SPACING BETWEEN DETECTORS (OPEN AREA LOCATIONS)
The Models S250/S260 series detectors are intended for installation on 30 foot centers
maximum, based on a smooth ceilings up to 15 feet high with minimum air circulation.
This results in a maximum coverage area of 900 square feet. This figure may be used as
a reasonable guide for comparable applications. Where special conditions exist (ceiling
obstructions, high air exchange rates, etc.), reduced square footage spacing must be
used to achieve adequate protection. Computer rooms and other such installations may
require spacing with a maximum of 200 square feet due to high air exchange rates. For
additional information, consult National Fire Protection Association Standard 72.
INSTALLING AND WIRING THE DETECTOR BASES
The Detector Bases are
designed to mount directly on a
standard electrical junction
boxes (3, 3 1/2, or 4 inch round,
square or octagonal). Two sets
of mounting slots on the base
permit installing on the various
size boxes. Applicable dimen-
sions are shown in Figure 250-
2.
Refer to the typical wiring
diagram, SST drawing
50002,which shows the proper
2-wire smoke detector wiring
methods when using the
various mounting bases.
Make connections to the screw terminals or colored wires on the base per the wiring
diagram. Be sure to connect two individual wires to terminal number 1 as shown in
Figure 250-3. Do not leave these twowires uncut and looped around the screw. This
is to insure that a fault will be signaled if the screw terminal becomes loose and either
wire becomes disconnected.
Dress allwiresaway fromtheconnector terminals
on the base that will mate with the detector, then
mount the base on the junction box.
After alldetectorbasesareinstalled,includingthe
end-of-line resistor, check loop continuity. To
make the continuity check, a preformed spring
jumper wire is supplied with each base, installed
between terminals 6 and 7. With the jumper in
place on each base, measure the resistance be-
tween the two wires at the control panel. (Unplug
the input module if the wires are already ter-
minated on the control panel. You should read
3300 ohms, the end-of-line resistor. After loop Figure 250-3 Wiring Methods
Figure 250-2 Mounting Base Dimensions
SPACING BETWEEN DETECTORS (OPEN AREA LOCATIONS) MODELS S250 AND S260 SMOKE DETECTORS
DESIGN MANUAL December, 2002 250-5