Modbus
Registers The controller supports the following Modbus registers and function codes. The default communication speed is
9600 bps, 8 data bits, Parity None and 1 Stop Bit.
Register Parameter Description Data Type Range
FUNCTION CODE 01 -READ COILS
1Overdrive mode Bit0 On -Off
2NIGHT-mode Bit1 On -Off
3SERVICE ALARM Bit2 On -Off
5Fan Speed 1 asked Bit4 On -Off
6Fan Speed 2 asked Bit5 On -Off
7Fan Speed 3 asked Bit6 On -Off
8Fan Speed 4 (Auto) asked Bit7 On -Off
FUNCTION CODE 02 -READ DISCRETEINPUTS
1Occupied by PIR ( NIGHT mode to DAY-mode ) Bit0 On -Off
2Manually Occupied ( NIGHT mode to DAY-mode ) Bit1 On -Off
3DAY EXTENSION ( NIGHT mode to DAY-mode ) Bit2 On -Off
4EXT.S (External Sensor) Bit3 On -Off
5Fan Speed 1 run Bit4 On -Off
6Fan Speed 2 run Bit5 On -Off
7Fan Speed 3 run Bit6 On -Off
FUNCTION CODE 03 -READ HOLDING REGISTERS
2Coils 16 -01 16 bit
3Fan Speed (Set by Network) Signed 16 0 -1 -2-3 -4
4Cooling Output (Set by Network) Signed 16 0,0 … 100,0 (%)
5Heating Output (Set by Network) Signed 16 0,0 … 100,0 (%)
6Set Point (Set by Network) Signed 16 5,0 … 37,0 (C)
13 DAY EXTENSION period Signed 16 1 … 480 (min)
FUNCTION CODE 04 -READ INPUT REGISTERS
1Discrete Inputs 16 -01 16 bit
2Coils 16 -01 16 bit
3Fan Speed (Set by Network) Signed 16 0 -1 -2-3 -4
4Cooling Output (Set by Network) Signed 16 0,0 … 100,0 (%)
5Heating Output (Set by Network) Signed 16 0,0 … 100,0 (%)
6Set Point (Set by Network) Signed 16 5,0 … 37,0 (C)
7Temperature Signed 16 -60,0 … 60,0 (C)
8CO2 Signed 16 0 … 2000 (ppm)
9Current Cooling Output Signed 16 0,0 … 100,0 (%)
10 Current Heating Output Signed 16 0,0 … 100,0 (%)
11 Current Fan Speed Signed 16 0 -1 -2-3