9
has been configured press ‘ENTER’ when the ‘NEXT’ item is highlighted. This will bring up the
‘INPUT BIAS’ program screens. This allows configuration of the ‘normal’ condition of the relay and
solid state outputs.
In this screen an input channel can be configured to be ‘Normally Open’ or ‘Normally Closed’ when it
changes state, i.e. goes into alarm.
With the ‘Normally Open’ item highlighted with the cursor, press the ↑↓keys to select normally open or
normally closed.
With ‘Normally Open’ selected, the annunciator will alarm when the channel input closes. The channel
output relay will change state from open to close. The opposite action will occur with ‘Normally Closed;
selected.
NOTE: Where a system requires an output to change from closed to open on an alarm, channels 1-
4 provide SPDT contact outputs which may be used to satisfy this need. (See SETUP menu
“OUTPUT MODE’ screen.)
SETUP MENU - SEQUENCE
ALARM SEQUENCE PROGRAMMING
Several alarm sequences are available as follows:
NOTE: The audible alarm and the ‘Pop Up’ alarm windows will activate automatically upon an
alarm event if programmed to do so. See relevant section of this manual.
1) Sequence F3A
Automatic reset with first out indication. In this mode the first channel to go into an alarm condition will
be indicated by the channel indicator for that channel ‘flashing’ on and off. All other subsequent alarms
will be indicated by a ‘solid’ non flashing indicator. Once the alarm condition has been acknowledged
with the ‘ENTER’ key, the first alarm condition will ‘CLEAR’ automatically when the causal input has
been removed. Subsequent alarms must be reset manually.
2) Sequence ‘A’