Parameters for the protection of the compressor
Para-
meter Function Adjustment range Standard
setting Customer
setting
c0 Start protection of the
compressor after "cooling on" 0...15 min.
0 min.
c1 Start protection after
compressor start 0...15 min. 5 min.
c2 Start protection after
compressor stop 0...15 min. 3 min.
c3 Function in the case of error of
sensor F1 0: compressor off
1: compressor on
2: compressor according c5
0
c4 Switching delay compressor
relay 0: no delay
1: 3 sec. delay 0
c5 Time for “compressor on” at
sensor error 1 ... 99 min. 15 min.
Parameters for defrosting
Para-
meter Function Adjustment range Standard
setting Customer
setting
d0 Defrosting interval 0...99 Std.
0 = inactive 8
d1 Defrosting mode 0: electrical
1: with hot gas 0
d2 Defrosting temperature -55...+99°C 10°C
d3 Defrosting time limit 1...99 min. 30 min.
d4 Function after "cooling on" 0: immediate cooling, no defrost
1: first defrosting, then cooling 0
d5 Defrost delay after
“cooling on” 0...30 min. 0 min.
d6 Indication of the cold room
temperature during
defrosting
0: actual temperature
1: temperature determined just
before the start of defrosting
0
d7 Drainage time 0...15 min
0: no drainage 2 min.
d8 Alarm suppression time
after defrosting 0...15 h
1 h
d9 Execution of defrost
demand 0: dependent execution
1: immediate execution
2: temperature decrease before
defrosting
1
db Time base defrost cycle 0: standard time basis
1: reduced time basis 0
dC Temperature decrease
before defrosting -20...0 K
0
dF Time limitation for
temperature decrease 0...999 Min
60
dH Waiting after defrost 0: not activated
1: activated 0
dU Manual defrosting 0: no defrost
1: manual start 0