SKF CMPT DCL Manual de usuario

SKF alarm and display module CMPT DCL
Copyright © 2014 by SKF Group
All rights reserved.
Aurorum 30, 977 75 Luleå
Sweden
Telephone: +46 (0) 31 337 10 00, Fax: +46 (0) 920 134 40
Part No. 32163200
Revision D
Instruction Manual

SKF Reliability Systems
SKF Condition Monitoring Center
Aurorum 30
977 75 Luleå
Sweden
Telephone: +46 (0) 31 337 10 00
FAX: +46 (0) 920 134 40
For technical support, contact:
for customers in Europe, Middle East and Africa.
Telephone: +46 (0) 31 337 65 00
or
for customers in North America, South America and Asia.
Telephone: +1 800 523 7514
Telephone in Latin America: +55 11 4448 8620
Visit us at our web site
www.skf.com/cm
® SKF is a registered trademark of the SKF Group

SKF alarm and display module CMPT DCL TOC-3
Instruction Manual, Revision D
Table of Contents
Description 1 - 4
Features 2 - 6
Specifications 3 - 7
Dimensions/Front panel 4 - 8
Caution 5 - 9
Wiring Connections 6 - 10
Configuration 7 - 11
Configuration for CMPT CTU Vibration and
Temperature Transmitter 8 - 13
....................................................................................................8 - 13
Vibration/Temperature and Alarm High
....................................................................................................8 - 16
Alarm Limit Setting and Alarm Options
....................................................................................................8 - 17
Completed Configuration and Connection to CMPT CTU
....................................................................................................8 - 17
Default Configuration when DCL is part of an SKF enclosure
....................................................................................................8 - 17
Connections with Relay Contacts
Optional Configurations 9 - 18
....................................................................................................9 - 18
Lock
....................................................................................................9 - 18
Display and Output Dampening
Appendix 10 - 19

Description
SKF alarm and display module CMPT DCL
1-4
Instruction Manual, Revision D
Description
1
Figure 1-1: CMPT DCL display and alarm module
This Instruction Manual provides detailed wiring connection and configuration
information for the CMPT DCL display and alarm module.
The CMPT DCL is configured by SKF when it is part of an assembled CMPT enclosure.
The CMPT DCL must otherwise be properly installed and configured by the user.
Important: Please read this Instruction Manual and the cautionary notes thoroughly.
·The SKF CMPT DCL is a digital alarm and display module. It is part of a machinery
fault detection system to monitor analog signals from the SKF CMPT CTU vibration
and temperature transmitter, various thermocouples and Resistive Temperature
Detectors (RTDs).
·The DCL is a single channel module with digital display and alarm function with LED
event lamp and relay contacts.
·The front panel digital display provides the user a visual indication of the monitored
signal. The display can be scaled to indicate vibration (gE, g, mm/s, inch/s),
temperature (°C, °F), etc. The DCL has programmable alarm, relay and variable
time delay functions. The DCL can indicate HIGH, LOW, HIGH-LOW, and various
other alarm limits. The front panel event lamp illuminates (red) to indicate alarm.
·The relay contacts are programmable with various options (Normally
Open/Normally Close, Non-latching/latching).
·The DCL provides a 4 to 20 mA output signal proportional to the scaled analog
input signal.

SKF alarm and display module CMPT DCL 1-5
Description
Instruction Manual, Revision D
·Two CMPT DCL modules are needed for stand-alone monitoring of an SKF CMPT
CTU vibration transmitter (one each for vibration and temperature). One CMPT
CTU and two DCL modules together are a user-friendly fault detection system of
machinery vibration and temperature.
·The CMPT CTU transmitter can also be connected directly to a PLC/DCS
automation system without the DCL modules.

