Marathon Electric DVR 2000E+ Manual de usuario

DVR®2000E+
DIGITAL VOLTAGE REGULATOR
INSTALLATION, OPERATION AND
MAINTENANCE MANUAL


3
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
CONTENTS
SECTION 1 – OVERVIEW
General ................................................................................................................................. 5
Features ................................................................................................................................ 5
Protections ............................................................................................................................ 6
Warranty................................................................................................................................ 6
SECTION 2 – SPECIFICATIONS
Operating Power................................................................................................................... 7
Generator Voltage Sensing................................................................................................... 7
Generator Current Sensing................................................................................................... 7
Contact Inputs ...................................................................................................................... 7
Fault Contact Output............................................................................................................. 7
Field Output .......................................................................................................................... 7
AVR1 and 3 Operating Modes .............................................................................................. 8
FCR Operating Mode............................................................................................................ 8
Parallel Compensation.......................................................................................................... 8
Serial Communication Port ................................................................................................... 8
CAN Communication Port..................................................................................................... 8
Over Excitation Protection..................................................................................................... 8
Field Current Limit Protection................................................................................................ 8
Field Instantaneous Over Current Protection........................................................................ 8
Generator Over Voltage Protection....................................................................................... 9
Generator Under Voltage Protection..................................................................................... 9
Soft-Start Function ................................................................................................................ 9
Auxiliary Input ....................................................................................................................... 9
Metering.............................................................................................................................. 10
Environmental ..................................................................................................................... 11
Environmental Test.............................................................................................................. 11
Electromagnetic Compatibility............................................................................................ 11
Electromagnetic Compatibility Tests................................................................................... 11
Mechanical Tests ................................................................................................................ 11
Physical............................................................................................................................... 11
Mating Connectors ............................................................................................................. 11
SECTION 3 – FEATURES AND PROTECTION
Introduction......................................................................................................................... 12
DVR®2000E+ Function Blocks ............................................................................................ 12
DVR®2000E+ Operating Features ...................................................................................... 15
Regulation Modes.................................................................................................... 15
Auxiliary Input .......................................................................................................... 15
Load Sharing ........................................................................................................... 16
Generator Soft Start ................................................................................................. 16
DVR®2000E + Protection Features...................................................................................... 17
Field Over Excitation Shutdown............................................................................... 17
Generator Over Voltage Shutdown.......................................................................... 17
Generator Under Voltage Shutdown........................................................................ 18
Generator Voltage Imbalance Shutdown................................................................. 18
Loss of Generator Sensing Shutdown ..................................................................... 18
Field Current Limiting Shutdown.............................................................................. 19

4
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
CONTENTS cont.
Instantaneous Field Over Current Shutdown........................................................... 19
Regulator Over Temperature Shutdown .................................................................. 19
Generator Under Frequency Alarm ......................................................................... 20
Generator Reverse Power Flow Alarm..................................................................... 21
Loss of CAN Communication Alarm ........................................................................ 21
SECTION 4 – INSTALLATION
General ............................................................................................................................... 22
Mounting ............................................................................................................................. 22
Connections........................................................................................................................ 25
Preliminary Set-up on Generator ........................................................................................ 35
Preliminary Set-up on Bench .............................................................................................. 36
SECTION 5 – HUMAN-MACHINE INTERFACE
General ............................................................................................................................... 37
Front Panel Display............................................................................................................. 38
Making Settings Changes................................................................................................... 39
SECTION 6 – GRAPHICAL USER INTERFACE
Header Buttons................................................................................................................... 40
Administration.......................................................................................................... 40
Login........................................................................................................................ 40
Load Factory Settings.............................................................................................. 40
Save to EEPROM ..................................................................................................... 40
Load Config ............................................................................................................. 40
Save Config ............................................................................................................. 41
Connect ................................................................................................................... 41
Parameter Screen Selection Buttons .................................................................................. 41
Metering Tab............................................................................................................ 41
Configuration Tab .................................................................................................... 42
Operating Modes Sub Panel ................................................................................... 42
Set Points Sub Panel ............................................................................................... 43
Protection Settings Sub Panel ................................................................................. 44
CAN Bus Configuration Sub Panel .......................................................................... 45
Identification Tab ..................................................................................................... 45
SECTION 7 – MAINTENANCE AND TROUBELSHOOTING
Preventative Maintenance................................................................................................... 46
Troubleshooting .................................................................................................................. 46
SECTION 8 – CAN BUS INTERFACE
Message Format ................................................................................................................. 53
Outbound Messages From DVR®2000E+ ......................................................................... 55
Inbound Messages From ECU1 or ECU2 or ECU3 ............................................................ 70
APPENDIX A
Alarm Codes ....................................................................................................................... 74
Fault Codes......................................................................................................................... 74
APPENDIX B
Connector Pin-out Figures and Tables................................................................................ 75
APPENDIX C
Quick Start Programming Guide......................................................................................... 78

