Power Measurement ION 8300 Manual de usuario


PRODUCT WARRANTY
For products and software that are sold or licensed by Power Measurement Ltd. (“Power Measurement”)
during the period from the date of receipt by you until the present, Power Measurement warrants only
to the original purchaser who acquired the products or software, or a purchaser through an authorized
representative (the “Purchaser”):
1. that the purchased products other than software shall be substantially free from material defects
in material and workmanship by Power Measurement for thirty-six (36) months from the date of
receipt by you; and
2. that the medium on which any purchased software (“Software”) is provided shall be substantially
free from material defects in material and workmanship for twelve (12) months from the date of
receipt by you of any purchased Software.
The Software itself is provided “as is” without any warranty of any kind.
In order for the Purchaser to make a claim under the warranties described in items 1 and 2 above
(“Warranties”) the Purchaser must promptly (but in any event before the Warranties period ends)
contact Power Measurement, 2195 Keating Cross Road, Saanichton, British Columbia, Canada V8M
2A5 at telephone number 1-250-652-7100. After receiving such notice, Power Measurement may
either in Power Measurement's sole discretion, examine the product at the Purchaser's site or issue
shipping instructions to the Purchaser to return the relevant product to Power Measurement for
examination at the Purchaser's expense, transportation charges prepaid.
If after examining the product Power Measurement reasonably confirms that such examined product
does not meet the Warranties, then the Purchaser's sole remedy and Power Measurement's sole
obligation or liability shall be, at Power Measurement's option, to repair, replace or refund the price
paid for the product.
Regardless of whether any remedy set forth herein fails of its essential purpose, except to the extent the
following limitation is prohibited by applicable law, Power Measurement shall not, in any event or under
any legal claim or theory (whether based on contract, indemnity, warranty, tort (including negligence
and strict liability) or otherwise), be liable to the Purchaser or any other person or entity for special,
indirect, incidental, punitive, liquidated, special or consequential damages whatsoever with respect to
any purchased product, including, without limitation, business interruption, loss of use, profit or
revenue, even if Power Measurement has been advised of the possibility of such damages. To the extent
that a limitation or exclusion of consequential damages are prohibited by applicable law, then Power
Measurement's liability shall be limited to twice the amount of the relevant purchased product.
Not to limit the foregoing, a) Power Measurement shall not be liable for any claim (other than a claim
solely for the breach of one of the above Warranties that is made in accordance with the above
described procedures) made by the Purchaser, its employees, agents, or contractors for any loss,
damage, or expense incurred due to, caused by, or related to any purchased product; and b) the above
Warranties are the Purchaser's exclusive remedy and Power Measurement hereby expressly disclaims
all other warranties, express or implied, including, without limitation, warranties of non-infringement
and the implied warranties of merchantability and fitness for a particular purpose.
These limited Warranties shall not apply to any product that has been subject to alteration, accident,
misuse, abuse, neglect or failure to exactly follow Power Measurement's instructions for operation and
maintenance. Any technical assistance provided by Power Measurement's personnel or representatives
in system design shall be deemed to be a proposal and not a recommendation. The responsibility for
determining the feasibility of such proposals rests with the Purchaser and should be tested by the
Purchaser.
It is the original Purchaser's responsibility to determine the suitability of any product and associated
documentation for its purposes. The original Purchaser acknowledges that 100% “up” time is not
realizable because of possible hardware or software defects. The original Purchaser recognizes that
such defects and failures may cause inaccuracies or malfunctions.
Only the terms expressed in these limited Warranties shall apply and no distributor, corporation or
other entity, individual or employee of Power Measurement or any other entity is authorized to amend,
modify or extend the Warranties in any way.

