THIS GUIDE IS ONLY FOR EXPERIENCED INSTALLERS OF EMERGENCY OICE COMMUNICATION SYSTEMS (E CS) and summarises key information provided in the full manual (Document No.
DAU0000091). Section numbers, e.g. , reference sections in the full manual with additional information.
SigTEL (1 to 16 Lines) Standalone EVCS - Quick Start Installation Guide
FUSE
8 x
extension lines
EVC302F EVC301RPO
ECU-8*
EVC302GS
3A fused spur
ECU-8S
(optional)
Outstation lines: 2-core enhanced
fire rated cable (1.0 to 1.5 mm2), up
to 1 km in length.
Master/Slave connection:
Mount slave adjacent to
the master.
Power supply: Fixed wiring, 2-core
enhanced fire rated cable (0.75 mm2
to 2.5 mm2) fed from a switched spur,
fused at 3 amps.
additional
extensions
NC951
NC951 lines: 2-core
enhanced fire rated cable.
*ECU-8 has eight available
extension lines, ECU-4 (not
shown) has four.
1 of 2
Approved Document No. DAU0000093 Rev 2
SigTEL
Emergency Voice
Communication System
SigTEL EVCS Typical Wiring Overview
Install the EVCS
Location
Site all equipment indoors in well-lit areas, free from obstruction. If background noise exceeds 40 dBA,
use an acoustic hood. Site control unit(s) in the control room or lobby, 1.4 metres above final floor level
(FFL). Fit Type A (fire telephone) outstations in fire fighting lobbies and fire access points, 1.3 to 1.4
metres above FFL. Fit type B (disabled refuge) outstations in disabled refuges, 0.9 to 1.0 metre above FFL.
Mounting
Remove base PCBs before first fix installation to protect them and expose the base mounting holes.
Wall mount the control units, either surface or semi-flush. Fix the base securely onto a wall using No.8
round-head, or countersunk screws. If an optional ECU-8S is fitted make the interconnections to the
ECU-4/ECU-8 using supplied looms and short length of steel conduit (25 mm OD, max. length 60 mm).
After mounting, remove any dust/swarf and re-install base PCBs. Ensure all connecting looms are refitted.
6.1
6.1
Wiring and Cable Entry
See Fig 1 above for cable types. Install wiring in accordance with the relevant national, regional or local regulations (in the UK this is the IEE
Wiring Regs BS 7671 and BS 5839 Part 1. Use enhanced fire-rated cables from the controller to the outstations / NC951 and the power supply.
Test Extension Lines
Test all lines for faults before terminating extension lines to the control unit. Also, test outstation lines using a FITT EVC line tester (see
component list above).
CAUTION: DO NOT use an Insulation Resistance Tester with any devices connected as they will be destroyed and the warranty will be void.
Fit Outstations & NC951 Interface
aximum recommended cable distance to the outstations is 1 km, beyond which audio quality may degrade. For wiring and connection details
refer to Type A outstation instructions (Doc. No. DC 0003819) and Type B outstation instructions (Doc. No. DAU0302000).
Connect Extension Lines to the Control Equipment
Do not connect extension lines to the ECU-4/ECU-8, or optional ECU-8S, until they have been tested, fault-free and suitable cable glands fitted.
Connect extension lines directly to the Exchange PCB (see Fig 2 left). Connect screens to the earth terminal in the back of the enclosure.
4 x Extension Lines from Outstations & NC951
N/O C N/C 0V + 24O P3 OP2 OP1
All screens connect
to Earth terminal
ECU-4
Exchange PCB
A
CD
B
8 x Extension Lines from Outstations & NC951
N/O C N/C 0V + 24O P3 OP2 OP1
All screens connect
to Earth terminal
ECU-8 or ECU-8NT or ECU-8S
Exchange PCB
A
CD
B
Fig 2
7
4
11
13.1
SigTEL E CS Components
12
Fig 1
Part No. Description
ECU-4 4 Line aster EVC Controller c/w handset & display, needs 2 x 7 Ah batteries
ECU-8 8 Line aster EVC Controller c/w handset & display, needs 2 x 7 Ah batteries
ECU-8NT 8 Line aster EVC Controller (no handset) c/w display, needs 2 x 7 Ah batteries
ECU-8S 8 Line Slave EVC Expansion Unit (adds 8 extra lines to ECU-4, ECU-8, ECU-8NT)
EVC302F/GF Disabled Refuge (Type B) Outstation, flush mounting, SS (‘G’ - Green steel)
EVC302S/GS Disabled Refuge (Type B) Outstation, surface mounting, SS (‘G’ - Green steel)
EVC301RPO Red Fire Telephone (Type A) Outstation c/w handset (push to open)
EVC301RLK Red Fire Telephone (Type A) Outstation c/w handset (lift lock)
BF359/1 Weatherproof enclosure for EVC302F/GF
BF359/3D Stainless steel enclosure for ECU-4/ECU-8/ECU-8NT
NC951 Disabled Persons Toilet Alarm (DPTA)
FITT EVC Line Tester
BC286/2 24 V, 7 Ah battery (2 x 12 V) used with ECU-4/ECU-8/ECU-8NT
AFP385 Grey flush bezel for ECU-4/ECU-8/ECU-8NT
T-BEZ301 Red flush bezel for EVC301RPO and EVC301RLK
ECU423 PC programming software