Features (Continued):
Capacitor Bank Values: Normalized for rated supply voltage and
frequency and monitored on line.
All Capacitor Bank Status.
Temperature of the TPF-56 Unit.
Battery Voltage for RTCC / NV-RAM Battery.
•Data Mobilizer –In future, we will add Hand Held Unit (HHU-01) as a separate
unit, that can be procured separately for transfer of data from remote site
located TPF-56 Unit that can be further uploaded to PC having “Data View”
software. Such Unit even have added facilities like fixed set parameter
uploading (5 pre-programmed sets of Parameters to be programmed in TPF-
56).
•Manual Mode (Testing) facility available for convenience of checking the Turn-
On and Turn-Off of capacitor banks. This feature is additionally useful for
Manual Synchronization and for resetting the “faulty” declared capacitor banks.
•GSM (global system for mobile) :
Enabling GSM send SMS about various parameter :
3-phase Voltages (Line –Neutral Values)
3-phase Currents and Neutral Current.
Bank status .
Fault.
•RS485 communication :
There are two basic transmission modes found in serial MOD-BUS
connections, ASCII and RTU. These transmission modes determine the
way in which the MOD-BUS messages are coded.
One of the main differences between MOD-BUS/ ASCII and MOD-BUS RTU
is that ASCII allows gaps between the bytes of a message with a
maximum length of 1 second. With MOD-BUS RTU, continuous streams of
messages must be sent. Enabling Modbus ASCII or RTU gives values:
3-phase Voltages (Line –Neutral Values)
3-phase Currents and Neutral Current.
Individual Phase PF, Active Power, Reactive Power, Apparent Power values.
AC Mains Supply Line frequency.
Overall Values: Average Voltage & Current, Total Active Power, Total
Reactive Power, Total Apparent Power.
Energy Values: Active Energy Consumed, Reactive Energy Inductive
(uncompensated), Reactive Energy Capacitive (uncompensated),
Apparent Energy.
Harmonics: Per Phase V-THD-F% and I-THD-F% values.
Capacitor Bank Values: Normalized for rated supply voltage and
frequency and monitored on line.
Temperature of the Unit.
Intelligent Power Factor Controller TPF-56
7 of 56 Version 1.1.5 22nd March, 2016