3
Danger
This symbol indicates the presence of dangerous voltage within and outside the product enclosure
that may constitute a risk of electric shock, serious injury or death to persons if proper precautions
are not followed.
Caution
This symbol alerts the user to the presence of hazards that may cause minor or moderate injury to
persons, damage to property or damage to the device itself, if proper precautions are not followed.
Note
This symbol directs the user’s attention to important installation, operating and maintenance
instructions.
Installation Considerations
Installation and maintenance of the I/O Expander meter should only be performed by qualified, competent personnel
that have appropriate training and experience with high voltage and current devices. The meter must be installed in
accordance with all Local and National Electrical Codes.
DANGER
Failure to observe the following instructions may result in severe injury or death.
During normal operation of the I/O Expander meter, hazardous voltages are present on its terminal strips,
and throughout the connected potential transformer (PT), current transformer (CT), digital (status) input,
control power and external I/O circuits. PT and CT secondary circuits are capable of generating lethal
voltages and currents with their primary circuit energized. Follow standard safety precautions while per-
forming any installation or service work (i.e. removing PT fuses, shorting CT secondaries, etc).
The terminal strips on the meter base should not be user-accessible after installation.
Do not use digital output devices for primary protection functions. These include applications where the
devices perform energy limiting functions or provide protection of people from injury. Do not use the I/O
Expander in situations where failure of the devices can cause injury or death, or cause sufficient energy to
be released that can start a fire. The meter can be used for secondary protection functions.
Do not HIPOT/Dielectric test the digital (status) inputs, digital outputs, or communications terminals. Refer
to the label on the I/O Expander meter for the maximum voltage level the device can withstand.
CAUTION
Observe the following instructions, or permanent damage to the meter may occur.
The I/O Expander meter offers a range of hardware options that affect input ratings. The I/O Expander
meter’s serial number label lists all equipped options. Applying current levels
incompatible with the current inputs will permanently damage the meter. This document provides
installation instructions applicable to each hardware option.
The I/O Expander meter’s chassis ground must be properly connected to the switchgear earth ground for
the noise and surge protection circuitry to function correctly. Failure to do so will void the
warranty.
Terminal screw torque: Barrier-type (current, voltage, and relay terminal screws: 1.35 Nm (1.00 ft-lbf)
max. Captured-wire type (digital inputs/outputs, communications, power supply: 0.90 Nm
(0.66 ft.lbf) max.
FCC Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.

4
The Ringer Equivalence Number (REN) for the I/O Expander optional internal modem is 0.6. Connection to the I/O
Expander internal modem should be made via an FCC Part 68 compliant telephone cord (not supplied). The I/O
Expander cannot be used on a public coin phone service or party line services.
Network Compatibility Notice for the Internal Modem
The internal modem in meters equipped with this option is compatible with the telephone systems of most countries
in the world, with the exception of Australia and New Zealand. Use in some countries may require modification of the
internal modem’s initialization strings. If problems using the modem on your phone system occur, please contact
Power Measurement Technical Support
Standards Compliance
Limitation of Liability
Power Measurement Ltd. (“Power Measurement”) reserves the right to make changes in the device or its
specifications identified in this
document without notice. Power Measurement advises customers to obtain the
latest version of the device specifications before placing orders to verify that the information being relied upon
by the customer is current.
Regardless of whether any remedy set forth herein fails of its essential purpose, except to the extent the following
limitation is prohibited by applicable law, Power Measurement shall not, in any event or under any legal claim
or theory (whether based on contract, indemnity, warranty, tort (including negligence and strict liability) or
otherwise), be liable to the original purchaser or any other person or entity for special, indirect, incidental,
punitive, liquidated, special or consequential damages whatsoever with respect to any purchased product,
including, without limitation, business interruption, loss of use, profit or revenue, even if Power Measurement has
been advised of the possibility of such damages. To the extent that a limitation or exclusion of consequential
damages are prohibited by applicable law, then Power Measurement’s liability shall be limited to twice the
amount of the relevant purchased product. Not to limit the foregoing, a) Power Measurement shall not be liable
for any claim (other than a claim solely for the breach of one of the above Warranties that is made in accordance
with the above described procedures) made by the original purchaser, its employees, agents, or contractors for
any loss, damage, or expense incurred due to, caused by, or related to any purchased product; and b) the above
Warranties are the original purchaser's exclusive remedy and Power Measurement hereby expressly disclaims all
other warranties, express or implied, including, without limitation, warranties of non-infringement and the
implied warranties of merchantability and fitness for a particular purpose.
These limited Warranties shall not apply to any product that has been subject to alteration, accident, misuse,
abuse, neglect or failure to exactly follow Power Measurement's instructions for operation and maintenance. Any
technical assistance provided by Power Measurement's personnel or representatives in system design shall be
deemed to be a proposal and not a recommendation. The responsibility for determining the feasibility of such
proposals rests with the original purchaser and should be tested by the original purchaser. It is the original
purchaser’s responsibility to determine the suitability of any product and associated documentation for its
purposes. The original purchaser acknowledges that 100% "up" time is not realizable because of possible
hardware or software defects. The original purchaser recognizes that such defects and failures may cause
inaccuracies or malfunctions. Only the terms expressed in these limited Warranties shall apply and no
distributor, corporation or other entity, individual or employee of Power Measurement or any other entity is
authorized to amend, modify or extend the Warranties in any way.
The information contained in this document is believed to be accurate at the time of publication, however, Power
Measurement assumes no responsibility for any errors which may appear here and reserves the right to make
changes without notice.
ION, ION Enterprise, ION Setup, ION Wire, PEGASYS, ION 6200, ION 7300, ION 7330, ION 7350, ION
7500, ION 7600, ION 7700, ION 8300, ION 8400, ION 8500, COM32, COM128, Vista, VIP, Designer,
Reporter, MeterM@il, WebMeter, EtherGate, ModemGate, Xpress Card, Feature Packs and "smart energy
everywhere" are either registered trademarks or trademarks of Power Measurement. All other trademarks are
property of their respective owners.
Covered by one or more of the following patents:
U.S. Patent No's 6615147, 6611922, 6611773, 6563697, 6493644, 6397155, 6186842, 6185508,
6000034, 5995911, 5828576, 5736847, 5650936, D459259, D458863, D443541, D439535, D435471,
D432934, D429655, D429533, D427533.
CSA: Certified to CAN/
CSA C22.2 No.1010-1
Certified to
UL 3111
CE: approved

