Entering Settings: When the SET button is pressed while on any measurement page, the
PASSWORD page (Figure-2) is displayed to enter the menu.
While on this page, press the SET button to enter the menu.
(The password value is "0000" by default. If the password has been changed by the user, the
password specified by the user must be used to enter the menu.)
For password entry, you can switch between the steps with the RIGHT button. You can change
the value of the digit with the UP button.
If no button is pressed for 30 seconds in the menu, the device returns to the main screen.
CURRENT MENU (Menu 1.0): It is the first menu that appears when you proceed by pressing
the UP button after entering the settings menu (Figure-3). In this menu, high/low current set
values, error delays, automatic reset delays, automatic reset numbers, demurrage multiplier
and demurrage time and current asymmetry set value settings can be set.
VOLTAGE MENU (Menu 2.0): It is the second menu that appears when you proceed by pressing
the UP button after entering the settings menu (Figure-4). In this menu, high/low voltage set
values, error delays, automatic reset delays, voltage asymmetry set value and phase sequence
protection feature set value settings can be set.
ELECTRODE MENU (Menu 3.0): It is the third menu that appears when you proceed by pressing
the UP button after entering the settings menu (Figure-5). In this menu, electrode set value,
well and tank electrode reading values, electrode delay times, high/low cosine set values,
cosine automatic reset delays set value settings can be set.
ADVANCED SETTING MENU (Menu 4.0): It is the fourth menu that appears when you proceed
by pressing the UP button after entering the settings menu (Figure-6). In this menu, starting
time, Modbus RTU communication settings, start/stop memory, star waiting time, panel
control feature, alarm relay assignment set value settings can be set.
EXPERT SETTING MENU (Menu 5.0): It is the fifth menu that appears when you proceed by
pressing the UP button after entering the settings menu (Figure-7). In this menu, engine
operation information, voltage, current and cosine error records can be displayed. Factory
values can be restored, menu language and password values and screen light off time set
value settings can be set.
Settings E Current Menu
It is the first menu that appears after you enter the settings
menu. In this menu, high/low current set values, error delays,
automatic reset delays, automatic reset numbers, demurrage
multiplier and demurrage time and current asymmetry set
value settings can be set.
To enter the Current Menu, press the SET button while the
Current Menu page is on the screen. Use UP and DOWN
buttons to access other settings in the menu.
AKIM TRAFO
Menu.1.0
MENUSU
Menu 1.0
CURRENT MENU
Esc Set Up Down
_____________________
Menu 1.1
High Current Set
50.0A
_____________________
Esc Set Up Down
It determines the maximum operating current (overload) of
the pump.
To change this value, press the SET button while the High
Current Set page is on the screen. “Menu 1.1.0” will appear
on the screen. Enter the new value to the device using the UP
and DOWN buttons and press the SET button to save.
Settings E Current Menu E High Current Set Value