Modulating Output 1 Proportional Band
Screen. Enter the number of degrees away
from the heating setpoint that the valve or
damper will be fully open.
Modulating Output 2 Proportional Band
Screen. Enter the number of degrees away
from the cooling setpoint that the valve or
damper will be fully open.
Modulating 1 Setpoint Offset Screen.
Enter an offset value for modulating output
1. This is the number of degrees below the
heating setpoint before the output begins to
modulate.
Modulating 2 Setpoint Offset Screen.
Enter an offset value for modulating output
2. This is the number of degrees above the
cooling setpoint before the output begins to
modulate.
Modulating 1 Output Action Screen.
Choose whether modulating output 1 will be
direct or reverse acting.
Modulating 2 Output Action Screen.
Choose whether modulating output 2 will be
direct or reverse acting.
Modulating Output 1 Range Screen.
Choose whether the modulating output 1
range will be 0-20 mA or 4-20 mA.
Modulating Output 2 Range Screen.
Choose whether the modulating output 2
range will be 0-20 mA or 4-20 mA.
Modulating Output 1 Unoccupied Action
Screen. Choose whether the modulating
output 1 unoccupied action will be 0mA,
4mA, 20mA or MODulating.
Modulating Output 2 Unoccupied Action
Screen. Choose whether the modulating
output 2 unoccupied action will be 0mA,
4mA, 20mA or MODulating.
Discharge Air Sensor Function Screen.
Choose whether or not you are using a dis-
charge air sensor function. To monitor only,
select NO. See setup instructions for dip-
switch settings which must also be set.
Discharge Air Low Limit Screen. Enter
a discharge air low limit value. This
screen will not appear if the discharge air
sensor function is disabled.
Discharge Air High Limit Screen. Enter
a discharge air high limit value. This
screen will not appear if the discharge air
sensor function is disabled.
Modulating Output 1 Control Screen.
Choose whether to control based on
DISCHARGE air reset or SPACE tem-
perature.
Modulating Output 2 Control Screen.
Choose whether to control based on
DISCHARGE air reset or SPACE tem-
perature.
Modulating Output Enable Heating
Low Limit Screen. Choose whether to
enable Heating Low Limit.
Modulating Output 1 Discharge Air
Setpoint Screen. Enter a value at which
the discharge air setpoint is to be con-
trolled for heating.
Modulating Output 2 Discharge Air
Setpoint Screen. Enter a value at which
the discharge air setpoint is to be con-
trolled for cooling.
Modulating Output 1 Reset Ratio
Factor Screen. Enter a reset ratio factor.
This is the number of degrees that the
discharge air setpoint is raised when the
space temperature falls by 1 degree.
Modulating Output 2 Reset Ratio
Factor Screen. Enter a reset ratio factor.
This is the number of degrees that the
discharge air setpoint is lowered when
the space temperature rises by 1 degree.
Outdoor Air Sensor Function Screen.
Choose whether or not you are using an
outdoor air sensor function. To monitor
only, select NO. See setup instructions
for dipswitch settings which must also
be set.
Cooling Lockout Screen. Enter an
outdoor air cooling lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled.
Heating Lockout Screen. Enter an
outdoor air heating lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled.
SZ1053 Programming Sequences
program
setup
MOD OUT 2
RANGE: 4-20 MA
30d.
program
setup
MOD OUT 1 UNOCC
ACTION: MOD
31d.
program
setup
MOD OUT
RANGE: 4-20 MA
29d.
program
setup
MO 1 PROPORTIONAL
BAND: 04F
23d.
program
setup
MOD OUT 2
ACTION: DIRECT
28d.
program
setup
MO 2 PROPORTIONAL
BAND: 04F
24d.
program
setup
MO 2 SETPOINT
OFFSET: 00F
26d.
program
setup
MOD OUT 1
ACTION: DIRECT
27d.
program
setup
MO 1 SETPOINT
OFFSET: 00F
25d.
program
setup
MOD OUT 2 UNOCC
ACTION: MOD
32d.
program
setup
ENABLE DISCHARGE
AIR FUNCT.? YES
33d.
program
setup
MO 1 RESET RATIO
FACTOR: 2.0F
41d.
program
setup
MO 2 RESET RATIO
FACTOR: 2.0F
42d.
program
setup
MO 2 DISCHARGE
SETPOINT: 60F
40d.
program
setup
DISCHARGE AIR
LOW LIMIT: 045F
34d.
program
setup
MO 1 DISCHARGE
SETPOINT: 90F
39d.
program
setup
DISCHARGE AIR
HIGH LIMIT: 125F
35d.
program
setup
MOD OUT 2 BASED
ON: SPACE
37d.
program
setup
ENABLE HEATING
LOW LIMIT? NO
38d.
program
setup
MOD OUT 1 BASED
ON: SPACE
36d.
program
setup
ENABLE OUTDOOR
AIR FUNCT.? YES
43d.
program
setup
COOLING LOCKOUT
TEMP: 60F
44d.
program
setup
HEATING LOCKOUT
TEMP: 70F
45d.
Go to #46 p.6