SteamOvap SB Manual de usuario

SPACE BLOWER FOR STEAM HUMIDIFIER
Installation and Operation Manual
Please read and save this manual
steamOvap technologies inc, 9495 Charles de la Tour, Montreal, Qc, H4N 1M5, Canada
Tel.: 1-844-357-4477 • www.steamOvap.com
Rev.190201
SB

2
Introduction
Foreword
Thank you for purchasing IER steamOvap electric steam Humidifier.
If you have questions or comments please contact us:
www.steamOvap.com
info@steamOvap.com
1-844-357-4477
Intended use
SB space blower for steam humidifier is intended exclusively to distribute steam
produced by a steam humidifier for direct in-space air humidification.
Operating conditions are specified in this Installation and Operation Manual (IOM).
Operation of this Space blower in the intended use scope requires that all directions
and information contained in this IOM are observed.
Any other use or operation outside the above design scope without written
authorization from steamOvap may lead to trouble and hazardous conditions and
will void warranty.
No alteration or modification to the Space blower must be done without written
authorization from steamOvap.
Replacement of any defective components must be done with original component
and spare parts from steamOvap representative.
Installation and Operation Manual Limitation
This IOM is intended for trained and qualified personnel and must be applied along
with the applicable local codes and regulations.
Any work related to installation or service for this humidifier must comply with local
code and regulation regarding safety and prevention of accidents.
End of life disposition
Disconnect Space blower from power supply, electrical control signal, Steam line,
and condensate line. Space blower can then be removed from the wall or from
steam humidifier.
Space blower is an electrical equipment and as such MUST not be disposed of in
domestic waste.
This Space blower should be returned to the closest steamOvap authorized
representative for proper dismantling, recycling and disposition of components
according to local regulations.

3
Table of content
Introduction ........................................................................................ 2
Table of content ................................................................................. 3
Safety warnings .................................................................................. 4
Before to proceed to Installation ......................................................... 5
Space blower Overview ...................................................................... 6
Installation overview ........................................................................... 8
Installation – step 1 IER Positioning & Mounting ................................ 8
Installation – step 4 Steam line installation ....................................... 11
Installation – step 5 Power supply installation .................................. 12
Installation – step 6 Control installation ............................................ 13
Verification before start-up ............................................................... 14
Start-up & normal operation ............................................................. 15
Maintenance & service ..................................................................... 15
Warranty .......................................................................................... 16

S A F E T Y
4
Safety warnings
General
Risk of electric shock.
Disconnect power supply before installation or service.
For safety and warranty reasons, Installation and service of this humidifier should be carried
out by trained and qualified personnel.
Any work related to installation and service of this humidifier must comply with local code and
regulation regarding safety and prevention of accidents.
Electrical Warning
Risk of electric shock.
Disconnect power supply before installation or service.
Power supply connexion must be done by a trained and qualified electrician.
Any work related to power supply installation or service of this humidifier must comply with
local code and regulation regarding safety and prevention of accidents.
Steam safety warning
Any work related to steam line and condensate returns lines installation or service of
such for this space blower for humidifier must comply with local code and regulation
regarding safety and prevention of accidents.
Risk of malfunction. Steam lines should not have any restriction or blockage that may cause a
burst of pressure in the steam line.
Risk of malfunction. Do not block steam outlet(s).
section
0

I N T E N D E D U S E
5
Before to proceed to Installation
Please read this Installation and Operation manual before to proceed to the Installation
Receiving & Unpacking
1. Upon receipt verify that packaging is complete and not damaged.
In case of damage, and/or missing boxes advise immediately the carrier by writing a note
on the waybill.
2. Verify that model of the space blower matches the purchase order and that all
accessories are included.
3. Any missing item should be reported as soon as possible to steamOvap or its
representative and within 5 business days after receipt.
steamOvap will not assume any responsibility for missing item after this delay.
4. Proceed carefully to unpacking, and check that the humidifier and its accessories are not
damaged. in case of damage please proceed as for point 3
Included in standard delivery of Space blower
1. This IOM
For Remote model:
2. Collar(s) to secure steam hose
3. 3 feet long condensate line & collars
section
1

O V E R V I E W
6
Space blower Overview
Space blower
Built-in Remote
Figure 1 – SB Built-in Overview
Figure 2 – SB Remote Overview
Model designation and options codification
Type & Model
S=Small
M=Medium
Nominal Voltage
SB S 120
section
2

