Sorel AIR TDC Manual de usuario

Read carefully before installation, commissioning and operation
Temperature Difference Controller AIR TDC
Installation and operating instructions

Content
A. Safety instruction 3
A.1. EC declaration of conformity 3
A.2. General instructions 3
A.3. Explanation of symbols 3
A.4. Changes to the unit 4
A.5. Warranty and liability 4
B. Specications 5
B.1. Specications 5
B.2. About the controller 6
B.3. Scope of supply 6
B.4. Disposal and pollutants 6
B.5. Hydraulic variants 7
C. Installation 8
C.1. Wall installation 8
C.2. Electrical connection 9
C.3. Installing the temperature sensors 10
D. - Terminal connection diagram 11
E. Operation 12
E.1. Display and input 12
E.2. Commissioning help 13
E.3. Free commissioning 13
E.4. Menu sequence and menu structure 14
1. Measurementvalues 15
2. Statistics 16
2.1. Operating Hours 16
2.2. Average Temperature Difference ∆T 16
2.4. Graphic Overview 16
2.5. Message Log 16
2.6. Reset / Clear 16
3. Display mode 17
3.1. Schematic 17
3.2. Overview 17
3.3. Alternating 17
4. Operating modes 18
4.1. Automatic 18
4.2. Manual 18
4.3. Off 18
5. Settings 19
5.1. Tmin Collector 19
5.2. Tset Room 19
5.3. Collector / Room 19
5.4. Tset Room 20
5.8. Collector / Room 20
5.20. Ventilator Flap 20
5.21. Min Outdoor Temperature 20
5.23. Tmax Outdoor 20
6. Protective functions 21
6.1. Seizing Protection 21
6.2. Fan Protection 21
6.3. Night Cooling 21
7. Special functions 22
7.2. Signal V1 22
7.2.1. Type of ventilator 22
7.2.2. Ventilator 22
7.2.3. Output Signal 22
7.2.4. 0-10V off / PWM off 22
7.2.5. 0-10V on / PWM on 22
7.2.6. 0-10V Max / PWM Max 22
7.2.7. Show signal 22
7.3. Speed control V1 23
7.3.1. Speed control Modes 23
7.3.2. Purging time 23
7.3.3. Sweep time 23
7.3.4. max. speed 24
7.3.5. min. speed 24
7.4. Time & Date 24
7.5. Sensor calibration 24
7.6. Commissioning 24
7.7. Factory settings 25
7.8. Heat quantity 25
8. Menulock 25
9. Servicevalues 26
10. Language 27
Z. Malfunctions 27
Z.1. Malfunctions with error messages 27
Z.2. Replacing the fuse 28
Z.3. Maintenance 28

3
Safety instructions
By af xing the CE mark to the unit the manufacturer declares that the Temperature-
Difference-Controller AIR TDC, conforms to the following relevant safety regulations:
- EC low voltage directive 2006/95/EC
- EC electromagnetic compatibility directive 2004/108/EC
Conformity has been veri ed and the corresponding documentation and the EC declaration
of conformity are kept on le by the manufacturer.
A.1. EC declaration of conformity
These installation and operating instructions contain basic instructions and important
information regarding safety, installation, commissioning, maintenance and the optimal
use of the unit. Therefore these instructions must be read completely and understood
by the installation technician/specialist and by the system user before installation, com-
missioning and operation of the unit.
The valid accident prevention regulations, VDE regulations, the regulations of the lo-
cal power utility, the applicable DIN-EN standards and the installation and operating
instruction of the additional system components must also be observed. The controller
does not under any circumstances replace any safety devices to be provided by the
customer!
Installation, electrical connection, commissioning and maintenance of the unit may
only be carried out by specialists who possess the appropriate training.
For the user: Make sure that the specialist gives you detailed information on the func-
tion and operation of the controller. Always keep these instructions in the vicinity of the
controller.
A.2. General instructions
Danger
Caution
A.3. Explanation of symbols
Failure to observe these instructions can result in danger to life from
electric voltage.
Danger
Failure to observe these instructions can result in serious damage to
health such as scalding, or even life-threatening injuries.
Caution
Failure to observe these instructions can result in destruction of the unit
or the system, or damage to the environment.
Information which is especially important for the function and optimal
use of the unit and the system.
It is essential that you read this!

