Kohler 744T(DC) Manual de usuario

-1-
ODEON
/
TOILET/SQUAT SENSOR
K-744T-C05(AC/ )
INSTALLATION INSTRUCTIONS
K-744T(DC/ )
·
·
·
Please read these instructions carefully to familiarize
yourself with the required tools, materials, and installation
sequences. Follow the sections that pertain to your
particular installation. This will help you avoid costly
mistakes. In addition to proper installation, read all
operation and safety instructions.
All information in these instructions is based upon the
latest product information available at the time of
publication. Kohler China reserves the right to make
changes in product characteristics, packaging, or
availability at any time without notice.
These instructions contain important care, cleaning, and
warranty information - please leave instructions for the
consumer.
·
·
·-
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
Open end/adjustable wrenches
Tape measure
Basin wrench
Pipe wrench
Square
Level
Pliers
Socket wrench with sockets
Philips driver
Seal tape
Special wrenches
Connection wire
Wire cutter
Insulation tape
Bushing
·
·
·
·
·
·
·
·
·
·
·
·
·
·
·
/
RECOMMENDED TOOLS AND MATERIALSRECOMMENDED TOOLS AND MATERIALS
SENSOR SPECIFICATIONSSENSOR SPECIFICATIONS
Model 744T(DC)/744T-C05(AC)
Power AAA size alkaline batteries( 2)(744T)
220V AC 50/60Hz (744T-C05)
744T( )/744T-C05( )
2 7 (AAA 2)(744T)
220V AC 50/60Hz (744T-C05)
0.10~0.55MPa
46811
: 1 ~55 1 ~45
0.05~0.86MPa
100cm ( )
3~8
G1 G1-1/2
24
0.1~0.55MPa
()
25mm
Liter per flushing Water pressure at 0.10~0.55 MPa: 4 L,
6 L, 8 L,11 L(adjustable)
Temperature Environmental temperature: 1 ~55
Water temperature: 1 ~45
Starting pressure 0.05~0.86MPa
Sensing distance
Flushing delay
Connect dimension
Protective flushing
Recommended
working pressure
3~8 seconds after user leave
Inlet pipe G 1 , Outlet pipe G 1-1/2 .
Auto flush once every 24h if unused
Sensor inlet dynamic pressure:
0.1~0.55MPa, recommended inner
diameter of water supply ( including
water meter, valve, etc. ) no less than
25 mm.
Within 100cm from sensing window
(along the direction of transmitting angle)
, 2007
Copyright Kohler China Ltd., 2007
18 E 201206
1046837-T01-D

1.
2.
3. 27
37
4. ( K-8750 )
5. K-4330 K-8750
L 70cm
6.
7.
8.
o
o
30cm 30cmNote: 1. The sensing distance in the table is measured with a
30 30cm white or black board as the reflecting
surface.
2. The user may set the amount of water per flush
according to the specifications of the specific toilet.
4. To ensure an effective flushing preformame, please
turn the adjusting bolt properly according to actual
using conditions when the product is used with toilet
( such as K-8750, etc.)
2
3 .The infrared transmiting angle is 27 downward , 37
when used with angle-comerting piece.
.
oo
5 The angle-converting piece is used only with K-4330,
K-8750 or for toilets with the length less than 70cm.
6. Do not discard the special wrench when the
installation is complete. It will be helpful for qualified
maintenance personnel to repair the outlet
connection assembly and the vacuum breaker.
7. Setup switch unit is used only during the setup of
flash volume.
8. The slurry mold is used only when install the valve
box.
-2-
1046837-T01-D

-3-
PRODUCT PAGE
O-Ring
O
11
Main Valve
Core Assy.
Spring
Check Valve Cover
2
Sensor Lens 8
Bracket, Button
Battery Box Assy.
744T Use Only
744T
5
*Angle-Converting
Piece, Optional
Control Box
Fixed Plate
3
Control Box a Assy.
W/Battery Box
9
Fixed Plate Assy.
Manual Lever Assy.
Manually
Operated Line
Outlet Shield
Valve Body
Inlet Connection Assy.
*Special Wrench
*
26
*Switch Assy.
*
Sealing
Shield
Adjustment Nut
Filter Cover
10
Main Filter
Filter Assy.
Screws
Pressing Board
1
Cover
6
Button
Bracket, Battery Box
*
19
Manual Valve
Cover Assy. Driving Valve Assy.
15
Solenoid
Valve Assy.
13
Double Head
Valve Cover
17
Membrane Assy.
16
Membrane Spring
Main Check
Valve Spring
Stop Valve Assy.
Double Valve Core Assy.
Valve Core
Cover
W/O-Ring
( O-Ring)
Outlet Connector
Assy.
Angle
Screws
Screws
Screws
Screws
Screws
Valve Core
Membrane
Screws
Screws
12
Valve Core
Membrane
Center Unit Assy.
Screws
Screws
Screws
7
Spring, Button
20
Sealing Bracket Assy.
Filter
18
Membrane Bracket,
W/ O-Ring
*Slurry Mold
*
Valve Box
O-Ring
O
O-Ring
O
Straightening
Device-1
-1
22
Turbine Assy.
21
Hall Hook Assy.
23
Hall Box Assy.
Speed Detector
Connector(Three-Pin)
()
24
Vacuum
Breaker Assy.
25
O-Ring
O
Speed
Detector
Assy.
Outlet Pipe
4
14
.1046367-SC/CP 1046368 1046369 1046371 1046372 1046377-SC/CP 1046378 1046379 1046382
123456789
.1046394 1346399 1046400 1046403 1045457 1045452 1046404 1046405 1046406
10 11 12 13 14 15 16 17 18
.1046407 1046408 1046414 1046415 1046416 1046417 1046419 1046424
19 20 21 22 23 24 25 26
AC
16306T-NA
744T-C05 Use Only
744T-C05
Connector
1046837-T01-D

