Smart Communication Room Controllers User Manual
Issue Number 7.0
11/05/2022
Analog Output 1 (AO1) (continued)
20. "AO1 Off Voltage"
Default: MIN (Minimum voltage)
Range: MIN (Minimum voltage), OFF (0 Volt)
MIN (Minimum voltage), OFF (0 Volt)
This option does not appear if the signal ramp for AO1 is set to OFF (Step 17, "AO1 Ramp"). Set the analog output voltage when the controller
is turned off. When set to MIN, the output will remain at the minimum voltage level defined by Step 18, "AO1 Minimum Voltage". When set to
OFF, the output will remain at 0V.
21. "AO1 Dirrev"
Default: dir (Direct)
Range: dir (Direct), rEV (Reverse)
This option does not appear if the signal ramp for AO1 is set to OFF (Step 17, "AO1 Ramp"). Set the direction of the analog signal to either
Direct (e.g. 0 to 10Vdc), or Reverse (e.g. 10 to 0Vdc).
22. “AO1 Signal Type”
Default: ANLg (Analog Output)
Range: ANLg (Analog Output), OnOF (On/Off), PuLs (Pulsing)
This option does not appear if the signal ramp for AO1 is set to OFF (Step 17, "AO1 Ramp"). Set the signal type for AO1 to either Analog Out-
put, On/Off or Pulsing.
Analog Output 2 (AO2)
23. "AO2 Ramp"
Default: Hr1 (Heating Ramp 1)
Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6W, dto, VFdt, VFdP, FAN, OFF, COr
Select the desired signal from the available options. The AO1 input signal has priority over AO2.
• Cr1 (Cooling Ramp 1) or Cr2 (Cooling Ramp 2). The Cr1 and Cr2 ramps are used for cooling. If selected, the controller performs cool-
ing based on the cooling proportional, integral, and dead band values.
• Hr1, Hr2 (heat with fan), or Hr2 (heat without fan). The Hr1 and Hr2 ramps are used for heating. If selected, the controller performs
heating based on the heating proportional, integral, and dead band values.
• CH1 (Cooling and Heating). If selected, the controller performs cooling regularly. If another output is set to heat, it performs heating
regularly.
• HU (Humidify). If selected, the controller modulates the output based on the humidify demand.
• CO2 (Carbon dioxide). If selected, the controller will activate or deactivate the output based on carbon dioxide levels.
• 6W (6-way Valve). If selected, the controller will modulate the 6-way valve depending on the heating or cooling demand.
• dto (Delta temperature control). If selected, the controller will modulate the ΔT control based on the inlet and outlet temperature of the
water inside the fan coil unit.
• VFdt (VFD Temp Loop). If selected, the controller will modulate the VFD fan based on the selected temperature input.
• VFdP (VFD Pressure Loop). If selected, the controller will modulate the static pressure based on the reading and the pressure setpoint.
• FAN. The FAN option is available only if you selected OFF at Step 12, "Heat Pump Option". If selected, the controller modulates the
output based on the Fan demand.
• OFF. If selected, the controller does not use the output.
• COr (Changeover). If selected, the controller will modulate heating and cooling, as appropriate.
If you select OFF, Steps 24 to 28 will not be available.
If you select VFdt or VFdP, Steps 42 to 48 will not be available.
If you select CH1, Step 41, "Minimum Cool 1 Heat 1 Percent" will be available.
If you select FAN, Step 42, "Fan Spd Signal" will not be available
Cr1
Cr2
Hr1