Sentry AutoVREL Manual de usuario

Original Instructions
Installation, Operation
&Maintenance Manual
Sentry AutoVREL Flow Controller
Sample Conditioning Automation
S-SW-IOM-00457-2 02-18

2 Sentry Equipment Corp
Do not install, maintain, or operate this equipment without reading,
understanding, and following the appropriate Sentry Equipment Corp
instructions. Otherwise, injury, damage, or both may result.
Copyright
© 2018 by Sentry Equipment Corp. All rights reserved. All product and company names
are property of their respective owners. This document contains proprietary information.
No part of this document may be photocopied or reproduced without the prior written
consent of Sentry Equipment Corp.
Limit of Liability
Sentry Equipment Corp, its employees, agents, and the authors and contributors to this
document specically disclaim all liabilities and warranties, express or implied (including
warranties of merchantability and tness for a particular purpose), for the accuracy,
currency, completeness, and/or reliability of the information contained herein and/or
for the tness for any particular use and/or for the performance of any material and/or
equipment selected in whole or part with the user of/or in reliance upon information
contained herein. Selection of materials and/or equipment is at the sole risk of the user of
this publication.
Note
The information contained in this document is subject to change without notice.
Table of Contents
Safety Information ......................... 3
General Safety Precautions ................. 4
Specications .............................. 5
General Description ........................ 6
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operation.................................. 14
Parts List................................... 17
Accessories List ............................ 18
Standard Warranty ......................... 18
Customer Support.......................... 19

Sentry AutoVREL Flow Controller 3
Safety Information
Please read the entire manual before attempting to unpack, set up, or operate this
product. Pay careful attention to all Warnings, Cautions, and Notes. Failure to do so could
result in serious personal injury and/or equipment damage.
Use of Hazard Information
If multiple hazards exist, the signal word corresponding to the greatest hazard shall be
used.
Denitions
DANGER indicates a hazardous situation
which, if not avoided, will result in death or
serious injury.
WARNING indicates a hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION, used with the safety alert symbol,
indicates a hazardous situation which, if not
avoided, could result in minor or moderate
injury.
NOTICE is used to address practices not
related to personal injury.
ÂNOTE
Information that requires special emphasis.
ÂTIP
Alternate techniques or clarifying information.
SHALL:
This word is understood to be mandatory.
SHOULD:
This word is understood to be advisory.

4 Sentry Equipment Corp
General Safety Precautions
Product Selection, Installation, and Use
Improper selection, installation, or use can cause personal injury or property damage. It is solely
the responsibility of users, through their own analysis and testing, to select products suitable
for their specic application requirements, ensure they are properly maintained, and limit their
use to their intended purpose.
Follow proper local, state, and federal regulations for proper installation and operational
requirements.
Always use caution and common sense when working with any chemical. Read the product
label and Material Safety Data Sheets (MSDS) carefully and follow the instructions exactly.
Potential Equipment Hazards
Hot surfaces! This equipment may have very hot surfaces. If an operator contacts a hot surface,
injury may occur. Use protective clothing to prevent injury. If other equipment comes in contact
with a hot surface, damage to the equipment may occur. Ensure the area around this equipment
is kept clear to prevent this damage from occurring.
High pressures! This equipment may contain uids at very high pressures. Prior to installing,
removing, or maintaining this equipment, ensure that the equipment is isolated from all
connecting piping, the equipment is depressurized, the contents have been drained, and the
equipment is cool.
Moving parts! This equipment may contain moving parts. All drive guards and doors must be
secured in place when this machine is being operated.

Sentry AutoVREL Flow Controller 5
Specications
Specications are subject to change without notice.
Sample Ratings
Pressure: 500 to 3000 psi (35 to 207 bar)
Temperature (calibrated): 60 to 95°F (15 to 35°C)*
Range: 200 to 1500 cc/min**
Accuracy: ± 100 cc/min**
Measurements
Sample Flow Rate
Alarm Relay Contact Rating
Max. operating voltage: 250 VAC, 220 VDC
Max. switching capacity: 25 W, 55 VA Inductive
55 W, 110 VA Resistive
Display
Backlit LCD 2x8 character
Power
Input Voltage: 24VDC +/-10%
Typical Operating Current: 0.5 A
Absolute Max Current: 3 A
(see parts list for power sizing recommendations)
Wired Connections: 14-30 AWG
Power supply needed (see Parts List)
Wiring
Min Current rating: 3A
Wire Size: 14-30 AWG
Dimensions
4.25 in L x 4.25 in W x 6.93 in D
Mounting
Panel mount
Factory mounting recommended
Optional installation kit available (see Parts List)
Ambient Temperature
-4 to 140°F (-20 to 60°C)
Approximate Shipping Weight
15 lb (6.8 kg)
*The AutoVREL has been designed for optimum performance at EPRI recommended value of 25°C (77°F). If your normal
sample temperatures fall outside the sample temperature range, please contact Sentry Equipment to discuss options.
**Range and accuracy are dependent on ow meter selection. Numbers shown are based on the default ow meter.