-4-
ROUGHING-IN
UNIT: mm
Table of installation positions for toilets (Used with K-4350, K-4368, K-4349, K-4367)
( K-4350, K-4368, K-4349, K-4367)
L
H
700 L 730
640 H 670 670 H 700 700 H 730 730 H 760 760 H 790
730 L 760 760 L 790 790 L 820 820 L 850
K-4350
K-4368
K-4349
K-4367
105+30
0158
H
158
L
CL OF OUTLET
G1-1/2 SPUD
G1-1/2
G1-1/2
105+30
0
158
158
L
CL OF OUTLET
H
G1-1/2
G1-1/2 SPUD
G1-1/2
105+30
0158
H
158
CL OF OUTLET
L
G1-1/2
G1-1/2 SPUD
G1-1/2
K-4330 K-8750
Used with K-4330, K-8750, or when toilet installation length less than 70 cm, must install angle-converting piece.
K-4330, K-8750 L 70cm,
L
H
540 L 570
570 H 600 600 H 630 630 H 670 670 H 700 700 H 740
570 L 600 600 L 630 630 L 660 660 L 700
H
158
158
G1-1/2
CL OF OUTLET
L
105+30
0
1046837-T01-D

+30
0
105
H
L
a. L H
b. L H
e.
c. 540 L 850
2430T-NA
2429T-NA 2429T-
SA-NA
d. K-4330, K-8750
L 700mm (
H)
Notice: a. To ensure sensing effect, the dimensions
for L & H should be strictly observed.
b. Do not use if dimension for L and H is not
in table.
c. When toilet length between 540mm and
850mm, please use 2430T-NA as top inlet,
please use 2429T-NA as rear inlet; When
squat, please use 2429T-SA-NA as rear
inlet.
d. When used with K-4330, K-8750 or toilet
installation length less than 700mm, please
use angle-converting piece. (See step H)
e. To comply with above tables, you may cut
either end of the connecting pipe.
-5-
Table of installation positions for squats
CL OF OUTLET
L
H
700 L 730
640 H 670
730 L 760
670 H 700
760 L 790
700 H 730
790 L 820
730 H 760
820 L 850
760 H 790
1046837-T01-D

-6-
INSTALLATION
1
Notice:
.
a.
See the figure
right for rough-in dimension requirement.
While installing 744T-C05(AC),chisel out the slot indicated
in the dot line area of figure right for installation of bushing.
Determine the installation location per rough-in dimensions
and the table of installation position. Chisel out a slot and
install the supply tubes. Then flush the supply tubes. The
depth of the slot is not less than 105 mm, see the figure to
the right for rough-in dimension requirement.
Installation that fails to accord with the
installation position or rough-in dimensions
may result in false operations or no
operations.
b. No light shall enter or be reflected into the
sensing window.
c. reflectible objects in front of the sensing
window (e.g., mirror, polishing stainless
steel and some other polished plates).
d. trong ultraviolet radiation or
electromagnetic field nearby.
No
No s
1.
105mm
744T-C05( )
a.
b.
c. (
)
d.
Supply Tube (recommended inner
diameter is more than 25 mm)
( 25mm)
Battens
Nut
2. Remove the dust-proof cover from the inlet connection of
the flushing valve. Then place the flushing valve into the
slot, adjust its level and square with battens and connect
the inlet tubes. Screw down the nut at the outlet position.
Refer to the specific rough-in of different toilets/squats for
the connection of outlet fittings.(You need to flush the pipe
before connect to the toilet sensor.)
2.
/
(
)
58
Installation Side
100
100
100 100
130 130
Install bushing
Connector
Connect control box while
installing 744T-C05
744T-C05
Connect DC wiring terminal
Outer diameter of bushing
is no more than 25mm
25mm
1046837-T01-D

Please directly reference to Step 3 when installing 744T
(DC).
Please match 16306T-NA AC power unit when installing
744T-C05 (AC).
a. Outlet of AC power unit upward prohibited.
b. Do not connect 220V AC power supply to DC wiring
terminal.
c. Do not damage the covering of AC power unit or
remove screws to avoid leakage.
CAUTION:
744T( ) 3
744T-C05( ) 16306T-NA
a.
b. 220V
c.
A.1
A. Fig. #1: AC power unit connected to electric control box by
connection wire.
B. When installing the power unit on the ceiling, please layout
bushing according to Fig. #2 and thread wire through the
bushing.
Fig. #2: Connection sketch while installing power unit on the
ceiling.
One AC power unit can supply two sensors
at most.
CAUTION:
B.
2
-7-
Outlet downwards
Outlet upwards
Connect to
sensor
Connect to AC
Power supply
Connect to AC
Power supply
Connect to
sensor
AC
16306T-NA
AC Power Unit
Connector
Wire prepared
by customer
Connect with the same color ,
and protect connect area by insulation tape.
wire
Connector
Fig. #1
1
AC Power Unit Ceiling
Bushing
Fig. #2
2
1046837-T01-D