5
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
SECTION 1 - OVERVIEW
SAFTY AND PRECAUTIONS
When the DVR®2000E+ Voltage regulator is mounted on the generator at the factory a molded cover is
provided. This cover prevents exposure and unintentional contact. This cover must be installed whenever the voltage
regulator is energized.
:Use caution when working around the component side of the DVR®2000E+. Voltage levels
may be present at the exposed components and contacts when the unit is energized.
GENERAL
The DVR®2000E+ is a microprocessor-based control device that regulates the output voltage of a brushless, ac
generator by controlling the current into the generator exciter field. Input power to the DVR®2000E+ is derived
from a single phase, multi-pole, high-frequency, permanent magnet generator (PMG).
The DVR®2000E+ is supplied in an encapsulated package designed for behind-the-panel mounting. The
DVR®2000E+ is held in place by thread-forming screws that thread into its plastic shell. The front panel display
annunciates regulator status and system conditions. DVR®2000E+ connections are made through four types of
connectors:
•Tenquarter-inch,quick-connectterminalsforgeneratorconnections
•Two12-pinDeutsch(DTCstyle)connectorsforcurrenttransformer(CT)andsystem
interface connections
•One3-pinAmp/TycoMiniMate-N-LokreceptacleforCANbusinterface.
•One9-pinDB-9typeconnectorforcommunicationbetweentheDVR®2000E+ and a
Windows®compatible PC.
FEATURES
DVR®2000E+ has the following features:
•Threeregulationmodes:singlephaseautomaticvoltageregulation(AVR1),threephase
automatic voltage regulation (AVR3) and field current regulation (FCR)
•Presetstabilitysettings
•AdjustablesoftstartinAVR1orAVR3regulationmodes
•Underfrequency(volts/hertz)regulation
•Three-phaseorsingle-phasegeneratorvoltage(RMS)sensing
•Three-phaseorsingle-phasegeneratorcurrent(RMS)sensing
•Truethree-phasepowermetering
•Fieldcurrentsensing
•Fieldvoltagemonitoring
•Contactinputsforsysteminterfacecapability

6
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
•Contactoutputforfaultindication
•Generatorparallelingwithreactivedroopcompensationandreactivedifferentialcompensation
•Front-panelhuman-machineinterface(HMI)forstatusandconguration
•MODBUSprotocolviaRS232forexternalcommunication
•DVR®2000E+ Windows®based software for configuration and monitoring
•ControllerAreaNetwork(CAN)interfacewithCAN2.0BJ1939protocolformeteringandcontrol
•“Poweron”LEDindicator
•Congurableauxiliaryinputformeteringandcontrol
PROTECTIONS
DVR®2000E+ has the following protection features:
•FieldOverExcitationShutdown
•GeneratorOverVoltageShutdown
•GeneratorUnderVoltageShutdown
•GeneratorVoltageImbalanceShutdown
•LossofGeneratorSensingShutdown
•FieldCurrentLimitingShutdown
•InstantaneousFieldOverCurrentShutdown
•RegulatorOverTemperatureShutdown
•GeneratorUnderFrequencyAlarm
•GeneratorReversePowerFlowAlarm
•LossofCANCommunicationAlarm
WARRANTY
When supplied on a generator, the DVR®2000E+ carries the same warranty as the generator. (a) Marathon
warrants Standby Duty Generators manufactured by or for it to be free from defects in materials and workmanship
and to conform to Marathon’s written specifications for a period of 24 months from date of startup or 30 months
from date of shipment or 1000 hours in use, whichever period shall expire first. (b) Marathon warrants Continuous
Duty Generators manufactured by or for it to be free from defects in materials and workmanship and to conform
to Marathon’s written specifications for a period of 12 months from data of startup or 18 months from date of
shipment, whichever period shall expire first.
When supplied as a separate component, Marathon warrants the DVR®2000E+ to be free from defects in
materials and workmanship and to conform to Marathon’s written specifications for a period of 12 months from
date of shipment.

