Mandik FDMB Manual de usuario


2
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers)
FDMB. It is valid for production, designing, ordering, delivery, assembly and operation.
1. Description.........................................................................................................................
3
2. Design................................................................................................................................
4
3. Communication and control devices……….........................................................................
16
4. Dimensions, weights and effective area..............................................................................
19
5. Placement and Assembly....................................................................................................
27
6. Statement of installations....................................................................................................
29
7. Shaft walls...............….….......................................................….……….....…....................
62
8. Installation frames.……..............................................................................…................….
64
9. Suspension system……….............................................................................................….
72
10. Pressure loss....................................................................................................................
78
11. Coefficient of local pressure loss.......................................................................................
79
12. Noise data.........................................................................................................................
80
13. Material.............................................................................................................................
82
14. Inspection, testing.............................................................................................................
83
15. Logistic terms....................................................................................................................
82
16. Assembly..........................................................................................................................
83
17. Entry into service and revisions.........................................................................................
84
18. Spare parts.......................................................................................................................
85
19. Restore function of actuating mechanism after fuses initiation...........................................
85
20. Ordering key.................................................................................................................….
86
21. Data label.....................................................................................................................….
87

3
Fire dampers are shutters in ducts of air-conditioning devices that prevent spreading the fire and
combustion products from one fire segment to the other one by means of closing the duct in the
points of fire separating constructions.
Dampers blade automatically closes air duct using a shutting spring or an actuating mechanism
back spring. Closing spring is released either by pushing of the button or by thermal fuse.
The back spring of the actuating mechanism is started when the thermoelectrical starting
mechanism BAT is activated, when a reset button on BAT is pushed or when a power supply of
the actuating mechanism is stopped.
The damper is sealed with a silicon packing against smoke penetration after closing the blade. At
the same time, the damper blade is bedded in a material which enlarges its capacity and air
proofs the air duct.
Dampers have two inspection holes.
Damper characteristics
• CE certified acc. to EN 15650
• Tested in accordance with EN 1366-2
• Classified acc. to EN 13501-3+A1
• Fire resistance EIS 120 - 500 Pa, EIS 120, EIS 90
• Leakage acc. to EN 1751 - External Casing leakage: A<160 or B<160 class B
A≥160 and B≥160 class C
- Internal leakage: class 2
• Cycling test in class C 10000 acc. to EN 15650
• Corrosion resistant acc. to EN 15650
• ES Certificate of conformity No. 1391-CPR-2020/0136
• Declaration of Performance No. PM/FDMB/01/22/5
• Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b
Working conditions
Right damper function is secured under the following conditions:
a) Maximum air circulation speed: 12 m/s
Maximum pressure difference: 1200 Pa
b) The air circulation in the whole damper section must be secured as steady on whole
surface.
Operation of the dampers does not depend on the direction of air circulation. The dampers can
be located in an arbitrary position.
Dampers are suitable for systems without abrasive, chemical and adhesive particles.
Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.
Temperature in the place of installation is permitted to range from -30°C to +50°C.

4
Design with mechanical control
Design with mechanical control with a thermal protective fuse which actuates the shutting device,
after the nominal start temperature 72°C has been reached. Automatic initiation of the shutting
device is not activated if the temperature does not exceed 70°C. In case that other start
temperatures are required, thermal fuses with nominal start temperature +104°C or +147°C can
be supplied (this requirement must be specified in the order).
Mechanisms are produced in four designs to ,
difference is only in size of inner spring, which closes
the fire damper. For the size of fire dampers is always
assigned the size of mechanism - It is not
recommended to use different size of mechanism,
than given by the manufacturer, otherwise, there is a
risk of fire damper destruction.
Design .01 with mechanical control can be complemented with a limit switch signalling of the
damper blade position "CLOSED". Cable is connected directly to limit switch.
Limit switch
“CLOSED”
Design .01 with mechanical control can be complemented with a terminal switches signaling of
the damper blade position "CLOSED" and "OPEN". Limit switches are connected via damper
casing, cables are connected directly to limit switches.
Limit switch
“CLOSED” Limit switch
“OPEN”