Notice: a. Because the installation position of the
sensor will affect directly to the future
operation of the sensor, you are
recommended to confirm the correction
position of the sensor after its placement
and fix it.
b. Don't mistake the direction of inlet and
outlet.
c. Don't drop the O-rings.
d. Keep the wire plug-in away from water.
e. Align the center of the flushing valve with
the center of the toilets/squats, and ensure
it parallel with the wall, or will result in the
false operation of the sensor.
f. Do not use any sealant or grease on the
valve or connector and outlet pipe.
g. While more than 3 sets of sensor were
installed in one lavatory, the inner diameter
of main inlet pipe should not be less than
38mm.
h. Do not connect the DC output of AC Power
unit to AC power supply.
i. Do not connect to power supply while
installing. Connection line is not supplied.
AC connection wire with insulating sleeving
is recommended. Wire of which the nominal
section area of conductor is not less than
0.5mm is also recommended. DC
connection line use wire of which the
nominal section area is not less than
0.3mm . It is cut according to acted
installation requirements(The length of cut
wire is recommended less than 10m).
j. The head AC power supply must be
protected with appropriate fuse.
k. Please confirm the AC power supply and
water supply should be shut off before
maintaining the products with AC power
related.
2
2
a.
b.
c.
d.
e. /
,
f.
g. 3
38mm
h.
i.
0.5mm
0.3mm
( 10m)
j.
k.
2
2
-8-
1046837-T01-D

-9-
4. When the slurry turns solid, remove the short screws, pull
out slurry mold, mount the bracket assembly, and secure
with long screws.
4.
Screws
M4 50
M4 50
3.
Notice:
Gently remove the manual device inside the plastic bag of
valve box and drive the flushing unit with manual lever
assembly. Once it is confirmed that there is no leakage
after the connection of supply tube, put the manual lever
assembly to its original place. Mount the slurry mold onto
the valve box and apply slurry into the crevice around the
valve box and smooth the surface.
a. Please confirm the completion of the outlet
connection or no leakage during the
application of water supply.
b. Please avoid breaking the manual lever line
during this procedure.
c. Avoid the plug-ins from wetting, or this will
result in false operations of the sensor.
Valve Box
Tiles
Slurry Mold
Push here to drive
Manual Lever Assy.
3.
a.
b.
c.
Slurry Mold
Screws
M4 10
M4 10
105+30
0
35
1046837-T01-D

-10-
5.
Notice: a. Don't twist, circle or pull the manual line to
avoid it from broken.
b. Don't adjust the screws on the manual
lever assembly, or it will affect the
operation of the assembly.
Mount the manual lever assembly onto the bracket with
screw.
Manual Lever Assy. Screws
5.
a.
b. ,
6.
Notice:
Don t connect to power supply while installing the cover.
Connect the solenoid valve connector and speed detector
on the control box with the corresponding cords
of the solenoid valve. Install the sensor cover with control
box as shown by the figure:
a. Buckle the sensor cover into the wall slightly above the
bracket assy.
b. Press the sensor cover down along the wall and fit
tightly into the bracket assy.
c. Push upward with basin wrench and rotate clockwise to
lock the sensor cover (rotate counterclockwise to
remove the sensor cover).
a.
b.
c. Prevent damage or drop of the cover or
break the cord during this procedure.
d. Please observe the indicator from the
bottom of the sensor cover upwards.
connector
connector
Ensure the tightness of the to
avoid them from wetting
Wear clean gloves when installing the
sensor cover to avoid surface injury by
cement or sand
.
.
'
a
b
Solenoid Valve
()
Connector
Speed Detector
()
Connector
Indicator
6. ,
a.
b.
c. (
)
a.
b.
c.
d.
c
90o
1046837-T01-D
Este manual sirve para los siguientes modelos
3
Tabla de contenidos
Otros manuales de Accesorios de Kohler

Kohler
Kohler K-4991X-ET Instrucciones de montaje

Kohler
Kohler K-EX27460T-NW-CP Manual de usuario

Kohler
Kohler 8787T-B01 Manual de usuario

Kohler
Kohler K-682 Instrucciones de montaje

Kohler
Kohler K-EX29936T-N-CP Manual de usuario

Kohler
Kohler Bardon K-8787T-C01 Manual de usuario

Kohler
Kohler GM88594-KP1-QS Manual de usuario

Kohler
Kohler K-8872T-C01 Manual de usuario

Kohler
Kohler PATIO K-8791T-YC01(0.5L/DC) Manual de usuario

Kohler
Kohler KARAT 72870T-ST Manual de usuario