The maximum and minimum temperature alarms can be
disabled by setting the relative parameters "HAL" and "LAL" =
OFF.
At the same time as the signalling of the configured alarm
(buzzer and/or output), the instrument signals the alarm by
turning on the led light AL, switching off the LED OK, turning on
the led - in case of minimum alarm or the led + for maximum
alarm, and visualises on the display:
- Alternately HI and the set variable in parameter “diSP” for
maximum alarm
- Alternately LO and the set variable in parameter “diSP” for the
minimum alarm
4.9.2 - EXTERNAL ALARM
The instrument can signal an external alarm by activating the
digital input with the function programmed as “diF” = 4 or 9 (see
par. 4.10).
At the same time as the signalling of the configured alarm
(buzzer and/or output), the instrument signals the alarm by
turning on the led AL, turning off the led OK and visualising AL
and the variable set in parameter “diSP” alternately on the
display.
4.9.3 - OPEN DOOR ALARM
The instrument can signal an open door alarm by activating the
digital input with the function programmed as “din” = 5 or 6 (see
par. 4.10).
When the digital input is activated and after the delay
programmed in parameter “oAd”, the instrument signals the
alarm via the activation of the configured devices (buzzer
and/or output), the turning on of the led AL, the turning off of
the led OK and AP and the variable set in parameter “diSP” are
visualised alternately on the display.
4.9.4 - ALARM MEMORY
The instrument offers the possibility of arranging the alarm
memory function via the parameter “tAL”.
If "tAL" = no, the instrument cancels the alarm signal when the
alarm status ends, if instead it is programmed as "yES" , the
led AL flashes even when the alarm status has ended to
indicate that there has been an alarm.
If the memorised alarm is for temperature, it also keeps the led
- flashing to show a minimum alarm and + to show a maximum
alarm.
To cancel the alarm memory signal, press any key.
It must be remembered that if an output function is desired (or
the buzzer) with an alarm memory (=ALL or =-ALL) it is
necessary to set the parameter “tAL” = yES.
4.10 - DIGITAL INPUT
All the parameters concerning the digital input functions are
contained in the group “]din”.
The digital input present on the instrument accepts contacts
free of voltage, the function carried out is defined by the
parameter “diF” and the action can be delayed for the time set
in parameter “did”.
The parameter “diF” can be configured for the following
functions:
=0- Digital input not active
= 1 - defrosting commencement command with contact
normally open: on closing the input (and after the “did” time) a
defrosting cycle is activated.
= 2 - defrosting end command with contact normally open: on
closing the input (and after the “did” time) a defrosting cycle is
ended if in progress or defrosting is inhibited.
= 3 - continuous cycle activation command with contact
normally open: on closing the input (and after the “did” time) a
continuous cycle is started up as described in the paragraph on
the continuous cycle function.
= 4 - External alarm signal with contact normally open: on
closing the input (and after the “did” time) the alarm is activated
and the instrument visualises AL and the variable set in
parameter “diSP” alternately on the display.
= 5 -Cell door opening with fan block with contact normally
open: on closing the input (and after the “did” time) the fans are
stopped and the instrument visualises AP and the variable set
in parameter “diSP” alternately on the display. With this
function mode, the action of the digital input also activates the
time that can be set in parameter "oAd" after which the alarm is
activated to signal that the door has been left open.
= 6 - Cell door opening with compressor and fan block with
contact normally open: similar to “diF” = 5 but with fan and
compressor block.
= 7 - Remote control of auxiliary output AUX with contact
normally open: on closing the input (and after the “did” time)
the auxiliary output is activated as described in the "FOA" = 2
function mode of the auxiliary output.
= 8 - Selecting the active set point with contact normally open:
on closing the input (and after the “did” time) the temperature
regulation set point “SP 2” is activated. When instead the input
is open the set point “SP 1” is active (see selecting active set
point)
= 9 - Signalling of external alarm with disablement of all the
control outputs with contact normally open: on closing the input
(and after the “did” time) all the control outputs are disabled,
the alarm is activated and the instrument visualises AL and the
variable set in parameter “diSP” alternately on the display.
= 10 - Switching on/switching off (Stand-by) of instrument with
contact normally open: on closing the input (and after the “did”
time) the instrument is switched on while it is placed in Stand-
by when opened.
= -1 - defrosting commencement command with contact
normally closed : similar to “diF”=1 but with function logic
reversed.
= -2 - defrosting end command with contact normally closed :
similar to “diF”=2 but with function logic reversed.
= -3 - continuous cycle start-up command with contact normally
closed : similar to “diF”=3 but with function logic reversed.