5
I/O Expander for ION 8000 Series
The I/O Expander provides an Input/Output (I/O) and serial communications
interface for ION 8000 series meters. The Expander provides convenient
locations for RS-232 and RS-485 wiring, and takes advantage of the
ION 8000 series I/O capabilities. You can install and configure I/O without
affecting your meter’s operation; a multi-conductor cable combined with low
profile connectors allows you to remove the meter without disconnecting all
attached I/O wiring.
I/O Expander Overview
Its I/O capabilities enable recording and totaling of energy pulses from
external electricity, water or gas meters. With the ION 8000 series, you can
also monitor and record the status of auxiliary contacts, breakers, relays and
transformers, as well as special equipment such as transfer switches,
uninterruptible power supplies (UPS), and battery chargers. Accurate time-
stamping of state changes helps the operator determine the sequence of trip
events.
Digital outputs allow direct control of audio/visual alarm equipment when
over/under setpoint conditions occur. The I/O Expander can also provide
analog output signals proportional to key power parameters, and data can
be easily shared via "KYZ" and demand sync pulsing to other metering or
recording equipment, or via analog or digital output signals to an existing
Digital Control System (DCS).
Standard physical connectors for RS-232 and RS-485 ports allow data
sharing with energy management systems, either directly or via modems (e.g.
fibre, radio, and telephone).

6
I/O Expander Labels
RS-232
DB-9 connector Analog only label
Digital only label
Form C
outputs
Molex
connector
Status
LED
Digital input
connections
I/O device
status LEDs
Analog
outputs
RS-485 captured-
wire connectors
Form A
digital outputs
Chassis ground
connection
Form C
outputs
Form C
outputs

7
Before You Begin
Familiarize yourself with the steps in this guide and read the safety
precautions presented on the “Installation Considerations” page.
Recommended Tools
Precision Torx T10 screwdriver
Wire cutters / stripper
Firmware Considerations
Contact Power Measurement (or go to www.pwrm.com) for your meter’s
latest firmware version.
Framework File Naming Convention
I/O Ports ION 8000 series
Firmware Version Required
Digital Inputs v203 and higher
Digital Outputs v203 and higher
Analog Outputs v205 and higher
8X00_VXX_FAC_C2A-36S_V1.X.X.X.X.fwn
Meter type: 83/84/8500
Firmware version
Factory default framework Meter form factor (36S, 35S, 9S...)
Framework version
ANSI Class 2 (IEC 1A). ANSI Class 20 (IEC 5A) if blank

8
Installation Overview

9
Step 1: Mount the I/O Expander
Review the steps in this section before installing the I/O Expander. Examine
its label to verify its service type matches your intended application.
CAUTION
Include a switch or circuit breaker in the installation in close proximity to the
unit and within easy reach of the operator. Mark it as the disconnecting
device for the unit.
Environmental Considerations
Operating Temperature -40 to 85ºC (-40 to 185ºF) internal
Storage Temperature -40 to 85ºC (-40 to 185ºF)
Humidity 5% to 95% non-condensing humidity

10
Step 2: Wire the Ground Terminal
Step 2(A): Connect Internal Power Supply (Analog Model Only)
CAUTION
This device must be installed with an adequate chassis ground
connection. Failure to properly connect the device chassis
ground voids the I/O Expander’s warranty. Do not use metal
door hinges as a ground path.
Chassis Ground Connection Wire Size
Contact to the provided chassis
ground terminal.
AWG 12 (3.31 mm2) to
AWG 14 (2.08 mm2)
CAUTION
Unit is not internally fused.
Use a 2A slowblow fuse on the L/+ terminal.
Applying power above 264 VAC/VDC damages power supply.
Power Supply Independent, fused
Nominal power range 110 - 240 Vac/Vdc
Outside power range 80 - 264 Vac/Vdc
Supply Current 0.5 A (18 W)
Otros manuales para ION 8300
2
Este manual sirve para los siguientes modelos
2
Tabla de contenidos