O V E R V I E W
7
SB ratings
Model Steam
Capacity Airflow Power Voltage Current
Remote Built-in
SBS 26lb/h
[12kg/h]
220CFM
[375m3/h] 34W 120Vac Same as
IER
0.3A @
120Vac
SBM 65lb/h
[29.5kg/h]
330CFM
[560m3/h] 60W 120Vac Same as
IER
0.6A @
120Vac
SBL 96lb/h
[44kg/h]
330CFM
[560m3/h] 60W 120Vac Same as
IER
0.6A @
120Vac
IER Dimensions
Built-in Remote
Figure 3 – Built-in SB dimensions
Figure 4 – Remote SB dimensions
Model Dimensions
Steam
Inlet Ø Net weight
W
H
H1
D
SBS
Built-in
20in
[510m
m]
23in
[585mm]
8.5in
[216mm]
13in
[330mm] 1.5in
[DN40]
8lb
[3.6kg]
SBS
Remote
9.25in
[235m
m]
7in
[178mm] / 9in
[229mm]
SBM / SBL
Built-in
23.5in
[590m
m]
38in
[965mm]
10.5in
[267mm]
17.5in
[445mm] 2in
[DN50]
10lb
[4.5kg]
SBM / SBL
Remote
11.25in
[292m
m]
9in
[229mm] / 12in
[305mm]

I N T E N D E D U S E
8
Installation overview
General
1. Installation of this space blower should be carried out by trained and qualified
personnel.
2. Any work related to installation of this space blower must comply with local code and
regulation regarding safety and prevention of accidents.
WARNING. Risk of electric shock.
Power supply must be disconnected during installation.
Main power should be connected only after all installation steps have been completed and
properly verified.
Installation steps :
1. Positioning & mounting of Space blower/humidifier
2. If Remotely installed from humidifier
a. Steam line installation
b. Condensate line installation
c. Power supply installation
d. Control signal installation
Installation – step 1
IER Positioning & Mounting
General guidelines for positioning
Space blower should be positioned so that:
Length of the steam line (or hose) is as short as possible,
In case steam hose is used, the bend radius of 12in (300mm) is ensured
Space blower is easily accessible for service
CAUTION: Risk of water damage. Ensure that the surrounding area below and
around the space blower will not be damaged by any possible water projection.
CAUTION: Do not install Space blower above any electrical equipment, as water leak
from connection or abnormal operation can cause malfunction or short circuit.
IER maximum ambient conditions:
Temperature: 41°F to 122°F [+5 to +50°C]
Relative Humidity: 90%RH max (non condensing)
Ingress Protection for SB space blower standard enclosure: IP20
section
3

I N S T A L L A T I O N
9
Clearances for Space blower
Figure 5 – minimum clearances for SB
Clearance guidelines
There is no minimum clearance on both side of the Space blower, but it is a good practice to
have a clearance of 4 to 8 in [100 to 200mm] for ease of installation and service
Front clearance of 80in [2000mm] is required for steam absorption.
A top clearance is required of 24in [600mm] for access and for steam absorption to avoid any
condensing on the ceiling.

I N S T A L L A T I O N
10
General guidelines for Mounting
CAUTION. Risk of malfunction. Space blower must be levelled in X & Z axis.
CAUTION: Do not install Space blower above any electrical equipment, as water leak
from connection or abnormal operation can cause malfunction or short circuit.
Built-in SB
There are no specific installation steps for the mounting of the built-in space blower since it is
directly attached on the top of the IER steam humidifier.
Follow same installation steps for mounting as the one included in the IER electric steam
humidifier IOM.
Remote SB
Figure 6 – SB mounting holes location
Model A
SBS
SBM
SBL
6.5in
[165mm]
Wall installation
1. Verify that wall structure and strength is appropriate to support the operating weight of
the Space blower.
2. Mark the wall or support according to the above holes location, and drill 2 holes to the
wall or support as per the size of anchors and/or screws.
3. Use anchors of sufficient size (at least 1/4in [6mm]). Insert those anchors and the 2
screws, ensure that the screw heads extends 1/4in [6mm] from the wall, so that the
Space box will be able to be hung on those 2 screws.
4. With Top cover removed, hung the Space blower onto the 2 screws.
Ensure that the Space blower is properly levelled.
Tighten the 2 screws. Re verify the level in the 2 direction X and Z axis.
5. Re-install the top cover to the Space blower.
Ensure that the mounting bracket is properly levelled.
1. With front cover removed, hung the IER electric steam humidifier onto the mounting
bracket.
2. Insert the bottom screw through the back plate of the humidifier and into the anchors
in the wall.
Tighten the bottom screw. Re verify the level in the 2 direction X and Z axis.