7
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
SECTION 2 – SPECIFICATIONS
Operating Power
Type: 1-phase, ungrounded PMG
Range: 180 to 240 Vac, 250 to 300 Hz
Burden: 350 VA
FuseType: Timedelay250V/4.0A
Terminals: 3, 4
Generator Voltage Sensing
Type: 1-phase/3-phase
Range: 100to600Vac,50/60Hz
Burden: <1 VA per phase
Terminals: E1, E2, E3
Generator Current Sensing
Type: 1-phase(BØ)/3-phase
Rating: 5Aacmaximumcontinuous50/60Hz
Input Impedance: <10 mΩ
Terminals: CT1, CT2 for 1-phase (BØ)
J2-1,J2-12for3-phase(AØ)
J2-2,J2-11for3-phase(BØ)
J2-3,J2-10for3-phase(CØ)
Contact Inputs
Type: Dry Contact
Input Pull-Up Voltage: 3.3 Vdc
Terminals: DROOP_OFF: J1-10,J1-4
UP: J1-2,J1-4
DOWN: J1-3,J1-4
EXCITATION_OFF: J1-11,J1-4
Fault Contact Output
Type: Form A
Rated Load: 3 A continuous
Break: 3Aac/0.1Adc
OperatingVoltage: 240Vac/250Vdcmaximum
Terminals: J1-6,J1-7
Field Output
Continuous Rating: 75 Vdc, 3.0 Adc
10 Second Forcing Rating
200 Vac Power Input: 150 Vdc, 7.5 Adc
Field Resistance: 18 to 35 *
Terminals: F+, F-

8
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
AVR1 and AVR3 Operating Modes
Range: 100.0 to 600.0 Vac
Voltage Regulation: ±0.25 % over load range at rated power factor
and constant generator frequency.
TemperatureDrift: ±0.0125%/degreeC
Underfrequency(V/Hz)
Slope: 1.00 to 3.00 PU
Knee: 40.0 to 70.0 Hz
FCR Operating Mode
Range: 0.000 to 3.000 Adc
Current Regulation: ±1.0 % over 18 to 35 Ohms of exciter resistance
TemperatureDrift: ±0.0125%/degreeC
Parallel Compensation
Modes: Reactive Droop and
Reactive Differential (cross-current)
Droop
Range: 0.0 to 10.0 %
Serial Communication Port
Interface: Full Duplex RS-232
Connector: DB-9 connector on rear panel
Baud: 4800
Data Bits: 8
Parity: None
Stop Bit: 2
Handshaking: None
CAN Communication Port
Connector: J3
Protocol: SAEJ1939
DataRate: 250kbits/sec
Over Excitation Protection
Threshold: 0.500 to 4.000 Adc
Timer: 1.0 to 15.0 seconds
Field Current Limit Protection
Threshold: 0.500 to 7.500 Adc
Timer: 1.0 to 10.0 seconds
Field Instantaneous Over Current Protection
Threshold: 11 Adc

9
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
Generator Over Voltage Protection
Threshold: 5.0 to 20.0 %
Timer: 0.75 seconds
Generator Under Voltage Protection
Threshold: 5.0 to 50.0 %
Timer: 1.0 to 15.0 seconds
Soft-Start Function
Range: 2 to 120 seconds
Auxiliary Input
Auxiliary – Controller (AVR3 or AVR1 regulation)
Voltage Range: -3 Vdc to +3 Vdc
Set point Range: -30 % to +30 % shift
Burden: 2260 *
Terminals: J1-1(+),J1-12(-)
Auxiliary – Controller (FCR regulation)
Voltage Range: 0 Vdc to +3 Vdc
Increment: 1 mA per 1mV
Burden: 2260 *
Terminal: J1-1(+),J1-12(-)
Auxiliary – Meter (Voltage input)
Voltage Range: -5 Vdc to 5 Vdc
Scale Factor: User-defined
Burden: 2260 *
Terminal: J1-1(+),J1-12(-)
Auxiliary – Meter (Current input)
Current Range: 4 mA to 20 mA
Scale Factor: User-defined
Burden: 250 *
Terminal: J1-1(+),J1-12(-)
Jumper: J1-5toJ1-8

10
Marathon Electric (a division of RBC Manufacturing Corp.) reserves the right to change specications and this manual without notice.
Revised 06/2011
Metering
Accuracyofallmeteringvaluesassumes25°C,50/60Hzandlessthan20%THD.
Regulator-side Metering
Generator Voltage
Range: 10 Vac to 600 Vac
Accuracy: 0.5 %
Generator Current
Range: 0.1 to 5.000 Aac (5 Aac CTs)
Accuracy: 0.5 %
Power (Apparent, Real and Reactive)
Range: 0 to 5200 VA and W
0to4160VARleading/lagging
Accuracy: 3.0 %
Power Factor
Range: 0.6to1.0leading/lagging
Accuracy: 0.02
Frequency
Range: 40 to 75 Hz
Accuracy: 0.2 Hz
Field Voltage
Range: 0 to 200 Vdc
Accuracy: 5.0 %
Field Current
Range: 0 to 8.0 Adc
Accuracy: 0.5 %
Generator-side (Scaled) Metering
Generator Voltage
Range: 10 V to 15 kV
Accuracy: 0.5 %
Generator Current
Range: 0.1 to 5,000 Aac (5 Aac CTs)
Accuracy: 0.5 %
Power (Apparent, Real and Reactive)
Range: 0 to 10 MVA and MW
0to8MVARleading/lagging
Accuracy: 3.0 %