9
Please find a sketch of the wiring diagram in the paragraph 1 of this manual.
Make sure that you fix the wires properly to prevent them from getting loose
due to vibrations. Fix the plastic screw nuts sufficiently to ensure electric
contact.
We recommend the use of the enclosed wire kits
3 x H07V-K 4mm2, red (input of 3 phases of the wind generator)
1 x H07V-K 6mm2, red (output "+" to battery)
1 x H07V-K 6mm2, black (output "-" to battery)
Connect the free end of the connecting wire with your wires coming from the wind
generator and the battery with suitable insulating screw joints.
In case you do not use the connecting wires we recommend the use of crimp type
cable sockets to fix your wires directly to the charge controller. After having fixed the
crimp type cable sockets with the bared wires these can be fixed to the cable
sockets.
It is most important that you first connect the charge controller to the battery
with the right polarity.
Please connect the enclosed fuse (50Amp.) close to the battery in the positive wire.
The fuse is only included in delivery if you buy a wind generator (not only a charge
controller).
Please take note:
If you wish to connect solar panels with more as 200Wp (20A) you must acquire a
stronger circuit breaker.
After the connection of the battery you can connect the Silentwind Generator, the
solar panel and if required a load output with maximum 15A. On the 3-phase output
wires of the Silentwind you need not to pay attention to polarity.
If you want to connect 24 volt batteries to the charge controller, make sure that the
voltage of the batteries is above 20 Volt. Otherwise the charge controller will detect a
12 volt battery system.
Attention: The confusion of Plus and Minus will definitely destroy your charge
controller. In that case warranty is gone.
If there is sufficient windspeed when connecting the Silentwind Generator, this will
immediately generate electric power at the end of the 3 AC-wires without being
connected to the charger. Therefore we recommend to block the Silentwind
Generator blades with a rope before connecting the wires to the charger. The 3 AC
output wires must be connected to the 3 screw terminals on the back of the charge
regulator. (see paragraph 3.2). In a 3 phase AC system the connection order /
polarity does not matter.
In case you want to connect additional solarpower (max. 550Wp or 40A) to the
charge controller, this should be done by using the PV screw terminals.
Please make always sure that you do not confuse polarity. You can find the
connection diagram in paragraph 8.