Sw1 - Equipment Type Switch 1 sets the equipment type.
For heat / cool equipment, set the switch to the OFF position
(factory default).
For heat pump equipment, set the switch to the ON position.
Sw2 - Equipment Stages Switch 2 sets the equipment stages.
For single stage equipment, set the switch to the OFF position
(factory default). For multi-stage equipment, set the switch to the
ON position.
SYSTEM SWITCH FUNCTIONS
Sw3 - Heat Pump Type Switch 3 is used to select conventional heat pump or dual fuel
operation.
For conventional heat pump, set the switch to the OFF position
(factory default).
For dual fuel operation, set the switch to the ON position.
Sw4 - Reversing Valve Switch 4 is used to select the heat pump reversing valve. For ‘O’
reversing valve (energize in cooling), set the switch to the OFF
position (factory default).
For ‘B’ reversing valve (energize in heating), set the switch to the
ON position.
Sw5 - Fan Switch 5 is used to configure the fan operation. For gas systems,
set the switch to OFF (factory default).
For heat pump and electric systems, set the switch to ON position.
Sw6 - Thermostat Mode Switch 6 is used to set the thermostat mode.
For non-programmable, set the switch to the OFF position
(factory default).
For programmable, set the switch to the ON position.
Sw7 - Schedules OFF = 4 schedules per day (factory default).
ON = 2 schedules per day.
Sw8 - Compressor Delay OFF = 4 minute short cycle protection (factory default).
ON = Disabled.
FACTORY DEFAULT SETTINGS
SWITCH ON/OFF FUNCTION
1 - Equipment Type OFF Heat / Cool
2 - Equipment tages OFF Single Stage
3 - Heat Pump Type OFF Conventional Heat Pump
4 - Reversing Valve OFF ‘O’ Reversing Valve
5 - Fan OFF Equipment Controls Fan
6 - Thermostat Mode OFF Non-programmable
7 - Schedules OFF 4 Schedules per Day
8 - Compressor Delay OFF 4 Minute Short Cycle Protection Enabled