Texmate, Inc. Tel. (760) 598-9899 • www.texmate.comApr-23-2009 FL-B101D40 DS (FL7) Page 1
Now featuring New Version 2.0 software
with one-color Brightness control, this smart
Tricolor or Mono-color digital bargraph has four
fully programmable set points for monitoring,
measurement, and control applications.
• External transmitters or signal conditioners can be eliminated
by direct connection of the sensor output to more than
40 Plug-in Input Signal Conditioners that include:
– AC/DC Current – Pressure – Resistance
– AC/DC Voltage – Process – Temperature
– Load Cell – Prototype – 4 to 20 mA
• Optional isolated 16 bit analog output. User or factory scal-
able to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across any
desired digital span from ± one count to the full scale range
of – 1999 to 9999 (12000 counts).
• A Programmable Tricolor (Red-Green-Orange) or mono
color (red or green), 101 segment high brightness bargraph.
Vertical or optional horizontal format.
• Red 4-digit LED display with a range of -1999 to 9999
(12000 counts). Optional green digital display.
• Front panel LED annunciators provide indication of setpoint
status.
• Two 10 Amp Form C, and two 5 Amp Form A relays available
• Auto-sensing AC/DC power supply. For voltages between
85-265 V AC / 95-370 V DC (PS1) or 18-48 V AC / 10-72 V
DC (PS2).
• 24 V DC excitation is available to power external 4/20mA
transmitters and 5 or 10 V DC excitation is available for
resistance bridge type sensors.
• Provision to connect an external programming lockout switch.
• Provision for external DIM switch to reduce the brightest
display setting by 50%.
• Optional NEMA-4 front cover.
• Automatic intelligent averaging, smooths noisy signals while
providing a fast display response to real level changes.
Input Specs: ..............Depends on Input signal conditioner
A/D Converter:...........14 bit single slope
Accuracy:...................±(0.05% of reading + 2 counts)
Temp. Coeff.:.............100 ppm/°C (Typical)
Warm up time:...........2 minutes
Conversion Rate: ......10 conversions per second (Typical)
Digital Display:..........
4 digit 0.31" LED red (std), green (optn)
Range
–1999 to 9999 counts.
Bargraph Display:.....
101 segment 4” red vertical (std),
green or tricolor (optn), horizontal (optn)
Polarity:......................Assumed positive. Displays – negative
Decimal Selection:....Front panel button selectable, X•X•X•X•
Positive Overrange:..Bargraph and top segments of digital
display flash.
Negative Overrange:.First segment of bargraph and bottom
segments of digital display flash.
Relay Output: ............Two 5 Amp Form A relays and Two
10 Amp Form C relays.
Analog Output:..........Isolated 16 bit user scalable mA or V
OIC (mA out)...........
4-20 mA @ 0 to 500Ωmax loop resistance
OIV (volts out).......... 0-10 V DC @ 500 Ωor higher resistance
Power Supply:...........AC/DC Auto sensing wide range supply
PS1 (std) ................
85-265 VAC / 95-370 VDC @ 2.5W max 4.2W
PS2 .........................
18-48 VAC / 10-72 VDC @ 2.5W max 4.2W
Operating Temp.:.......0 to 60°C
Storage Temp: ...........–20°C to 70°C
Relative Humidity: ....95% (non condensing)
Case Dimensions:.....
9/64 DIN (Bezel 36Wx144Hmm)
Depth behind bezel (5.83") 148mm
Plus (0.7”) 18mm for connectors
Weight:.......................9.5 oz., 12 oz when packed
General Features Input Module Compatibility
Specifications
Index
LEOPARD FAMILY
FL-B101D40
Leopard Bargraph Meter
101 Segment, 4 Digit 0.32” LEDs
in a 9/64 DIN CASE
• The bargraph can display, full
scale, any desired portion of
the digital reading.
•
Bargraph center zero function.
•
Four programmable setpoints
with adjustable Hysteresis.
• Setpoint 1 has delay-on-
make and delay-on-break
plus a special “pump on
pump off” mode that creates
Software Features
a Hysteresis Band between
SP1 and SP2.
• Relay activation can be
selected to occur above (hi)
or below (Lo) each setpoint.
• Digital display blanking.
• Decimal point setting.
• Four-level brightness control
accessed by the button
and adjusted by the
button.
Bargraph Center Point Display Mode Selection . . 6
Bargraph Color Programming Mode . ...... 9
CaseDimensions....................... 7
Component Layout . ................... 11
Connector Pinouts . ................... 10
Connectors . ......................... 11
Controls and Indicators . ................ 2
Custom Faceplates and Scales . ......... 19
Decimal Point and Brightness Selection . . . . 5
Programming Conventions . . . . . . . . . . . . . . . 2
Setpoint Setting & Relay Configuration Mode . . 8-9
SoftwareFeatures...................... 1
Software Logic Tree . . . ................. 3
Specifications . ........................ 1
Standard Faceplates and Scales . . . . . . . . . 18
Two Point Analog Range Setting & Calibration. . . 7
Two Point Digital Calibration Mode . ....... 4
Digital Span Selection for Display . . . ...... 5
Digital Span Selection for Analog Range Output . 6
Functional Diagram . . . . . . . . . . . . . . . . . . . . 10
GeneralFeatures....................... 1
I-Series Input Signal Conditioning Modules . . 12-15
Input Module Calibration Procedures . ... . 17
Input Module Component Glossary . . . . . . . 16
Ordering Information . . . . . . . . . . . . . . . . . . . 20
Pin Descriptions . ..................... 10
Version 2.0
LEOPARD
✔LEOPARD FAMILY: More than 38 different
Plug-in I-Series Input Signal Conditioners are
approved for Texmate’s Leopard Family of meters.
Some examples are shown on pages 12 - 15.
See www.texmate.com for an up to date listing.