4
Safety instructions
A.4. Changes to the unit
The controller has been manufactured and tested with regard to high quality and
safety requirements. The unit is subject to the statutory guarantee period of two years
from the date of sale.
The warranty and liability shall not include, however, any injury to persons or material
damage that is attributable to one or more of the following causes:
• Failure to observe these installation and operating instructions
• Improper installation, commissioning, maintenance and operation
• Improperly executed repairs
• Unauthorised structural changes to the unit
• Installation of additional components that have not been tested
together with the unit
• Any damage resulting from continued use of the unit despite an
obvious defect
• Failure to use original spare parts and accessories
• Use of the device for other than its intended purpose
• Operation above or below the limit values listed in the speci cations
• Force majeure
A.5. Warrantyandliability
• Changes, additions to or conversion of the unit are not permitted without the writ-
ten permission from the manufacturer
• It is likewise forbidden to install additional components that have not been tested
together with the unit
• If it becomes clear that safe operation of the unit is no longer possible, for example
because of damage to the housing, then turn the controller off immediately
• Any parts of the unit or accessories that are not in perfect condition must be ex-
changed immediately
• Use only original spare parts and accessories from the manufacturer.
• Markings made on the unit at the factory must not be altered, removed or made
illegible
• Only the settings actually described in these instructions may be made on the
controller
Changes to the unit can compromise the safety and function of the unit
or the entire system.
Danger
1.1. - Temperature resistance table for Pt1000 sensors

5
B.1. Specications
°C 0 10 20 30 40 50 60 70 80 90 100
Ω1000 1039 1077 1116 1155 1194 1232 1270 1308 1347 1385
Description of controller
Electricalspecications:
Mains voltage 230VAC +/- 10 %
Mains frequency 50 - 60 Hz
Power consumption 1,5 W - 2,3 W
Internal fuse T2A / 250V slow blow
Protection category IP40
Protection class II
Overvoltage Category II
Degree of Pollution Category II
mechanical relay 460VA for AC1 / 460W for AC3 2 (R1 - R2)
0-10V output, tolerance 10 %, 10 k Ω load or
PWM output freq. 1 kHz, level 10 V 1
PT1000 sensor input measuring range -40 °C to 300 °C 3
Permissiblecablelengthofsensorsandappliances:
Collector and outdoor sensor < 30 m
other PT1000 sensors < 10 m
PWM / 0...10V < 3 m
mechanichal relay < 10 m
Real Time Clock RTC with 24 hour power reserve
Permissibleambientconditions:
Ambient temperature
for controller operation 0 °C ... 40 °C
for transport/storage 0 °C ... 60 °C
Air humidity
for controller operation max. 85 % rel. humidity at 25 °C
for transport/storage no moisture condensation permitted
Otherspecicationsanddimensions
Housing design 2-part, ABS plastic
Installation methods Wall installation, optionally panel installation
Overall dimensions 163 mm x 110 mm x 52 mm
Aperture installation dimensions 157 mm x 106 mm x 31 mm
Display Fully graphical display, 128 x 128 dots
Light diode Multicolor red/green
Operation 4 entry keys
B.2. Temperature resistance table for Pt1000 sensors

6
The Temperature Difference Controller AIR TDC facilitates ef cient use and function
control of your solar or heating system. The device is impressive most of all for its
functionality and simple, almost self-explanatory operation. For each step in the input
process the individual entry keys are assigned to appropriate functions and explained.
The controller menu contains headwords for the measured values and settings, as well
as help texts or clearly-structured graphics.
The AIR TDC can be used as a temperature difference controller for the various sys-
tem variants illustrated and explained under B.5.
Important characteristics of the AIR TDC:
• Depiction of graphics and texts in a lighted display
• Simple viewing of the current measurement values
• Analysis and monitoring of the system by means of statistical graphics,etc.
• Extensive setting menus with explanations
• Menu block can be activated to prevent unintentional setting changes
• Resetting to factory settings
• A wide range of additional functions are available.
B.3. About the controller
Description of controller
• Temperature Difference Controller AIR TDC
• 3 screws 3,5 x 35 mm and 3 plugs 6mm for wall installation
• 6 strain relief clips with 12 screws, replacement fuse 2A slow-blow
• Installation and operating instructions AIR TDC
Optionally contained depending on design/order:
• 2-3 PT1000 temperature sensors and immersion sleeves
Additionally available:
• Pt1000 temperature sensor, immersion sleeves, overvoltage protection,
• Various additional functions by means of supplementary circuit boards
B.4. Scope of supply
B.5. Disposalandpollutants
The unit conforms to the European RoHS directive 2011/65/EU for the restriction of the
use of certain hazardous substances in electrical and electronic equipment.
Caution
The unit must not under any circumstances be disposed of with ordinary
household refuse. Dispose of the unit only at appropriate collection
points or ship it back to the seller or manufacturer.

