3
Temperature Sensing Operaon
Temperature and Humidity Monitoring - The temperature sensor will
record the temperature, temperature set point and humidity values*
every 10 seconds (sample period) when there is approximately 100 lux
(10 foot-candles) available. If there is less than 100 lux (10 fc), the sam-
ple period will increase to 100 seconds. Aer 24 hours at < 15 lux (1.5
fc) the sample period will increase to 200 seconds. *Assuming sucient
storage charge to operate.
Temperature Set Point - Users can adjust the temperature set point by
rotang the knob counterclockwise to lower the set point value; clock-
wise to increase the set point value.
The receiving temperature control equipment must scale the set point
range to values that are applicable for the applicaon.
Fan Speed Switch - Users can adjust the fan speed switch by sliding the
switch to a seng: Auto, OFF, Low (1) Med (2), High (3).
Occupancy Buon - (RTS-2HS models only) Users can override a room
occupancy state by pressing the occupancy buon on the lower right
edge of the sensor.
LED Operaon - LEDs are on the right side of the solar panel. The red
LED will ash when the Link or Occupancy buon is pressed. See Test
Operang Modes for further LED informaon.
Transming Values - The temperature sensor will transmit a telegram
when:
• 10 sample periods have been completed or
• when the fan switch or occupancy buon are used or
• when the temperature value dierence from the last transmied
value is greater than 0.3°C, (0.5°F) or
• the humidity value dierence from the last transmied value is
greater than 3%.
Installing the Temperature Sensor
The temperature sensor can be mounted on any surface; glass, stone,
concrete, wallboard, cubicle parons, etc. The sensor can be mounted
using screws (not supplied) through the removable back plate (2 key-
holes or using double sided tape or Velcro™ (not supplied).
The mounng locaon of the wireless transmier is important as this
will directly aect the receivers recepon of the telegrams. Before