6
5.2 Output protection
The display panel will show failure status using red LED indicators when inverter
is faced with abnormal operating conditions. This lets the user know there could
be problems with their setup.
(1) OTP: When the internal temperature is higher than the limit value, OTP will
activate and automatically shutdown the unit. Users should wait for at least
30 minutes before restarting the unit.
is too low or too high, the unit will turn OFF and should be restarted again.
(2) AC output abnormal protection: When the AC output voltage of the inverter
(3) AC output short circuit protection: When a short circuit situation occurs at
(4) Battery voltage abnormal protection: When the battery voltage is too high
(5) OLP: When the output is overloaded between 210~230W (TS-200) / 420~460W
the output side of the inverter or the load increase greatly in a short period of
time, the unit will turn OFF and should be restarted again.
or too low, this protection will be activated. Inverter will auto recover after
the battery voltage goes back to a safe level and the user do not need to
restart it.
(TS-400), the inverter can still continuously provide power for 3 minutes.
After that, if the overload condition is not removed, overload protection will
activate. When the load is higher than 400W (TS-200) / 800W (TS-400), the
overload protection will be activated instantly. For these overload protections,
once activated, the unit must reset to recover.
Table 6-1 Suggestion for wire selection
6. Installation & Wiring
(A)Wiring for Batteries: Wire connections should be as short as possible and less
than 1.5 meter is highly recommended. Make sure that suitable wires are chosen
based on the current rating. Too small of a cross-section will result in overheating
and could induce fire hazard.
Please choose suitable batteries that are compatible with the rated input
DC voltage of TS-200/400 (refer to spec). If the input DC voltage is too
low (ex. using 12Vdc battery bank for 24Vdc input models), TS-200/400
will not started up. If the input DC voltage is too high (ex. using 48Vdc
battery bank for 24Vdc input models), TS-200/400 could get damaged!
10A ~ 13A
13A ~ 16A
16A ~ 25A
25A ~ 32A
32A ~ 40A
40A ~ 63A
1.25
1.5
2.5
4
6
10
AWG
16
14
12
10
8
6
Inverter model
TS-200
148/248
124/224
112/212
TS-400
148/248
124/224
112/212
Cross-section of
Lead (mm )
2
Rated Current of
Equipment (Amp)
WARNING: