to 0
Differential time:The system oscillation can be
prevented by reducing the differential action to a
suitable value. The larger the value is, the stronger
the differential action is. Unit: s
Integral time, the smaller the value is, the stronger the integral action is,
otherwise, it is weeker. and the more it tends to eliminate the deviation
from the set value. The deviation may not be eliminated if the integral
effect is too weak. Unit: s
Proportional band: the smaller the setting value is, the faster the system
responds; otherwise, it is slower.Increasing the proportional band can
reduce the oscillation, but it will increase the control deviation. Decrease
the proportional band can reduce the control deviation, but it will cause
oscillation. Unit: corresponding measured value
Auto-manual control switch, AUTO(0): auto control
only; MAN(1): manual control only;
OUT1 control cycle, 1: SSR control output,
4-200: relay control output. Unit: s
Position control hystersis(Negative return differential
control),or cooling control and compressor refrigeration
control dead zone.after change the INP setting, please
change this parameter according to the decimal point
position.
Optional input signal. see the corresponding table of
input signal parameters for details,Note: other
relevant parameters to be modified
Amend value, display value= actual measured value
+ amend value
refer to input
signal para-
meters table
(page 2)
No.
Name
Symbol
Illustration
Setting range
Factory
setting
1st alarm extensions function,refer to alarm extension
function table
2nd alarm extensions function,refer to alarm
extension function table
Decimal point setting is effective under the linear
signal input
PV fuzzy tracking value,properly set this value on some
occasions, it can get a more stable control display value,
this value is unrelated with actual measured value. Note:
after setting this value,when alarm setting value is equal
to SV setting value, alarm output operation is subject to
actual measured value. Set as 0 to close this function.
The temperature input unit: Fahrenheit or Celsius.The
linear signal input unit: Engineering Digits
Measure range low limit,the setting value
must be less than measure range high limit
Measure range high limit,the setting value
must be more than measure range low limit.
Refer to
measured signal
parameter table
Refer to
measured signal
parameter table
Output low limit, limit the output low limit current amplitude.
Setting value must be less than high limit setting
Output high limit,limit the output high limit current amplitude.
Setting value must be greater than low limit setting
PV digital filter coefficient, the value larger,the
stronger of the filtering effect
Compressor start delay time, unit: s
PID algorithm option:0(FUZ): Advanced fuzzy PID
arithmetic; 1(STD): normal PID arithmetic
Setting parameter reserve position: 0 (EEP):EEPROM
with power failure protection; 1(RAM): RAM without power
failure protection. Description of setting parameter storage
location: EEP and RAM. EEP means that the setting
parameters are written into EEPROM and can be
permanently saved after power failure.It is generally used
for factory setting parameters of equipment. Because
EEPROM has the limit of writing times, too many and too
frequent writes will be damaged;RAM: it means that the
parameters are stored in RAM without writing limit and will
not be damaged due to frequent writing. The parameters
set after the equipment is powered off will not be saved.
After power on, they will be restored to the parameters
saved in EEPROM by the equipment manufacturer.It is
usually used for frequent parameters writing when
communicating with the upper computer PLC.
The method of using this parameter is to set this parameter
to EEP first. After the equipment factory has finished debugging
the equipment and set the parameters, the parameters
are saved in EEPROM, and then PRS is modified to RAM,
and the equipment is delivered to the user for use, so as to
prevent erroneous modification or long-term communication
writing data from damaging the EEPROM.
RUN/STOP reserve position: 0 (EEP):EEPROM with power
failure protection;1(RAM): RAM without power failure protection.
this parameter method: if the instrument is required to be in stop
mode every time when it is powered on, first set RSS to EEP,
and then set "start stop operation" = STOP. This setting parameter
will be saved for a long time; Then set RSS to RAM. When using,
the upper computer starts/stops the instrument, which is stored in
RAM. After power on again, the instrument still enters STOP mode.
6
(3)Auxiliary output function table
X. Key function operation
Continued
44
47
48
49
50
SLPL
DN
DNS
DNT
VER
0.0~999.9
1~16 16
1~84
0~99
—— ——
1
4
45
46
AU1P
(3)
AU2P
(3)
0~32 1
0~32 17
Auxiliary output 1 programming, use for programming
AU2 output function
Auxiliary output 2 programming, use for programming
AU2 output function
0.0
Total power limit, limits the power distribution of each
participating channel when the total power of channel output
controls exceeds the total power limit value; Unit: kW; Set to 0,
no power limit function
1. Monitoring mode operation(RUN/STOP)
1)SSM is set in open meter operation; Otherwise, the settings only be modified during communication.
2)Under the measure mode, long press “ ” key to enter the STOP mode, SV window will display
“STOP”, main control output will stop or keep the minimum output.
3)Under STOP mode, long press “ ” key to exit STOP mode, press “ ” key to modify SV value.