5
1(COM) - black wire
2(NC) - gray wire
4(NO) - blue wire
This limit switch is possible to connect in following two versions:
a) if the arm is moving … connect wire 1+2
b) if the arm is moving … connect wire 1+4
AC 230V / 5A
IP 67
-25°C … +120°C
1 Damper
2 Mounting plate
3 Sealing cover
4 Seal plates
5
Mounting plate cover
6 Thermal fuse
7 Mechanics
8
Actuator
9 Temperature sensor
10 Sensor sticker

6
Design with actuating mechanism
12 S3
S1 S2 S5S4 S6
NL1
<5° <80°
BAT
Tf Tf LED
The damper are equipped by Belimo actuators with spring return and thermoelectric activation
device of BFL, BFN or BF depending on the damper size (furher mentioned as „actuators“).
After being connected to power supply AC/DC 24V or 230V, the actuating mechanism displaces
the damper blade into operation position "OPEN" and at the same time it pre-stretches its back
spring. When the actuating mechanism is under voltage, the damper blade is in the position
"OPEN" and the back spring is pre-stretched. Time needed for full opening of the flap blade from
the position "CLOSED" to the position "OPEN" is maximum 120 sec. If the actuating power supply
is cut off (due to loss of supply voltage, or pushing the reset button on the thermoelectrical starting
mechanism BAT), the back spring displaces the damper blade into the breakdown position
"CLOSED". The time of displacing the blade from the position "OPEN" to the position "CLOSED"
takes maximum 20 sec. In case that the power supply is restored again (the blade can be in any
position), the actuating mechanism starts to re-displace the damper blade into the position "OPEN".
A thermoelectrical starting mechanism BAT, which contains two thermal fuses Tf1 and Tf2, is a
part of the actuating mechanism. These fuses are activated when temperature +72°C has been
exceeded (the fuse Tf1 when the temperature around the damper and the fuses Tf2 when the
temperature inside the air-conditioning piping has been exceeded). After the thermal fuse Tf1 or
Tf2 has been activated, the power supply is permanently and irreversibly cut off and the actuating
mechanism, by means of the pre-stretched spring, displaces the damper blade into the
breakdown position "CLOSED".
Signalisation of damper blade position "OPEN" a "CLOSE" is provided by two limit switches.
BAT
Actuating
mechanism

7
Nominal voltage AC 230 V 50/60 Hz AC 24 V 50/60 Hz
DC 24 V
Power consumption - motoring
- holding
3,5/5 W
1,1/2,1 W
2,5/4 W
0,8/1,4 W
Dimensioning 6,5/10 VA (Imax 4 A @ 5 ms) 4/6 VA (Imax 8,3 A @ 5 ms)
Protection class II III
Degree of protection IP 54
Running time - motor
- spring return
<60 s
~ 20 s
Ambient temperature
- normal duty
- safety duty
- non-operating temperature
- 30°C … +55°C
The safe position will be attained up to max. +75°C
- 40°C … +55°C
Connecting - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm² (BFL/BFN 24-T-ST) with 3-pin plug-in connectors
cable 1 m, 6 x 0,75 mm² (BFL/BFN 24-T-ST) with 6-pin plug-in connectors
Thermal trips duct outside temperature +72°C
duct inside temperature +72°C
12 S3
S1 S2 S5S4 S6
NL1
~
- +
<5° <80°
BAT
Tf Tf LED
12 S3
S1 S2 S5S4 S6
<5° <80°
BAT
Tf Tf LED
~
- +

