3. Open the hot water supply to the mixing valve. The
thermometer should return to the set temperature.
4. Shut off the cold water supply to the mixing valve. The
ow of water should shut down rapidly.
5. Open the cold water supply. The thermometer should
return to the set temperature.
The thermometer (T1) should be checked at least every six
months.
Operating Principle
The Model 911E Emergency Shower and Eye Wash Mixing
Valve is made of a thermostat housed in a single lead
free brass casting. The thermostatic cartridge responds to
temperature changes in the hot and cold water supplies.
The Model 911E Valve requires testing and maintenance on
a regular basis. In the event the element fails, the valve will
provide full cold water ow.
Installation
After installing the mixing valve, be sure to ush the system
thoroughly. Lawler recommends isolation and check valves
for proper maintenance.
Testing the Mixing Valve
The mixing valve and the emergency xtures it serves
should be tested weekly for proper operation.
Valve temperature test procedure is as follows:
1. Activate eye wash xture to observe and record
the temperature of the dial thermometer (T1). If the
temperature of the thermometer is not correct, readjust
the mixing valve according to the section “Setting the
Mixing Valve”
2. Observe the ow from the emergency xtures to ensure
an adequate ow of water.
In addition to testing for proper temperature, the cold water
by-pass and hot water shut down features of the mixing
valve should be tested weekly.
The test procedure is as follows:
1. Test valve temperature as described in Step 1 and Step
2 above.
2. Shut off the hot water supply to the mixing valve.
Observe the outlet ow from the emergency xtures
to ensure an adequate ow of cold water. A slight drop
in ow may occur after shutting down the hot water
supply to the mixing valve; however, the drop should be
minimal and for a short duration.
Replacing a Thermostat Cartridge
The thermostat replacement procedure is as follows:
1. Shut off the hot water supply and cold water supply to
the mixing valve.
2. Unscrew valve V1 and install a new thermostat
cartridge assembly.
3. Open the hot water supply and the cold water supply
to the mixing valve. Check the temperature to see if
the replacement cartridge is operating correctly. If the
temperature requires adjustment refer to the section
“Setting the Mixing Valve.”
20
40
60
80 100120
14 0
16 0
18 0
200
0
Cartridge Kit
Part Number 8334-50
Thermometer
Part Number 6679-00
Valve 1
(V1)