It is essential that the installation of the system is carried out in the order given
below to ensure the correct operation of the system.
This guide, when completed, should be posted to Medem UK in order that the
warranty period can be activated.
Site Name
Installing ompany
Engineers Name
Date ompleted
Tick as each step is completed
1: All wiring checked tight and connected
as per the installation instructions.
2: Each detector has an individual number
from adjusting the rotary switch before the
“learn” button was pressed.
3: All detectors have a solid green LED
Illuminated when not in alarm.
4: Each detector has been recognised by
the panel.
5: On applying test gas to the
detectors the LED turns red
and the panel alarms and closes the
gas valve.
With the panel fitted to the wall the following steps should be
followed.
1. Connect BMS, beacons, sounders etc to the
relay outputs.
2. Connect any additional EM stop buttons and
thermal links in series to the terminals marked
“EM STOP”.
3. Each detector has a rotary address switch and
each switch should be set to a different number
starting with “1”. Then connect the gas detectors
to terminals marked “detectors” on the panel.
Detectors can be wired “Daisy chain”.
4. Connect the 3 amp fused spur 240 volt supply to
marked terminals and switch on.
5. Press the “learn dets button” this is on the main
circuit board in the top right corner. Pressing this
once allows the panel to learn how many and
which type of detectors are fitted.
6. Once power is connected to the panel the
detectors will flash the green LED’s for 90
seconds after which the LED’s will be on
continuously.
Return one copy of this sheet to the address below:
Manufactured by:
Medem (UK) Limited
Project House, 19 Dallimore Road, Roundthorn Industrial Estate,
Manchester, M23 9NX
Tel: +44 (0) 6 233 0600
Fax:+44 (0) 6 233 060
Please do not hesitate to call for advice on the
following numbers:
0161 233 0600 office hours
Detector type Methane CO LPG
Number fitted