8. Control and monitoring using SNMP
TCW110 can be configured and monitored through S MP (Simple etwork
Management Protocol). This could be done using every S MP v.1 compatible program.
Parameters that can be changed, are grouped according to their functions in the tables below.
To obtain a valid OID number it is necessary to replace the “x” symbol with the prefix
”.1.3.6.1.4.1.17095”. To save the changes you should set a value ”1” of the
configurationSaved (OID x.8.0).
8.1 roduct
OID Name Access Description Syntax
x.1.1.0 name read-only Device name String
x.1.2.0 version read-only Software version String
x.1.3.0 date read-only Date of the version String
8.2 SNMP Setu
OID Name Access Description Syntax
x.2.1.1.0 trapEnabled read-write RAP messages enable/disable IN EGER { Yes(1), No(0) }
x.2.1.2.0 trapReceiverIPAddress read-write RAP messages receiver address IpAddress
x.2.1.3.0 trapCommunity read-write RAP community String (SIZE (0..13))
x.2.1.4.0 trapInterval read-write RAP messages interval IN EGER (0..255)
x.2.1.5.0 maxNumberOf raps read-write maximum number SNMP RAP messages IN EGER (0..255)
x.2.1.6.0 digitalInput1State read-write Digital input 1 trap status IN EGER { ON(1), OFF(0) }
x.2.1.8.1.0 voltage1minimum read-write Voltage1 lower range String (SIZE (0..13))
x.2.1.8.2.0 voltage1maximum read-write Voltage1 higher range String (SIZE (0..13))
x.2.1.10.1.0 temperatureMinimum read-write emperature lower range String (SIZE (0..6))
x.2.1.10.2.0 temperatureMaximum read-write emperature higher range String (SIZE (0..6))
x.2.2.0 SNMPConfiguration read-write SNMP Configuration IN EGER { ENABLED(1), DISABLED(0) }
x.2.3.0 readCommunity read-write SNMP Read Community String (SIZE (0..13))
x.2.4.0 writeCommunity read-write SNMP Write Community String (SIZE (0..13))
8.3 monitor
OID Name Access Description Syntax
x.3.1.1.0 relay_1 read-write relay 1 status IN EGER { ON(1), OFF(0) }
x.3.1.3.0 pulse_1 read-write relay 1 pulse status IN EGER { ON(1), OFF(0) }
x.3.2.1.0 voltage1 read-only Analog Input 1 voltage String (SIZE (0..4))
x.3.2.2.0 vol1int read-only Analog Input 1 voltage
(integer x100mV) IN EGER (0..65000)
x.3.3.1.0 digitalInput1 read-only Digital Input 1 status IN EGER { ON(1), OFF(0) }
x.3.4.0 temperature read-only temperature String (SIZE (0..4))
x.3.5.0 tempx10Int read-only emperature (integer x 10) IN EGER (-550..1250)