5
EN
1.4 Think of your safety
If you smell gas, it is expressly prohibited
– To ignite an appliance
– To touch electrical switches, or to telephone from the area in question
Take the following actions
– Switch off the gas and electricity
– Activate the operational emergency plan
Evacuate everyone from the building
2.0 Positioning the appliance
After unpacking, check the unit for damage. Check the accuracy of the type/model, the voltage
(230V) and the gas type. When determining the suspension height, remember to keep a sufcient
distance from any crane gantries. If necessary, shield any ammable goods. Place the appliance and
any accessories on a sufciently solid structure, taking into account the minimum required free
space. Wall-mounting support frames are available to order. [2A][2B]
INFRA HE
The radiant heater can be suspended with galvanised chains with links with a minimum diameter
of 4 mm and with 10 mm cross bars with good rust protection. In order to suspend the radiant
heaters in the right way, it is advisable to use gripple cable suspension sets with which the radiant
heaters can be readily adjusted to the correct height.The radiant heaters can be suspended at a
maximum inclination of 30°. If the radiant heaters are suspended inclined, the burner is installed
horizontally TO THE LOWESTTUBE on the right, as seen from the heated area.The radiant heater
must be mounted with the ue sloping with a drop of approximately 25 mm [3].
2.1 Mounting instructions
See enclosed installation instructions.
2.2 Positioning the ue and combustion air supply
The device only has the CE approval in combination with its ue gas system. The ue gas system
includes: single ue set vertical or horizontal, extension pipes and elbows. The table below i\ndicates
which parts can be used per appliance type. The ue gas system must be installed according to the
instructions attached.
The extension pipes must be laid in parallel. In exceptional cases, for example with thick roofs or
walls, the roof or wall terminal may be extended concentrically by a maximum of 1 meter.
If a ue gas set is to be installed sideways to or through a ammable oor or wall, then there must
be a minimum air gap of 25 mm around the ue gas sets. This to prevent re and / or scorch hazard.
The mentioned ue gas products are made of stainless steel or aluminium, or have an inner pipe of
the same material. This has been chosen because of the maximum ue gas temperature.
The combustion air inlet pipes may consist of the same materials as specied for the ue gas
discharge, but may also consist of materials mentioned in the table on pages 7-9. Other materials are
not allowed.
Device type Nominal diameter
35-9
50-12
100 mm