PPI UniRec Manual de usuario

Process Data Recorder
User Manual
UniRec
HumiTherm-i HumiTherm-c
HumiTherm-iS HumiTherm-cS
Test Chamber 1
25.3 C
o

CONTENTS
User Manual
UniRec
1. FRONT PANEL : LAYOUT AND OPERATION 1
2. BASIC OPERATION 3
3. PEN-DRIVE OPERATIONS 6
4. SET-UP MODE : ACCESS AND OPERATION 12
5. OPERATOR PARAMETERS 14
6. SUPERVISORY CONFIGURATION 15
7. DEVICE CONFIGURATION 16
8. RELAY CONFIGURATION 18
9. RECORDER CONFIGURATION 19
10. RTC SETTING 21
11. UTILITIES 22
12. ELECTRICAL CONNECTIONS 23

Section 1
The front panel comprises of 2 X 16 (2 rows of 16 characters each) LCD Display, LED indicators, membrane keys, and a
slot for Pen Drive. Refer Figure 1.1 below.
ENTER Key
UP Key
DOWN Key
PAGE Key
PPI
UniRec
SELECT PAGE>>
Device Config
AUTO
Lower Row
2 X 16 LCD Display
Pen Drive Slot
Upper Row
LED Indicator
Figure 1.1
LCD DISPLAY
The LCD Display has 2 rows, the Upper Row & the Lower Row; each having 16 Characters. In normal mode of operation
(Run Mode), the Upper Row displays the Channel Name and the Lower Row displays the corresponding Process Value
followed by Units. Refer Figure 1.2 (a) below.
In Set-up Mode, the Upper Row displays the parameter Name and the Lower Row displays the corresponding parameter
Value. Refer Figure 1.2(b) above.
Oven Temp
Figure 1.2(a)
120 C
SCAN RATE>>
15
Figure 1.2(b)
LED INDICATOR
The front panel round LED lamp indicates the channel scan mode. LED glows ON if the channel scanning is in Auto
mode.
KEYS
There are four tactile keys provided on the front panel for setting-up the parameter values and for other functions &
commands. The Table 1.1 below lists each key and the associated function.
User Manual
UniRec
1
FRONT PANEL : LAYOUT AND OPERATION

User Manual
UniRec
2
PEN-DRIVE SLOT
A rectangular slot with USB connector type A is provided for Pen-Drive operation.
ENTER
Symbol Key Function
DOWN
UP
PAGE Press to enter / exit Set-up Mode.
Press to decrease the parameter value. Pressing
once decreases the value by one count; holding the
key pressed speeds up the change.
Press to increase the parameter value. Pressing
once increases the value by one count; holding the
key pressed speeds up the change.
Press to store the set parameter value and to scroll to
the next parameter.
Table 1.1

BASIC OPERATION
POWER-UP
Upon switching on the power to the unit, the display shows model name on the Upper Row and the Firmware Version
Number on the Lower Row for approximately 4 seconds as shown below.
UniRec USB
Version 1.0.1.0
After the power-up display sequence, the UniRec starts showing the process values for all the Device Channels
sequentially. This is the MAIN Display Mode that shall be used most often.
MAIN DISPLAY MODE
This is the default display mode. This mode actually comprises of 4 different screens providing different information. The 4
screens are described below. Use Enter key (press and release) to switch from one screen to the next. The multiple
information within a selected screen can be viewed using UP / DOWN keys.
Process Value Screen
This is the default screen upon entering the Main Display Mode. The Upper Row shows the Device channel name and the
Lower Row shows the corresponding process value along with user set Units as shown below.
Oven Temp
Device Channel Name
Process Value
Units
120 C
In case of process value error, the Lower Row indicates the type of error in place of process value and units. The various
errors and the respective causes are listed in Table 2.1.
Table 2.1
Process Value above Max. Range
Process Value below Min. Range
Error Message Cause
Thermocouple / RTD broken
Sensor Open
Under Range
Over Range
Communication Link with Device brokenCom. Fail
The channel-wise process value updates depend upon the selected Auto / Manual scan mode. The scan mode can be
toggled between Auto and Manual by holding the ENTER key pressed for approximately 5 Seconds. The front panel LED
indicator glows ON in Auto mode and remains OFF in Manual mode. The channel update rate in Auto mode depends
upon the set value (1 to 99 Sec.) for the parameter ‘Scan Rate’. In Manual mode, the channels can be scrolled using UP
and DOWN keys.
Alarm Status Information Screen
The UniRec monitors and stores the Alarm status for the first two Alarms of each connected Device Channels. If any one
or more set Alarms for a channel is active, the channel is said to be under Alarm condition. The names for the channels
under Alarm condition keep flashing on the Upper Row in Process Value screen.
The complete Alarm status information for the channels under Alarm condition is available on this Screen. For example; If
Alarm1 (AL1) and Alarm2 (AL2) of a channel named ‘Boiler Pressure’ is active then the screen displays the following
information.
User Manual
UniRec
3
Section 2

If multiple channels are under Alarm condition; use UP / DOWN keys to scroll through the various Device channels for
viewing the individual Alarm status information.
Note: The front panel ENTER key can be used as Alarm - Acknowledge key. Use Alarm Acknowledgment feature to de-activate the
Alarm relay. Note that acknowledging the Alarm(s) does not remove the Alarm condition(s).
Recording Information Screen
This screen facilitates viewing information related to the recording feature. Use UP/DOWN keys to scroll through the
various information described below in Table 2.2.
Table 2.2
Balance Time>>
1:12:36
Information Sample Screen
New Records>>
12523
Old Records>>
10067
Free Space>>
3833410
First Record>>
Date: 01:01:11
This information is available if ‘Batch Recording’ mode is selected
and shows the remaining batch time in Hours:Minutes:Seconds
(HH:MM:SS) format if the batch is in progress. Upon completion or
prior to start of the batch, the remaining time is shown as 0:00:00.
REMAINING BATCH TIME
NEW RECORDS IN MEMORY
Shows the numbers of new records available in the recorder
memory for copying (downloading) to Pen-Drive using ‘Copy
(New)’ command.
Shows the numbers of old records available in the recorder
memory that were copied (downloaded) in the previous session.
These records can be re-copied using ‘Re-copy (Old)’ command.
OLD RECORDS IN MEMORY
Shows the recorder memory space available for new records.
That is, this information shows how many more new records can
be stored in the memory before it gets full.
FREE SPACE AVAILABLE FOR NEW RECORDS
This information shows the calendar date of recording of the first
available new record in the memory. This information does not
appear if there are no new records in the memory.
DATE STAMP FOR THE FIRST
NEW RECORD IN THE MEMORY
This information shows the clock time of recording of the first
available new record in the memory. This information does not
appear if there are no new records in the memory.
TIME STAMP FOR THE FIRST
NEW RECORD IN THE MEMORY
First Record>>
Time: 23:05:40
User Manual
UniRec
4
Boiler Pressure
AL1 AL2

Information Sample Screen
This information shows the calendar date of recording of the latest
available new record in the memory. This information does not
appear if there are no new records in the memory.
DATE STAMP FOR THE LAST
NEW RECORD IN THE MEMORY
Last Record>>
Date: 02:01:11
This information shows the clock time of recording of the latest
record in the memory. This information does not appear if there
are no new records in the available new
TIME STAMP FOR THE LAST
NEW RECORD IN THE MEMORY
Last Record>>
Time: 14:12:10
RTC Screen
This is a single screen providing the Real Time Clock (RTC) information as shown below. The upper row shows the
current calendar date in dd/mm/yy format and the lower row shows the running clock time in hh:mm:ss (24 Hours) format.
Date: 16/05/11
Time: 08:56:00
User Manual
UniRec
5

PEN-DRIVE OPERATIONS
UniRec can perform both, File Read and File Write, operations on the Pen Drive. The File Read Operation facilitates
assigning user defined names to each of the connected Device channels while the File Write operation allows copying the
Process Value records (stored inside the internal memory of UniRec) onto the Pen Drive for subsequent reading in Excel
Sheet. The two file operations are described in detail in the following pages.
File System for Read Operation
UniRec continuously monitors and updates the Process Values (PVs) for each Device channel. The Process Values are
displayed on the front panel 2 Rows LCD display. The Upper Row displays the channel name while the corresponding PV
and measurement Units are shown on the Lower Row.
UniRec supports up to 30 single or dual channel devices. In ‘Device Configuration’ setup mode; the user needs to enter
the Device Number, the Device Type and the Device Communication ID.
UniRec assigns default channel names depending upon the device number assigned by the user (in ‘Device
Configuration’ set-up mode) and the numbers of channels (1 or 2) belonging to the selected device type. Refer following
examples for clarification.
Example 1
Device
Number
Device
Type
Channels
Per
Device
Default Assignments by UniRec
Channel Number
1Zenex 1 1 Channel-1
2neuro102 1 2 Channel-2
Channel Name
Device
Number
Device
Type
Channels
Per
Device
Default Assignments by UniRec
Channel Number Channel Name
1 Zenex 1 1 Channel-1
2Zenex 1 2 Channel-2
3 Clavex 1 3 Channel-3
4 HumiTherm-c 2 4 Channel-4
5 Channel-5
5 neuro100 1 6 Channel-6
Example 2
The user can, however, assign a more meaningful name (such as Boiler Pressure, Oil Temperature, etc.) to each device
channel for easy identification of the process parameters that are being measured and displayed.
User Manual
UniRec
6
Section 3

