Page 2 – Bulletin 100-50-6.1
3 SETTINGS
3.1 Setting the working setpoint
•makesurenoprocedureisrunning
•press : LED will ash
•press or within15seconds;alsolookatparametersr1,r2andr3
•press ordonotpressanykeyfor15seconds.
YoualsocanmodifytheworkingsetpointthroughparameterSP.
3.2 Setting conguration parameters
To gain access to the procedure:
•makesurenoprocedureisrunning
•pressandhold and for4seconds:thedisplaywillshow“PA”
•press
•press or within15secondstosetdisplayto“-19”
•press ordonotpressanykeyfor15seconds
•pressandhold and for4seconds:thedisplaywillshow“SP”.
To select a parameter:
•press or
To modify a parameter:
•press
•press or within15seconds
•press ordonotpressanykeyfor15seconds.
Toquittheprocedure:
•pressandhold and for4secondsordonotpressanykeyfor
60seconds.
Switch off/on the power supply of the controller after the
modification of the parameters.
3.3 Restoring the default value of conguration parameters
•makesurenoprocedureisrunning
•pressandhold and for4seconds:thedisplaywillshow“PA”
•press
•press or within15secondstosetthedisplayto“743”
•press ordonotpressanykeyfor15seconds
•pressandhold and for4seconds:thedisplaywillshow“dEF”
•press
•press or within15secondstosetthedisplayto“149”
•press ordonotpressanykeyfor15seconds:thedisplaywill
show “dEF”ashing4seconds,afterwhichthecontrollerwillquit
the procedure
•switcho/onpowertothecontroller.
Make sure the default value of the parameters is correct, in
particular note if the probes are PTC probes.
4 SIGNALS
4.1 Signals
LED EXPLANATION
LED compressor
iflit,thecompressorwillbeturnedon
if ashing:
•themodiedworkingsetpointwillberunning
•acompressorprotectionwillberunning(parametersC0
andC2;thecompressordelaysincetheendofthecabinet
probeerroris2minutes)
LED defrost
iflit,thedefrostwillberunning
LED alarm
iflit,analarmwillberunning
°C °CLED
iflit,temperaturemeasurementswillbeindegrees
Celsius(parameterP2)
°F °F LED
iflit,temperaturemeasurementswillbeindegrees
Fahrenheit(parameterP2)
5 INTERNAL DIAGNOSTICS
5.1 Internal diagnostics
CODE EXPLANATION
Pr1 Cabinetprobeerror
Solution:
•lookatparameterP0
•checktheintegrityoftheprobe
•checktheconnectionbetweencontrollerandprobe
•checkthecabinettemperature
Eects:
•thecompressorwillbeturnedon
Whentheconditionsthattriggeredthealarmarenolongerpresent,the
controller will return to normal operation.
6 TECHNICAL DATA
6.1 Technical data
Frontal bezel protection:IP65.
Connections (use copper conductors only): screw terminal blocks
(powersupply,inputandoutput).
Working temperature:from0to55°C(32to131°F),10to90%
relativehumidity(withoutcondensation).
Power supply:115VAC/230VAC,50/60Hz,3VA(approximate).
Insulation class:2.
Measure inputs:1(cabinetprobe)forPTC/NTCprobes.
Working range:from-50.0to150.0°C(-50to300°F)forPTCprobe,
from-40.0to105.0°C(-40to220°F)forNTCprobe.
Resolution:0.1°C/1°C/1°F.
Digital outputs:1relay:
•compressorrelay:16res.A@250VAC(change-
overcontact);5FLA,30LRA.
The maximum current allowed on the load is 10 A.