8
Design .41 or .51 with actuating mechanism can be complemented with smoke detector ORS 142
K. The voltage can be AC 230 V or 24 V DC. Design with voltage AC 230 V is equpped with
Communication and supply device BKN 230-24-MOD and with actuating mechanism BF 24-TN
(BFL 24-T, BFN 24-T).
The smoke detector is activated when smoke spreads in air duct system. Deactivation of smoke
detector is provided by interruption of supply voltage for min. 2s.
Signalisation of damper blade position "OPEN" a "CLOSE" is provided by two limit switches.
The smoke detector sensor is not part of the fire damper in the case of dampers from A<160 or
B<160. The smoke sensor is supplied separately.
Operating voltage 18 … 28 V DC
Residual ripple ≤ 200 mV
Power Consumption Socket
(without actuating mechanism) max. 22 mA
Degree of protection IP 42
Ambient temperature -20°C … +75°C
Aditional temperature senzor +70°C
Connection - net
- motor
- communication and supply device BKN
Cabel 1m, connected to terminals 1, 2 and 4
Actuator connected on the terminals 2 and 5
Cabel 1m, connected to terminals 1, 2, 4 and 5
Nominal voltage AC 24 V 50/60 Hz
DC 24 V
AC 230 V 50/60 Hz
Power consumption - motoring
- holding
7 W
2 W
8 W
3 W
Dimensioning 10 VA (Imax 8,3 A @ 5 ms) 12,5 VA (Imax 500 mA @ 5 ms)
Protection class III II
Degree of protection IP 54
Running time - motor
- spring return
120 sec
~ 16 sec
Ambient Temperature
- normal duty
- safety duty
- non-operating temperature
-30°C … +50°C
The safe position will be attained up to max. 75°C
-40°C … +50°C
Connecting - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm²
cable 1 m, 6 x 0,75 mm²
(BF 24-T-ST) with plug-in connectors
Thermal trips Tf1: duct outside temperature Duct +72°C
Tf2/Tf3: duct intside temperature Duct +72°C

9
2
3
4
5
6
1
relay
contact
relay
contact
RS-Bus communication
1
2
3
4
5
6
7
1
2S2S1 S3 S5S4 S6
2
3
4
5
6
1
BAT
Tf Tf LED
1
2S2S1 S3 S5S4 S6
24 V DC
2
3
4
5
6
1
BAT
Tf Tf LED

10
Nominal voltage AC 230 V 50/60Hz
Power consumption 3,5 W (operating position)
Dimensioning 11 VA (including actuating mechanism with spring return)
Protection Class II
Degree of protection IP 40
Ambient temperature
Non-operating temperature
-20°C … +50°C
-40°C … +80°C
Connection - net
- motor
- terminal board
cable 0,9 m with EURO plug type 26
6-pole connector, 3-pole connector
screw terminals for cable 2x1,5 mm²
Design with the communication and supply device BKN 230-24 and the actuating mechanism
BF 24-TN-ST (BFL 24-T, BFN 24-T). It simplifies electrical wiring and interconnection of fire flap
valves. It facilitates on site check and enables central control and checks of fire damper by means
of a simple 2-conductor wiring.
BKN 230-24 functions as a decentralized network device for supplying the actuating mechanism
BF 24-TN-ST (BFL 24-T, BFN 24-T) with a spring back drive on one hand and on the other hand
it transmits the signal informing about the flap valve position OPERATION and FAILURE through
2-conductor wiring to the central. Control command SWITCHED ON - SWITCHED OFF from the
central through BKN 230-24 goes through the same wiring to the actuating mechanism.
To simplify the connection, the actuating mechanism BF 24-TN-ST (BFL 24-T, BFN 24-T) is
equipped with connecting plugs that are inserted directly to BKN 230-24. BKN 230-24 is supplied
with a conductor and an EURO plug to be connected to the 230V mains. 2- conductor wiring is
connected to BKN 230-24 by means of terminals 6 and 7. If the drive is supposed to be controlled
without any signal from the central, it can be switched on by means of a bridge between the
terminals 3 and 4. A green LED pilot light on BKN 230-24 is on when voltage is present in the
drive (AC 24V).
If the button on BAT is switched on or if the power supply (e.g. by a signal from ELECTRICAL
FIRE SIGNALISATION ) is disconnected, the damper position will be "FAILURE".
BAT
BKN
Actuating
mechanism
Otros manuales para FDMB
5
Tabla de contenidos
Otros manuales de Compuerta cortafuegos y de humo de Mandik

Mandik
Mandik FDMB Manual de usuario

Mandik
Mandik SEDM Guía

Mandik
Mandik FDMC Series Manual de usuario

Mandik
Mandik CFDM Manual de usuario

Mandik
Mandik FDMS Series Manual de usuario

Mandik
Mandik FDMR Manual

Mandik
Mandik SEDS Manual de usuario

Mandik
Mandik RKM Manual de usuario

Mandik
Mandik SEDS-R Manual de usuario

Mandik
Mandik FDMQ 120 Manual