4)Under STOP mode, alarm output and analog output work normally.
2. PID auto-tune operation:
1)Before auto-tune procedure, please switch off the control output load power, or set the meter as STOP
mode.
2)Before auto-tune procedure, PV value should meet below condition: when it is PID heating control, PV
needs to be much smaller than SV; when it is PID cooling control, PV needs to be much larger than SV.
3)Before auto-tune procedure, please set a proper alarm value or eliminate the alarm condition, in
order to prevent the auto-tune procedure from being affected by alarm output.
4)Set PID type and SV value; the factory default setting is fuzzy PID.
5)Set as PID control, if there is OLL & OLH output limiting, please set the output to a proper range;
factory default setting is OLL=0%, OLH=100%.
6)Exit STOP mode, or switch on the load Power, immediately long press “ ” key to enter auto-tune
mode, then the AT indicator light is on.。
7)The auto-tune procedure will take some time, in order not to affect auto-tune result,please don`t modify
the parameters or power-off.
8)When AT light goes out, it automatically exits auto-tune mode, PID parameters will be updated
automatically, and then the meter will control automatically and exactly.
9) During the auto-tune procedure, below actions will cause the termination of the precess, long press
“ ” key, measure beyond the scope, abnormal display, switch to STOP mode, power-off, etc.
10)Note: In the occasions with output limiting operation, sometimes, even if the auto-tune is carried out,
the best PID parameters still cannot be obtained.
11)Experienced users can set a proper PID parameter according to their experience.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Code Function
NO
CH1-AL1
CH2-AL1
CH3-AL1
CH4-AL1
CH5-AL1
CH6-AL1
CH7-AL1
CH10-AL1
CH9-AL1
CH11-AL1
CH12-AL1
CH13-AL1
CH14-AL1
CH15-AL1
CH16-AL1
CH1-AL2
CH2-AL2
CH3-AL2
CH4-AL2
CH5-AL2
CH6-AL2
CH7-AL2
CH8-AL2
CH9-AL2
CH10-AL2
CH11-AL2
CH12-AL2
CH13-AL2
CH14-AL2
CH15-AL2
CH16-AL2
CH8-AL1
Code Function Code Function Code Function
No.
Name
Symbol
Illustration Setting range
Factory
setting
Display the number of channels, indicating the number
of measurement channels actually used by the instrument
Display the starting channel number, which is used to indicate
number of channel 1 in multi-machine application. For example:
when DNS=3, CH3~CH18 represent 1~16 channels respectively
Channel cycle display time, 0 means cancel automatic cycle display
Software version.
7
8
9
10
11
12
High and low limit absolute
value interval alarm
※High and low limit deviation
value interval alarm
High/low limit absolute value
alarm
High/low limit deviation value
alarm
※High limit absolute value
and low limit deviation value
interval alarm
※High limit deviation value
and low limit absolute value
interval alarm
SV
SV
SV
SV
SV
SVSV-AL1
SV-AL1
SV-AL1
SV+AL2
SV+AL2
SV+AL2
AL2
AL2
AL2
AL1
AL1
AL1
(1) Alarm parameters and output logic diagram:
Symbol description: “☆” means HY, “▲” means alarm value, “ ” means SV value
Alarm
code Alarm mode
Alarm
code Alarm mode
Alarm output(AL1 & AL2 are independent from each)
Image:the hatched section means the alarm action
The below two alarm parameters(AL1,AL2) are used in
combination, AL1 alarm output, AD2 must be set as 0
PV
PV
PV
PV
PV
PV
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
▲▲
△
△
▲▲
△
▲▲
△
▲▲
△
▲
▲
▲
▲
△
△
High limit absolute value
alarm
1
2
3
4
5
6
※High limit deviation
value alarm
※Low limit deviation value
alarm
※High/low limit deviation
value alarm
※High/low limit interval
value alarm
Low limit absolute value
alarm
SV+AL
SV+AL
SV-AL
SV-AL SV
SV SV+ALSV-AL
AL
SV
SV
SV
SV
PV
PV
PV
PV
PV
PV
AL
☆
☆
☆
☆☆
☆
☆
▲
▲ ▲
▲ ▲
▲
△
△
△
☆
▲
△
△
△
▲
※When the alarm value with deviation alarm is set as a negative number, it will be dealed as an
absolute value.
(2)Alarm extension function table
AE1/AE2
value
0
1
2
3
4
5
Alarm handling method when
it displays HHHH/LLLL Power on, alarm inhibition
Power on, no alarm inhibition
(As long as the alarm condition is met, alarm
output immediately.)
Power on, alarm inhibition
(After power on and before the PV value reaches
the SV for the first time, the alarm is forced to
close, After that alarm work normally)
Alarm status remains the same
Forced alarm output
Forced alarm close
Alarm status remains the same
Forced alarm output
Forced alarm close