7
Description of controller
B.6. Hydraulic variants
Caution
The following illustrations should be viewed only as schematic diagrams
showing the respective hydraulic systems, and do not claim to be complete.
The controller does not replace safety devices under any circumstances.
Depending on the speci c application, additional system components and
safety components may be mandatory, such as check valves, non-return
valves, safety temperature limiters, scalding protectors, etc., and must
therefore be provided.
20°C 20°C
Aircollector Aircollector with vebtilation ap

8
C.1.1
C.1.2
Caution
C.1. Wallinstallation
Install the controller only in dry areas and under the ambient conditions de-
scribed under B.1 “Speci cations”. Carry out the following steps 1-8.
1. Unscrew cover screw completely
2. Carefully pull upper part of housing
from lower part.
3. Set upper part of housing aside, being
sure not to touch the electronics when
doing so.
4. Hold the lower part of the housing up
to the selected position and mark the 3
mounting holes. Make sure that the wall
surface is as even as possible so that the
housing does not become distorted when
it is screwed on.
5. Using a drill and size 6 bit, drill 3 holes
at the points marked on the wall and push
in the plugs.
6. Insert the upper screw and screw it in
slightly.
7. Fit the upper part of the housing and
insert the other two screws.
8. Align the housing and tighten the three
screws.
Installation

9
Installation
C.2. Electrical connection
Danger
Before working on the unit, switch off the power supply and secure it
against being switched on again! Check for the absence of power!
Electrical connections may only be made by a specialist and in compli-
ance with the applicable regulations.
Do not use the controller if the housing shows visible damage.
Caution
Low-voltage cables such as temperature sensor cables must be routed
separately from mains voltage cables. Feed temperature sensor cables
only into the left-hand side of the unit, and mains voltage cables only
into the right-hand side.
Caution
The customer must provide an all-pole disconnecting device, e.g. a
heating emergency switch.
Caution
The cables being connected to the unit must not be stripped by more
than 55mm, and the cable jacket must reach into the housing just to the
other side of the strain relief.
With hydraulic variant D1 - D8 relays R1 and R2 are switched on
simultaneously to allow the connection of another load at R2.
If in D1 speed control is active, R2 is switched on during purging time.
Caution

10
1.Select necessary program/hydraulics
(Fig. B5)
2.Open controller as described under C.1.
3.Strip cables by 55 mm max., insert, t
the strain relief devices, strip the last
8 - 9mm of the wires (Fig. C.2.1)
4.Open the terminals using a suitable
screwdriver (Fig. C.2.1) and make electri-
cal connections on the controller (s. D.1
- D.20)
5.Re t upper part of housing and fasten
with screw.
6.Switch on mains voltage and place con-
troller in operation.
C.2.1
Installation
C.3. Installing the temperature sensors
The temperature sensor cables must be routed separately from mains voltage
cables, and must not, for example, be routed in the same cable duct!
The controller operates with Pt1000 temperature sensors which are accurate to the
degree, thus ensuring optimal control of system functions.
If desired the sensor cables can be extended to a maximum of 30 m using
a cable with a cross-section of at least 0.75 mm². Make sure that there is no
contact resistance!
Position the sensor precisely in the area to be measured!
Only use immersion, pipe-mounted or at-mounted sensor suitable for the spe-
ci c area of application with the appropriate permissible temperature range.
Caution
Caution
Este manual sirve para los siguientes modelos
6
Tabla de contenidos
Otros manuales de Controladores de temperatura de Sorel

Sorel
Sorel TDC 3 Manual de usuario

Sorel
Sorel STDC Manual de usuario

Sorel
Sorel TDC 1 Manual de usuario

Sorel
Sorel TDC 3 Manual de usuario

Sorel
Sorel STDC V1 Manual de usuario

Sorel
Sorel STDC1 Manual de usuario

Sorel
Sorel MTDC Manual de usuario

Sorel
Sorel TDC 2 Manual de usuario

Sorel
Sorel TC Manual de usuario

Sorel
Sorel TDC 5A Manual de usuario