Features
SKF alarm and display module CMPT DCL
2-6
Instruction Manual, Revision D
Features
2
·Monitors various inputs
Current (mA)
DC voltage (i.e. vibration or temperature signals from CMPT CTU)
Thermocouple
Resistive Temperature Detector (RTD)
·Digital LED display of monitored signals
·Programmable alarm function (one channel)
Alarm on HIGH, LOW or HIGH-LOW signal input, etc.
Front panel LED event lamp
Relay contacts
üNormally Open or Normally Closed
üLatching or non-latching
Time delay (0 to 9 999 seconds)
·Analog output signal (4 to 20 mA)
·Front panel user configurable
Input type
Display scaling
Alarm function
Analog output scaling
·No need for voltmeter and screw driver to set alarm function
·35 mm DIN rail mounted

SKF alarm and display module CMPT DCL 3-7
Specifications
Instruction Manual, Revision D
Specifications
3
Power requirements
Supply voltage: 24 V AC/DC (20 to 28 V AC/DC)
Supply current: 200 mA, maximum
Power: 6 W, maximum
Sensor input
Current*: 4 to 20 mA, 0 to 20 mA (Input impedance: 50 W)
Voltage: 0 to 10 V DC (Input impedance: 100 KW or greater)
0 to 1 V DC, O to 5 V DC, 1 to 5 V DC
Thermocouple: K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26).
External resistance 100 W or less
RTD: Pt100, JPt100 three wire system.
Allowable input wire resistance 10 W or less per wire
*50 W shunt resistor (0.1% precision) required at input terminals (not included)
Alarm function
LED event lamp on front display (red)
Relay contact: 48 V DC or AC / 1,0 Amp, maximum
Programmable
üAlarm setting value
üOptional alarm on HIGH limit, LOW limit, HIGH-LOW limit, HIGH-LOW range limit
üOptional Normally Open or Normally Closed relay contacts
üOptional Non-latching or latching relay contacts
üVariable time delay (0 to 9 999 seconds)
Output
Analog output signal (4 to 20 mA) proportional to scaled input
Digital display
Four H/7,4 mm x W/4 mm high-red LEDs,
Scaleable for vibration (gE, g , mm/s, inch/s), temperature (°C, °F)
Operating environment
Operating temperature: -10 °C to 50 °C (14 °F to 122 °F)
Storage temperature: -25 °C to 65 °C (-13 °F to 149 F°)
Humidity: 85 % maximum
IP rating: 30
Mechanical
Weight: 0,12 kg (0.27 lbs)
Enclosure: Polyethylene and PET resin
Color: Gray with green terminals
Connectors: One 4–pole screw clamp type/
0ne 5-pole screw clamp type (10 total)
Wiring: Power and analog output 0,2 mm to 1,5 mm
diameter (0.008 inch to 0.06 inch)
Input and relay out 0,2 mm to 0,5 mm diameter
(0.008 inch to 0.03 inch)
Mounting: 35 mm DIN-rail type EN50022
Dimensions (W x H x D): 22,5 x 75 x 100 mm (0.89 x 2.95 x 3.94 inches)
Approval
CE

Dimensions/Front panel
SKF alarm and display module CMPT DCL
4-8
Instruction Manual, Revision D
Dimensions/Front panel
4
Figure 4-2: Dimensions
1 OUT indicator:
A green LED lights up when OUT (control outputs)
is ON.
For DC current output type, it flashes in a 0,25
second cycle corresponding to the output
manipulated variable.
2 EVENT indicator (alarm)
5 The upper row of digital characters displays the
Present Value (PV)
6 The lower row of digital characteristics displays the
Setting Value (SV)
7 Increase Key ( )increases the numeric value
8 Decrease Key ( )decreases the numeric value
9 Mode key ( )changes the setting mode or
registers the setting value. [Registers the setting
value by pressing the Mode Key]
10 Sub-mode Key
(beneath the SKF logo)
brings up Auxiliary Function Setting Mode 2 in
combination with the Mode Key.
Figure 4-3: Front panel
The CMPT DCL has two rows of digital characters:
·the upper row displays the Present Value (PV). The PV is the value received from
the input device (CMPT DCL, either vibration or temperature). The upper row of
digital characters will display the Present Value (PV) from the CMPT DCL
transmitter when in the normal operating (default) state.
·the lower row displays the Setting Value (SV). The SV is an input set by the user
during configuration if the DCL is to use the HIGH-LOW or Range alarm settings.
Otherwise the SV is not used.

