Seat 819700 Manual de usuario

Fume Hood Controller
Type A
REF 819700/819701
The type A controller is a safety device for monitoring a fixed air flow.
A speed sensor is used to determine the flow rate. Audible and visual alarm is set off in
case of insufficient speed or too high window height and other conditions.
The HMI allows to control the ventilation of the fume cupboard and to make the
adjustments on site.
This controller complies with standard EN 14175 and RoHS.

2
Table of contents
1. Presentation .................................................................................................................................... 3
1.1. Front panel .................................................................................................................................. 3
1.2. Electronic panel........................................................................................................................... 3
1.3. Schematic diagram ...................................................................................................................... 4
1.4. Connectors specifications............................................................................................................ 5
2. Installation and mounting ............................................................................................................... 6
2.1. Dimensions.................................................................................................................................. 6
2.2. Positioning on the fume hood..................................................................................................... 7
2.3. Cutting template ......................................................................................................................... 8
2.4. Installation tips............................................................................................................................ 9
3. Wiring diagram.............................................................................................................................. 10
4. Adjustment procedure .................................................................................................................. 11
5. Factory reset.................................................................................................................................. 12
6. Test mode...................................................................................................................................... 12
7. Change the audible alarme delay.................................................................................................. 13
8. Error messages (digital display option) ......................................................................................... 13
9. FAQ................................................................................................................................................ 14
10. Maintenance.............................................................................................................................. 15
11. Warranty.................................................................................................................................... 15
02/11/2021

3
1. Presentation
The type A flow controller is an electronic unit that can be easily installed on all fume hood.
The front panel controls the ventilation while the rear panel provides wiring.
1.1. Front panel
1.2. Electronic panel
Display
(Option)
Green LED: air flow OK
Red LED: insufficient air flow
Orange LED: sash too high
Yellow LED: ventilation ON/OFF
Push-button: ventilation ON/OFF
Yellow LED: lighting ON/OFF
Push-button: ON/OFF the lighting
Orange LED: auxiliary faults
Push-button: stop buzzer
VENT1 : ON/OFF
ventilation relay
VENT2 : ON/OFF
ventilation relay
Alarm contact
Light relay
Overtaking sash
contact
aux faults contact
or
night setback
Transformer 230v/12v
connector
Speed probe
connector
Push-button
velocity display
Cut the resistance to activate
the night setback mode

4
1.3. Schematic diagram
220v power
supply
FAN1 ON/OFF
Motor
power
supply
Switch sash
position
Power
contactor
Velocity probe
The type A flow controller is used to control the air flow of a fume hood.
Pressing the ON/OFF ventilation button on the remote interface closes the two relays VENT 1 and VENT 2,
which supplies the fan via a power contactor. It is a fixed flow controller.
A speed sensor permits to measure whether the suction flow is sufficient (≥0.4 m/s) and indicates, the
ventilation status by a green and a red LED.
The front panel allows you to control the operation of the fume cupboard and in particular:
-An ON/OFF for lighting
-An ON/OFF for ventilation
-An alarm stop button

5
1.4. Connectors specifications
Power supply
Electrical transformer 230v/12v 500mA. (delivered with)
VENT1/FAN1
ON/OFF ventilation relay driving by
Disconnection voltage : 120v
Disconnection current : 0.5 A
VENT2/FAN2
Same VENT1
LIGHT
ON/OFF lighting relay driving by
Disconnection voltage : 220v
Disconnection current : 3 A
ALARM
Relay controlled by alarm activation. Normally open contact
Disconnection voltage : 120v
Disconnection current : 0.5 A
SASH Open
Sash contact which triggers a visual and audible alarm.
IDLE
Auxiliary fault contact which triggers a visual and audible alarm.
This contact can be used to enable night standby mode by cutting
the resistance shown on page 3.

6
2. Installation and mounting
2.1. Dimensions
HMI
(Front and side view with surface box mounting)
Speed sensor
75mm
210mm
34mm
65 mm
40 mm
28 mm
22 mm

7
2.2. Positioning on the fume hood
The speed sensor must be positioned on
the fume hood ceiling in one of the two
positions shown in the diagram.
These locations must be respected so that
the probe is accurate.
Drill a 22mm diameter hole and put the
speed sensor in it.
An adhesive is provided on the sensor to
fix it correctly to the fume hood and
prevent leaks.
Where to install the speed probe?
Vertical HMI are usually attached to
the side frame of fume hoods.
Horizontal HMI’s can be set at the
user’s convenience.
◌
To comply with EN 14175
standard, you must install a
sash contact.
The sash contact must be fixed so that
it sets off when the sash exceeds
400mm or 500mm.
◌
500mm

8
2.3. Cutting template
If you want to install your fume hood controller without the surface box mounting, you will
need to make the following cuts:
67mm
173mm

9
2.4. Installation tips
•Do not install the sensor on the extraction tube above the fume hood
•Avoid installing the sensor in a dead zone of the fume cupboard
•The probe must pass entirely through the fume cupboard ceiling. Otherwise, you
must use a 25mm PVC tube to extend the outlet.
•A speed of 0.2 m/s minimum must be measured through the sensor to ensure proper
operation.
•When adjusting the controllers, it is necessary that:
oThe fans are running
oThe laboratory is completely closed (doors, windows, etc.)
oHave an anemometer
•Pay attention to motor connections (star or delta)
Note: For type A controller, no driver is necessary.
230V single phase
power supply
400V three phases
power supply
400V three phases
output
230V three phases
output
DELTA
STAR

10
3. Wiring diagram
220v power
supply
ON/OFF
ventilation
L
N
Power supply
Switch sash
position