6 Sentry Equipment Corp
General Description
Flow control of water and steam sampling is important to help assure representative
sampling, quality of the samples and, repeatability of the analytical results. During plant
cycling, constant ow in the sample line minimizes the chance of altering the chemistry
of the samples of high purity water through entrapment and/or release of soluble species
from deposits in the system. Sample inlet temperature and ow are easily controlled
under base load conditions. However, since sample pressures typically uctuate during
varying load conditions, maintaining a representative sample can be dicult and labor
intensive. The traditional manual sample conditioning system can require constant
adjustment during startup or as plant conditions change. The Sentry® AutoVREL Flow
Controller is designed to meet requirements for representative sampling by maintaining
a constant ow rate with varying inlet conditions. Automated ow control is achieved by
continuously monitoring the sample ow rate and controlling a Sentry VREL® valve. This
helps to avoid nuisance analyzer alarms and continual operator intervention.
ÂNOTE
The Sentry AutoVREL ow controller is designed to be used in conjunction with the Sentry TSV
(thermal shut-o valve) with alarm switch.

Sentry AutoVREL Flow Controller 7
Sample
In
2
V-2C
SC-2
Flush Water 3 2
* MT-5V
Mag Trap F-1
To Sink
41
VREL
TSV-1
SC-1
Alarm to
Customer
DCS
ZS-
310
R
MAutoVREL
FE-
307
FI
1
PI
1TI
1
F-2
MT-1 (option)
To Analyzers
To Sink
BPR/RV
* MT-5V recommended in applications
with high magnetite loading
Example P&ID

8 Sentry Equipment Corp
AVREL-300
AutoVREL
Alarm PWR Flow Meter
Optional
Alarm Out
Default Flow Meter
Power for
AutoVREL
BLK
BLU
BRN
4-20mA
-VDC
+24V
ZS-310
NO
NC
C
COM
NC
NO
TSV IN
RESERVE
GND
+24VDC
GND
MOD +
MOD -
+24VDC
+12VDC
GND
4-20mA IN
0-5VDC IN
EWD - AutoVREL
ZS-310
ZS-207
From DCS
To DCS
Replaced with
AutoVREL
AVREL-300
AutoVREL
Alarm PWR Flow Meter
Default
Flow
Meter
Power for
AutoVREL
BLK
BLU
BRN
ZS-310
TSV Connections
moved to AutoVREL
COM
NC
NO
TSV IN
RESERVE
GND
+24VDC
GND
MOD +
MOD -
+24VDC
+12VDC
GND
4-20mA IN
0-5VDC IN
Alarm to
Customer
DCS
Example TSV Alarm Conguration

Sentry AutoVREL Flow Controller 9
Installation
Unpacking
After carefully removing the Sentry AutoVREL ow controller and ow meter from its
shipping carton, inspect it for any damage. Report damages to the shipper immediately.
Mounting
ÂNOTE
Installation by a Sentry authorized service representative is recommended due to the complex
mechanical and electrical assembly needed.
Equipment Needed
Sentry AutoVREL ow controller
– controller and drive unit
– ow meter
– wire harnesses – DC power (4-pin connector) and I/O harness (8-pin connector)
– shaft adapter, set screw and locking nut
Corded power drill
Cutting oil
Loctite Blue 242 or equivalent
Hammer
1/8-inch, 3/16-inch and 9/64-inch Allen wrenches
7/16-inch and 1/2-inch open-end, crescent or socket wrench or equivalent
Sentry AutoVREL mounting kit
Sentry TSV thermal shuto valve and TSV switch (may already be on panel)
24 VDC power supply (only required if not available on existing panel)
AutoVREL
control unit
AutoVREL
drive unit
Mounted after secondary cooling Flow meter
TSV
TSV Switch
VREL control valve
Wire to ow meter
inputs on AutoVREL
ow controller
Wire to AutoVREL TSV
input and GND
(Alarm Conn pins 4 & 6)
Optional Alarm wiring
can be routed to the
AutoVREL ow controller

10 Sentry Equipment Corp
Installation Instructions
To avoid potential safety concerns, isolate the sample stream before beginning installation.
1. Using a 3/16-inch Allen wrench, loosen and
remove the Sentry VREL control valve handle.
ÂNOTE
Do not mark holes with punch until transfer plate is
level.
2. Place the transfer plate (2) from the Sentry
AutoVREL mounting kit over the Sentry VREL,
with the LEVEL indicator at the top of the
plate. Once the plate is horizontally level,
mark the ve (5) holes using the transfer
punch and hammer.
ÂNOTE
Stainless steel is a challenge to drill/punch through,
so make sure to constantly keep the drill wet with the
cutting oil and do not rush drilling.
3. Remove the transfer plate and, using the
3/8-inch drill bit, drill the ve (5) holes
through the panel.
4. The four (4) holes around the periphery of
the transfer plate should be deburred with a
standard le.
5. Using the hole punch provided in the Sentry
AutoVREL installation kit, punch out the
1-7/64-inch hole just to the right and below
the Sentry VREL control valve. This hole will
be used for the cable gland, and therefore
MUST be free of burrs. The cable gland will
serve as a channel way for the electrical
connections to the AutoVREL ow controller.