1. Open Microsoft Notepad Application Tool. A blank screen appears.
2. Type the desired name for Channel-1 in the top (first) line and press Enter key.
3. Type the desired name for Channel-2 in the next (second) line and press Enter key.
4. Repeat the procedure for other channels until names for all channels are assigned.
5. Open “File” menu and select “Save” option. In the open pop-up window, select appropriate directory, assign the file
name Set.txt (or only Set) and press “Save” button.
6. Copy the file onto Pen Drive in the main directory (outside of any folders) for subsequent File Read operation by the
UniRec.
Figure 3.1
Notes:
1. All the channel names must be written in the sequence starting with name for channel-1 in the first (top) line.
2. Each channel name must be terminated with Enter key operation to indicate the end of the name and for moving to the next line. An
Enter key operation is required for even the last channel name.
3. Do not leave any line space at the top of the file or between two consecutive channel names.
4. Each channel name must not exceed 16 characters. Any additional characters will be automatically ignored. The 16 characters are
counted from the left-most screen position.
File System for Write Operation
UniRec continuously fetches the measured Process Values and Alarm Status from various device channels.
A set of Process Values along with the corresponding Alarm Status for all channels, stamped with the current Date and
Time, is called a Record. UniRec stores such records in its internal memory at user set time interval, called Recording
Interval. These stored records are then available for downloading to a Pen Drive via the front panel USB connector.
Each of the installed UniRec creates and maintains its own Record-Data file on Pen Drive using a file naming scheme
User Manual
UniRec
7
For channel name assignments, the user can create and save a text document file with the name Set.txt using Microsoft
Notepad Application tool. The file needs to be saved on the Pen Drive in the main directory (outside of any folders).
Follow the guidelines below for creating and/or editing the file (Set.txt) for channel name assignments. Refer Figure 3.1
for example file.

that involves an user assigned identification tag, called Recorder ID. The user can assign any numeric value, from 1 to
127, as Recorder ID to the UniRec for its unique identification. The file created by UniRec for downloading the stored
records is named recN.csv; where N is the Recorder ID assigned to the UniRec. For example; the UniRec with Recorder
ID 5, creates and maintains the file with the name rec5.csv. The records are downloaded to the file on Pen Drive in
Comma Separated Values (CSV) format and thus the file is assigned the extension '.csv'.
Upon selecting the ‘Copy (New)’ or ‘Re-copy (Old)’ operation (explained later) after insertion of the Pen Drive; the UniRec
first searches for any existing file with the name recN.csv (where, N is the Recorder ID assigned to the UniRec). If the file
exists, the UniRec appends the available stored records to the file. If the file does not exist, the UniRec automatically
creates a new file with the name recN.csv (where, N is the Recorder ID assigned to the UniRec) and then downloads the
records.
Back-up File System
It is possible that a file-write operation may be interrupted due to reasons like sudden power-failure or removal (or, loose-
contact) of the Pen Drive, resulting in partial transfer of records. An interrupted file-write operation makes the file unusable
for appending any further records. Also, the partially transferred records in the interrupted file are lost (but are still retained
inside the UniRec’s internal memory). That is, the file on Pen Drive exists with the previous records intact (if any) and
becomes a read-only file.
An interrupted file-write operation event is registered by the UniRec in its internal memory as well as on the Pen Drive that
was being written. Upon resumption of operation, the UniRec prompts for Recovery of the interrupted operation. Upon
selecting the “Recover” operation, the following sequence of steps is executed.
1. A back-up file of the existing interrupted file is created to retain the previous records.
The back-up file is named bN_S.csv; where, 'N' is the Recorder ID and 'S' is the sequential number (1 to 250) assigned
to the back-up file. For example; if the Recorder ID is 5 and there does not exist any previous back-up file, then the
new back-up file is named b5_1.csv. If, however, there exists previous back-up file(s), then 'S' is assigned the lowest
numeric value (in sequential order). For example; if a Pen Drive already contains back-up files – [b5_1.csv, b5_4,csv
and b5_14.csv] – then the new back-up file is named b5_2.csv.
2. The existing interrupted file is deleted.
3. A new file with the same name (e.g. rec5.csv) is created.
4. All the records (including those that were already transferred during the interrupted operation) are downloaded to the
new file.
PEN DRIVE (MEMORY-STICK) OPERATION
The UniRec is provided with a front panel USB port for file read and write operations using Pen Drive.
Pen Drive Checking
Upon inserting the Pen Drive into the USB port, the UniRec responds by displaying the following message on the LCD
screen:
Please Wait....
User Manual
UniRec
8