SKF alarm and display module CMPT DCL 5-9
Caution
Instruction Manual, Revision D
Caution
5
Read and understand these instructions thoroughly before working with the CMPT DCL.
The CMPT DCL shall be used by persons qualified to work with electrical
instrumentation.
Caution - Damage or injury can result
•The CMPT DCL is powered by 24 V DC. Do not apply higher voltage.
•Do not connect the sensor input (DC voltage) to the CMPT DCL (terminals 5, 6
and 7) until after the unit is powered and the input type is configured. See sections
"Configuration" and "Configuration for CMPT CTU vibration and temperature
transmitter".
•The CMPT DCL relay contacts are rated 48 VAC/DC, 1 Wmaximum. Do not apply
higher voltage / current.
•Higher voltage (110–240 V AC) power may exist in the same proximity as the
CMPT DCL. Use caution to avoid contact with any voltage source.
•Make sure that the power is disconnected prior to working with electrical wiring.
•Make sure that the CMPT DCL is installed in an environment within its
specifications (see section "Specifications")
Lightning strikes, power surges and other electrical anomalies can damage this device.
For the protection of your equipment, SKF recommends the power connections be
made through a surge protector.

Wiring Connections
SKF alarm and display module CMPT DCL
6-10
Instruction Manual, Revision D
Wiring Connections
6
The electrical connections and terminals of the CMPT DCL are listed below. The same
figure is also applied to the side of each module. It is recommended to use 1,5 mm
(AWG 18 gauge) wire with the DCL.
CMPT DCL
DCL terminal
+24 V DC
1
0 V DC
2
+4 to 20 mA OUT
3
4 to 20 mA COMMON
4
INPUT HIGH (+)
5
INPUT COMMON (-)
6
RTD INPUT
7
RELAY OUTPUT (contact)
8
RELAY OUTPUT (contact)
9
Figure 6-4: Wiring connections and terminals
Connecting the CMPT DCL with the CMPT CTU – vibration or temperature input (0
to 10 V DC)
Two CMPT DCL modules are needed to monitor both vibration and temperature from
the CMPT CTU transmitter. Optionally, one CMPT DCL can monitor either vibration or
temperature from the CMPT CTU. The following connections are made to connect the
DCL with the CTU.
CMPT CTU terminal to CMPT DCL terminal
Vibration
0 –10 V VIB OUT 16 5
VIB COMMON OUT 15 6
Temperature
0–10 V TEMP OUT 13 5
TEMP COMMON OUT 12 6
Tabla de contenidos
Otros manuales de Unidad de control de SKF

SKF
SKF BCU Manual de usuario

SKF
SKF BPSG2-PTA-MOD-EX-SS Manual

SKF
SKF MAXILUBE MAX 230-IF105 Series Manual de usuario

SKF
SKF DCV5-4+924 Manual

SKF
SKF DCV5-4+924 Manual de usuario

SKF
SKF LC502 Manual de usuario

SKF
SKF LINCOLN 85831 Manual de usuario

SKF
SKF Lincoln 85307 Manual de usuario

SKF
SKF Lincoln 85307 Manual de usuario

SKF
SKF SCU 1 Manual de usuario
Manuales populares de Unidad de control de otras marcas

Festo
Festo Compact Performance CP-FB6-E Manual de lista de piezas

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manual de usuario

JS Automation
JS Automation MPC3034A Manual de usuario

JAUDT
JAUDT SW GII 6406 Series Guía rápida

Spektrum
Spektrum Air Module System Manual de usuario

BOC Edwards
BOC Edwards Q Series Manual de usuario