AFS-G3
AFS-G3 K04/0422 page 3
2. Note
Please read these operating instructions carefully before unpacking and putting
the unit into operation. Follow the instruction precisely as described herein.
The instruction manuals on our website www.kobold.com are always for currently
manufactured version of our products. Due to technical changes, the instruction
manuals available online may not always correspond to the product version you
have purchased. If you need an instruction manual that corresponds to the
purchased product version, you can request it from us free of charge by email
serial number. If you wish, the operating instructions can also be sent to you by
post in paper form against an applicable postage fee.
The devices are only to be used, maintained and serviced by persons familiar
with these operating instructions and in accordance with local regulations
applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only then when the
machines fulfil the EC-machine guidelines.
3. Recommended usage
Any use of the AFS-G3 which exceeds the manufacturers specification, may
invalidate its warranty and any resultant damage therefore is not the responsibility
of the manufacturer. The user assumes all risk for such usage.
4. Operating Principle
The humidity annex switch, Model AFS-G3, serves to monitor condensed water
formation. The hygroscopic module of the measuring instrument is arranged on
an aluminum base plate so that the measuring element is near the mounting
plate. Protected by the housing, relative humidity close to the dew point allows
condensation to form inside. The aluminium base plate is close to the cooling
tube and transmits cooling energy to the measuring element. The measuring
point can be set inside. The threshold should be adapted for local conditions. The
microswitch trips a potential-free SPDT with silver contact plates rated max 2A /
48 V and 100 mA / 20 VAC/DC. The AFS requires no supply voltage.